BLDG1403-0165-Energy CalculationsFORM 405-10 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Street: City, State, Zip: Owner: Design Location: LH -C -ML 120 EXT 9598 TOWN PARC CIRCLE NORTH PARKLAND, FL, C EXT. MODEL LOT 1 BLOCK 5 @ TOWN PARC FL, Fort Lauderdale 1. New construction or existing 2. Single family or multiple family 3. Number of units, if multiple family 4. Number of Bedrooms 5. Is this a worst case? 6. Conditioned floor area above grade (ft2) Conditioned floor area below grade (ft2) 7. Windows(207.0 sqft.) Description a. U -Factor: Sgl, U=1.08 SHGC: SHGC=0.49 b. U -Factor: Sgl, U=1.08 SHGC: SHGC=0.38 c. U -Factor: Sgl, U=1.30 SHGC: SHGC=0.64 d. U -Factor: N/A SHGC: Area Weighted Average Overhang Depth: Area Weighted Average SHGC: 8. Floor Types (1251.0 sqft.) a. Slab -On -Grade Edge Insulation b. Raised Floor c. N/A Glass/Floor Area: 0.101 New (From Plans) Multi -family 1 4 No 2057 0 Insulation R=0.0 R=11.0 R= Area 168.00 ft2 24.00 ft2 15.00 ft2 ft2 1.645 ft. 0.488 Area 846.00 ft2 405.00 ft2 ft2 Builder Name: LENNAR HOMES Permit Office: Permit Number: Jurisdiction: 163100 9. Wall Types (2469.0 sqft.) a. Concrete Block - Int Insul, Exterior b. Concrete Block - Int Insul, Common c. Frame - Wood, Adjacent d. N/A 10. Ceiling Types (1243.0 sqft.) a. Under Attic (Vented) b. N/A c. N/A 11. Ducts a. Sup: Attic, Ret: Attic, AH: 2ND FLR HALL Insulation R=4.1 R=4.1 R=11.0 R= Insulation R=30.0 R= R= 12. Cooling systems a. Central Unit 13. Heating systems a. Electric Strip Heat 14. Hot water systems a. Electric b. Conservation features None 15. Credits Total Proposed Modified Loads: 46.88 Total Standard Reference Loads: 59.75 I hereby certify that the plans and specifications covered by this calculation are in compliance with the Florida Energy Code. PREPARED BY: DATE: I hereby certify that this building, as designed, is in compliance with the Florida Enqgy Code. OWNER/AGENT:' / DATE: 77/ y `1 Review of the plans and specifications covered by this calculation indicates compliance with the Florida Energy Code. Before construction is completed this building will be inspected for compliance with Section 553.908 Florida Statutes. BUILDING OFFICIAL: U>P t f DATE: c ©_ 14 Area 1497.00 ft2 729.00 ft2 243.00 ft2 ft2 Area 1243.00 ft2 ft2 ft2 R ft2 6 200 kBtu/hr Efficiency 37.0 SEER:16.00 kBtu/hr Efficiency 32.0 COP:1.00 Cap: 40 gallons EF: 0.920 Pstat PASS - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory -sealed in accordance with 403.2.2.1.1. - Compliance requires completion of a Florida Air Barrier and Insulation Inspection Checklist 1/13/2014 10:52 AM EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 1 of 7 Title: Building Type: Owner: # of Units: Builder Name: Permit Office: Jurisdiction: Family Type: New/Existing: Comment: LH -C -ML 120 EXT User C EXT. MODEL LOT 1 BLOC 1 LENNAR HOMES 163100 Multi -family New (From Plans) Design Location TMY Site PROJECT Bedrooms: Conditioned Area: Total Stories: Worst Case: Rotate Angle: Cross Ventilation: Whole House Fan: FL, Fort Lauderdale FL FORT LAUDERDALE Number Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 V Name Entire House Name DINING KITCHEN FAMILY LIVING ROOM STAIRS POWDER MASTER BED MASTER BATH WIC MASTER 2ND FLR HALL 116 BED SML CLOSET 180 BED W LRG CLOS 154 BACK BED BY MA 154 ADDED BATH FRO 54 BATH BY BACK BE 55 INT MASTER WIC 24 WIC AT BED 41 Area 2057 Area 242 270 263 33 39 270 132 30 # Floor Type 1 Slab -On -Grade Edge Insulatio 2 Slab -On -Grade Edge Insulatio 1/13/2014 10:52 AM Space IECC Zone 1 Volume 18876 4 2057 2 No 180 No No CLIMATE Address Type: Lot # Block/SubDivision: PlatBook: Street: County: City, State, Zip: Street Address 9598 TOWN PARC CIR BROWARD PARKLAND, FL, Design Temp Int Design Temp Heating Design Daily Temp 97.5 % 2.5 % Winter Summer Degree Days Moisture Range 43 91 BLOCKS SPACES Volume Kitchen Occupants 2178 No 0 2430 No 0 2363 No 0 660 No 0 347 No 0 2430 No 2 1188 No 0 270 No 0 1044 No 0 1620 No 1 1386 No 1 1386 No 1 486 No 0 497 No 0 216 No 0 367 No 0 FLOORS 70 75 321.5 60 Low Bedrooms Infil ID Finished Cooled Heated 4 1 Yes Yes Yes 1 No Yes Yes 1 No Yes Yes 1 Yes Yes Yes 1 No Yes Yes 1 No Yes Yes 1 No Yes Yes 1 No Yes Yes 1 No Yes Yes 1 Yes Yes Yes 1 No Yes Yes 1 Yes Yes Yes 1 Yes Yes Yes 1 Yes Yes Yes 1 No Yes Yes 1 No Yes Yes Perimeter Perimeter R -Value Area DINING KITCHE 1 ft 0 242 ft2 FAMILY 1 ft 0 270 ft2 Joist R -Value Tile Wood Carpet 0.5 0 0.5 0.5 0 0.5 EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 2 of 7 # Floor Type 3 Slab -On -Grade Edge Insulatio 4 Slab -On -Grade Edge Insulatio 5SIab-On-Grade Edge Insulatio 6 Raised Floor 7 Raised Floor 8 Raised Floor 9 Raised Floor # Type 1 Gable or Shed # Type 1 Full attic V • Ceiling Type 1 Under Attic (Vented) 2 Under Attic (Vented) 3 Under Attic (Vented) 4 Under Attic (Vented) 5 Under Attic (Vented) 6 Under Attic (Vented) 7 Under Attic (Vented) 8 Under Attic (Vented) 9 Under Attic (Vented) 10 Under Attic (Vented) 11 Under Attic (Vented) 12 Under Attic (Vented) Space LIVING ROOM 17 ft FLOORS Perimeter Perimeter R -Value Area STAIRS 3.5 ft POWDER 3.5 ft MASTER BATH ____ BED SML CLOSE __- BED W LRG CLO ADDED BATH FR Materials Barrel tile Ventilation Vented Roof Area 1310 ft2 Space STAIRS MASTER BED MASTER BATH WIC MASTER 2ND FLR HALL BED SML CLOSE BED W LRG CLO BACK BED BY M ADDED BATH FR BATH BY BACK INT MASTER WI WIC AT BED 0 262.5 ft2 0 33 ft2 0 38.5 ft2 17 ft2 180 ft2 154 ft2 54 ft2 ROOF Gable Roof Solar Area Color Absor. 206 ft2 Medium 0.9 ATTIC Joist R -Value 11 11 11 11 SA Tested Tile Wood Carpet 0.5 0 0.5 0.5 0 0.5 0.5 0 0.5 0.5 0 0.5 0.5 0 0.5 0.5 0 0.5 0.5 0 0.5 Emitt Emitt Deck Tested Insul. Pitch (deg) No 0.9 No 0 18.4 Vent Ratio (1 in) Area RBS IRCC 300 1243 ft2 N N CEILING R -Value Area 30 33 ft2 30 270 ft2 30 132 ft2 30 30 ft2 30 116 ft2 30 180 ft2 30 154 ft2 30 154 ft2 30 54 ft2 30 55 ft2 30 24 ft2 30 41 ft2 WALLS Framing Frac 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Truss Type Wood Wood Wood Wood Wood Wood Wood Wood Wood Wood Wood Wood Adjacent Cavity Width Height Sheathing Framing Solar Below To Wall TyRp Space R_vallIP Ft In Ft In Aran P -\/alit. Fraction Abcor Grade% 1 N=>S Exterior Concrete Block - Int InsfIINING KITC 4.1 22 0 9 0 198.0 ft2 0 0 0.5 0 Exterior Concrete Block - Int InsBIINING KITC 4.1 15 0 9 0 135.0 ft2 0 0 0.5 0 Exterior Concrete Block - Int Insul FAMILY 4.1 10 7 9 0 95.3 ft2 0 0 0.5 0 Exterior Concrete Block - Int InstilVING ROO 4.1 5 0 9 0 45.0 ft2 0 0 0.5 0 2 3 4 W=>E W=>E E=>W 1/13/2014 10:52 AM EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 3 of 7 1 1 WALLS / Adjacent Space Cavity Width Height Sheathing Framing Solar Belo w V # Ornt TO Wall Type R_\lalua Ft In F+ �n Area R -Value Fraction_ Ahsor Grade /o _ 5 N=>S Exterior Concrete Block - Int Insut STAIRS 4.1 20 0 9 0 180.0 ft2 0 0 0.5 0 _ 6 W=>E Exterior Concrete Block - Int InsMASTER BE 4.1 14 0 9 0 126.0 ft2 0 0 0.5 0 _ 7 N=>S Exterior Concrete Block - Int Ins81ED SML CL 4.1 11 0 9 0 99.0 ft2 0 0 0.5 0 8 E=>W Exterior Concrete Block - Int InsfdIED SML CL 4.1 10 7 9 0 95.3 ft2 0 0 0.5 0 9 E=>W Exterior Concrete Block - Int Ins81ED W LRG 4.1 5 0 9 0 45.0 ft2 0 0 0.5 0 _ 10 N=>S Exterior Concrete Block - Int Ins8IACK BED B 4.1 16 0 9 0 144.0 ft2 0 0 0.5 0 _ 11 W=>E Exterior Concrete Block - Int InsBIACK BED B 4.1 11 0 9 0 99.0 ft2 0 0 0.5 0 12 N=>S Exterior Concrete Block - Int InsLADDED BAT 4.1 8 7 9 0 77.3 ft2 0 0 0.5 0 _ 13 N=>S Exterior Concrete Block - Int InsEIATH BY BA 4.1 5 7 9 0 50.3 ft2 0 0 0.5 0 _ 14 E=>W Exterior Concrete Block - Int Instil/IC AT BED 4.1 12 0 9 0 108.0 ft2 0 0 0.5 0 _ 15 N=>S Neighbor Concrete Block - Int Ins[DIINING KITC 4.1 81 0 9 0 729.0 ft2 0 0 0.5 0 16 E=>W Garage Frame - Wood LIVING ROO 11 27 0 9 0 243.0 ft2 0 0 0.5 0 v DOORS # Ornt Door Type Space Storms U -Value Width Height Area Ft In Ft In 1 E=>W Wood LIVING ROO None .39 3 7 6 8 23.9 ft2 2 E=>W Wood LIVING ROO None .46 2.8 8 22.4 ft2 WINDOWS Orientation shown is the entered orientation (=>) changed to As Built (rotated 180 denrees). / Wall Overhang V # Ornt ID Frame Panes NFRC U -Factor SHGC Area Depth Separation Int Shade Screening 1 _ N=>S 1 Metal Single (Tinted) Yes 1.08 0.49 30.0 ft2 1 ft 6 in 11 ft 0 in None None 2 W=>E 2 TIM Single (Tinted) Yes 1.08 0.38 24.0 ft2 1 ft 6 in 11 ft 0 in None None . 3 W=>E 2 Metal Single (Tinted) Yes 1.08 0.49 30.0 ft2 1 ft 6 in 11 ft 0 in None None 4 W=>E 3 Metal Single (Tinted) Yes 1.08 0.49 30.0 ft2 1 ft 6 in 11 ft 0 in None None 5 N=>S 5 Metal Single (Tinted) Yes 1.08 0.49 6.0 ft2 1 ft 6 in 1 ft 0 in None None 6 W=>E 6 Metal Single (Tinted) Yes 1.08 0.49 30.0 ft2 1 ft 6 in 1 ft 0 in None None 7 N=>S 7 Metal Single (Tinted) Yes 1.08 0.49 6.0 ft2 1 ft 6 in 1 ft 0 in None None 8 E=>W 8 Metal Single (Tinted) Yes 1.08 0.49 15.0 ft2 2 ft 6 in 1 ft 0 in None None 9 E=>W 9 Metal Single (Tinted) Yes 1.08 0.49 15.0 ft2 2 ft 6 in 1 ft 0 in None None 10 N=>S 10 Metal Single (Tinted) Yes 1.08 0.49 6.0 ft2 1 ft 6 in 1 ft 0 in None None 11 W=>E 11 Metal Single (Tinted) Yes 1.3 0.64 15.0 ft2 1 ft 6 in 1 ft 0 in None None GARAGE # Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation 1 397 ft2 397 ft2 49 ft 9 ft 0 1/13/2014 10:52 AM EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 4 of 7 INFILTRATION # Scope Method SLA CFM 50 ELA EqLA ACH ACH 50 1 Wholehouse Best Guess .0003 1618.7 88.86 167.12 .2548 5.1473 HEATING SYSTEM # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Strip Heat None COP: 1 32 kBtu/hr 1 sys#1 COOLING SYSTEM V # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit None SEER: 16 37 kBtu/hr 1110 cfm 0.75 1 sys#1 HOT WATER SYSTEM V # System Type SubType Location EF Cap Use SetPnt 1 Electric None 2ND FLR HALI0.92 40 gal 60.9 gal 120 deg FSEC Cert # Company Name None None SOLAR HOT WATER SYSTEM System Model # Conservation None Collector Storage Collector Model # Area Volume FEF ft2 DUCTS # Location R -Value ---- Supply ---- Return ---- Air CFM 25 CFM25 HVAC # V lue Area Location Area Leakage Type Handler TOT OUT ON RLF Heat Cool 1 Attic 6 200 ft2 Attic 1 ft2 Default Leakage 2ND FLR H (Default) (Default) 1 1 TEMPERATURES Programable Thermostat: Y Ceiling Fans: Cooling Heating Venting Jan X) Jan Jan 1/13/2014 10:52 AM Feb [[ 1j Mar [ ] Apr 1 1 Mayn Jun n Jul ri Aug Sepj Oct 1 Nov Dec 'X) Feb [X] Mar [ ] Aprpf 1 MaJun Jul AuSe] Oct 'X1 Nov X Dec Feb [[Xjj Mar [X] A r [ ] May Jun Jul Aug Sep'X Oct X Nov Dec EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 5 of 7 FORM 405-10 Florida Code Compliance Checklist Florida Department of Business and Professional Regulations Residential Whole Building Performance Method I ADDRESS: 9598 TOWN PARC CIRCLE NORTH PERMIT #: PARKLAND, FL, MANDATORY REQUIREMENTS SUMMARY - See individual code sections for full details. COMPONENT SECTION SUMMARY OF REQUIREMENT(S) Air leakage 402.4 Thermostat & controls 403.1 Ducts 403.2.2 Water heaters Mechanical ventilation Swimming Pools & Spas To be caulked, gasketed, weatherstripped or otherwise sealed. Recessed lighting IC -rated as meeting ASTM E 283. Windows and doors = 0.30 cfm/sq.ft. Testing or visual inspection required. Fireplaces: gasketed doors & outdoor combustion air. Must complete envelope leakage report or visually verify Table 402.4.2. At least one thermostat shall be provided for each separate heating and cooling system. Where forced -air furnace is primary system, programmable thermostat is required. Heat pumps with supplemental electric heat must prevent supplemental heat when compressor can meet the load. All ducts, air handlers, filter boxes and building cavities which form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section 503.2.7.2 of this code. 403.3.3 Building framing cavities shall not be used as supply ducts. 403.4 Heat trap required for vertical pipe risers. Comply with efficiencies in Table 403.4.3.2. Provide switch or clearly marked circuit breaker (electric) or shutoff (gas). Circulating system pipes insulated to = R-2 + accessible manual OFF switch. 403.5 Homes designed to operate at positive pressure or with mechanical ventilation systems shall not exceed the minimum ASHRAE 62 level. No make-up air from attics, crawlspaces, garages or outdoors adjacent to pools or spas. 403.9 Cooling/heating 403.6 equipment Ceilings/knee walls 405.2.1 Pool pumps and pool pump motors with a total horsepower (HP) of = 1 HP shall have the capability of operating at two or more speeds. Spas and heated pools must have vapor -retardant covers or a liquid cover or other means proven to reduce heat loss except if 70% of heat from site -recovered energy. Off/timer switch required. Gas heaters minimum thermal efficiency=78% (82% after 4/16/13). Heat pump pool heaters minimum COP= 4.0. Sizing calculation performed & attached. Minimum efficiencies per Tables 503.2.3. Equipment efficiency verification required. Special occasion cooling or heating capacity requires separate system or variable capacity system. Electric heat >10kW must be divided into two or more stages. R-19 space permitting. 1/13/2014 10:52 AM EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software CHECK Page 7 of 7 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 78 The lower the EnergyPerformance Index, the more efficient the home. 9598 TOWN PARC CIRCLE NORTH, PARKLAND, FL, 1. New construction or existing 2. Single family or multiple family 3. Number of units, if multiple family 4. Number of Bedrooms 5. Is this a worst case? 6. Conditioned floor area (ft2) 7. Windows** Description a. U -Factor: Sgl, U=1.08 SHGC: SHGC=0.49 ,b. U -Factor: Sgl, U=1.08 SHGC: SHGC=0.38 c. U -Factor: Sgl, U=1.30 SHGC: SHGC=0.64 d. U -Factor: N/A SHGC: Area Weighted Average Overhang Depth: Area Weighted Average SHGC: 8. Floor Types a. Slab -On -Grade Edge Insulation b. Raised Floor c. N/A New (From Plans) Multi -family 1 4 No 2057 Insulation R=0.0 R=11.0 R= Area 168.00 ft2 24.00 ft2 15.00 ft2 ft2 1.645 ft. 0.488 Area 846.00 ft2 405.00 ft2 ft2 9. Wall Types a. Concrete Block - Int Insul, Exterior b. Concrete Block - Int Insul, Common c. Frame - Wood, Adjacent d. N/A 10. Ceiling Types a. Under Attic (Vented) b. N/A c. N/A 11. Ducts a. Sup: Attic, Ret: Attic, AH: 2ND FLR HALL Insulation Area R=4.1 1497.00 ft2 R=4.1 729.00 ft2 R=11.0 243.00 ft2 R= ft2 Insulation Area R=30.0 1243.00 ft2 R= ft2 R= ft2 R ft2 6 200 12. Cooling systems a. Central Unit 13. Heating systems a. Electric Strip Heat 14. Hot water systems a. Electric b. Conservation features None 15. Credits I certify that this home has complied with the Florida Energy Efficiency Code for Building Construction through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL Display Card will be completed based on installed Code compliant features. Builder Signature: Address of New Home: Date: f-5-1? TSN Pic CA2.eke_ City/FL Zip: pe ,a) ` t kBtu/hr Efficiency 37.0 SEER:16.00 kBtu/hr Efficiency 32.0 COP:1.00 Cap: 40 gallons EF: 0.92 Pstat *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at (321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section 303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Project Summary Entire House Lindstrom Air Conditioning 3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com Job: LH -C -ML Date: Mar 28, 2013 By: LINDSTROM Pro'ect Information For: LENNAR HOMES Notes: C MODEL MIRALAGO Desi • n Information Weather: Winter Design Conditions Outside db Inside db Design TD Heating Summary Structure Ducts Central vent (60 cfm) Humidification Piping Equipment load Infiltration Method Construction quality Fireplaces 50 °F 70 °F 20 °F 10275 Btuh 1166 Btuh 1313 Btuh 0 Btuh 0 Btuh 12755 Btuh Fort Lauderdale/Hollywood, FL, US Summer Design Conditions Simplified Average 0 Heating Cooling Area (ft2) 2056 2056 Volume (ft3) 18867 18867 Air changes/hour 0.32 0.16 Equiv. AVF (cfm) 101 50 Heating Equipment Summary Make RHEEM/RUUD Trade Model 7.5 KW AHRI ref Efficiency 100 AFUE Heating input 0 kW Heating output 0 Btuh Temperature rise 0 °F Actual air flow 1000 cfm Air flow factor 0.087 cfm/Btuh Static pressure 0 in H2O Space thermostat Outside db Inside db Design TD Daily range Relative humidity Moisture difference 90 °F 75 °F 15 °F L 50 % 61 gr/Ib Sensible Cooling Equipment Load Sizing Structure Ducts Central vent (60 cfm) Blower 20823 Btuh 1111 Btuh 985 Btuh 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 21773 Btuh Latent Cooling Equipment Load Sizing Structure Ducts Central vent (60 cfm) Equipment latent Toad Equipment total load Req. total capacity at 0.70 SHR Make Trade Cond Coil AHRI ref Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio 2902 Btuh 405 Btuh 2496 Btuh 5802 Btuh 27575 Btuh 2.6 ton Cooling Equipment Summary RHEEM/RUUD 14AJM30A01 "HLL-HM3617JA 16 SEER 19320 Btuh 8280 Btuh 27600 Btuh 1000 cfm 0.046 cfm/Btuh 0 in H2O 0.80 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft` Right -Suite® Universal 2012 12.1.07 RSU08398 S:\PROJECTS ENERGY\A- MANUAL J\LH-C-ML 120.rup Calc = MJ8 Front Door faces: N 2014 -Jan -13 13:14:54 Page 1 :,..ems.... 3581 W MCNAB RD, POMPANO 1 Room name 2 Exposed wall 3 Room height 4 Room dimensions 5 Room area Ty Construction number 6 111 1omo 1A-hlcs {�-Gp 11D0 V�1 13A-4ocs 11 1 �L_CC1A-hl-h1om 1A-hlom Fj 12B-Obw 11D0 C 16D-30td F 19A-llcscp F 22A -cpm 6 c) AED excursion Envelope loss/gain 12 a) Infiltration b) Room ventilation 13 Internal gains: Subtotal (lines 6 to 13) Less external load Less transfer Redistribution 14 Subtotal 15 Duct loads Total room load Air required (cfm) Right -J® Worksheet Entire House Lindstrom Air Conditioning BEACH, FL 33069 Phone: 954421-4117 Fax: 954-420-0064 Web: www.lindstromair.com U -value Or (Btuh/ft2-°F) Entire House 50.0 ft 9,2 ft 2056.0 ft2 HTM Area (ft2) Load Area (ft2) Load (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 0.143 e 2.86 2.81 293 239 684 672 0 0 0 0 1.270 e 25.40 60.62 30 13 762 1819 0 0 0 0 0.390 e 7.80 12.03 24 24 187 289 0 0 0 0 0.143 w 2.86 2.81 455 326 932 916 135 81 232 228 0.970 w 19.40 45.84 24 0 466 1100 24 0 466 1100 1.270 w 25.40 66.89 45 5 1143 3010 0 0 0 0 1.270 w 25.40 69.02 60 0 1524 4141 30 0 762 2071 0.097 - 1.94 1.03 235 213 413 220 0 0 0 0 0.390 n 7.80 12.03 22 22 172 265 0 0 0 0 0.032 n 0.64 1.10 1243 1243 796 1366 0 0 0 0 0.073 n 1.03 0.78 405 405 419 314 0 0 0 0 1.180 n 23.60 0.00 846 24 566 0 242 0 0 0 Job: LH -C -ML Date: Mar 28, 2013 By: LINDSTROM DINING KITCHEN 14.0 ft 9.0 ft heat/cool 22.0 x 11.0 ft 242.0 52 Occupants @ 230 4 Appliances/other 11% 2562 8063 16673 2212 829 0 0 920 2400 10275 20823 0 0 0 0 0 0 10275 20823 5% 1166 1111 11441 21934 1000 1000 1060 1459 4458 399 150 O 0 0 0 1200 1858 5808 0 0 O 0 O 0 1858 5808 -0% 0% 0 0 1858 5808 162 265 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft` Right -Suite® Universal 2012 12.1.07 RSU08398 S:\PROJECTS ENERGY\A- MANUAL J\LH-C-ML 120.rup Calc = MJ8 Front Door faces: N 2014 -Jan -13 13:14:54 Page 1 cill5934420Pat Right -J® Worksheet Entire House Lindstrom Air Conditioning 3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com 1 Room name 2 Exposed wall 3 Room height 4 Room dimensions 5 Room area Job: LH -C -ML Date: Mar 28, 2013 By: LINDSTROM FAMILY LIVING ROOM 10.0 ft 17.0 ft 9.0 ft heat/cool 9.0 ft heat/cool 15.0 x 18.0 ft 25.0 x 10.5 ft 270.0 ft2 262.5 ft2 Ty Construction U -value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A-4ocs 0.143 e 2.86 2.81 0 0 0 0 45 21 ' 60 59 p 1A-hlom 1.270 e 25.40 60.62 0 0 0 0 0 0 0 0 11D0 0.390 e 7.80 12.03 0 0 0 0 24 24 187 289 13A-4ocs 0.143 w 2.86 2.81 95 65 186 183 0 0 0 0 11 10A -b 0.970 w 19.40 45.84 0 0 0 0 0 0 0 0 1A-hlom 1.270 w 25.40 66.89 0 0 0 0 0 0 0 0 p 1A-hlom 1.270 w 25.40 69.02 30 0 762 2071 0 0 0 0 12B-Obw 0.097 - 1.94 1.03 0 0 0 0 153 131 254 135 0 1100 0.390 n 7.80 12.03 0 0 0 0 22 22 172 ' 265 C 16D-30td 0.032 n 0.64 1.10 0 0 0 0 0 0 0 0 F 19A-llcscp 0.073 n 1.03 0.78 0 0 0 0 0 0 0 0 F 22A -cpm 1.180 n 23.60 0.00 270 0 0 0 263 17 401 . 0 6 c) AED excursion Envelope loss/gain 12 a) Infiltration b) Room ventilation 13 Internal gains: Subtotal (lines 6 to 13) Less external load Less transfer Redistribution 14 Subtotal 15 Duct loads Total room Toad Air required (cfm) Occupants © 230 Appliances/other 692 -31 948 2945 1074 717 281 105 133 50 O 0 0 0 0 0 0 0 0 0 1229 3051 1207 767 O 0 0 0 0 0 0 0 O 0 0 0 1229 3051 1207 767 -0% 0% 0 0 -0% 0% 0 0 1229 3051 1207 767 107 139 106 35 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 444- wrightsoft® Right -Suite® Universal 2012 12.1.07 RSU08398 ACc-;A` S:\PROJECTS ENERGY A- MANUAL J\LH-C-ML 120.rup Calc = MJ8 Front Door faces: N 2014 -Jan -13 13:14:54 Page 2 Right -J® Worksheet Entire House Lindstrom Air Conditioning 3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com Job: LH -C -ML Date: Mar 28, 2013 By: LINDSTROM 1 Room name STAIRS POWDER 2 Exposed wall 3.5 ft 5.5 ft 3 Room height 20.0 ft heat/cool 9.0 ft heat/cool 4 Room dimensions 11.0 x 3.0 ft 7.0 x 5.5 ft 5 Room area 33.0 ft2 38.5 ft2 Ty Construction U -value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/PIS Heat Cool Gross N/P/S Heat Cool 6 1,0 13A flocs 0.143 e 2.86 2.81 0 0 0 0 0 0 0 0 1A-hlom 1.270 e 25.40 60.62 0 0 0 0 0 0 0 0 1100 0.390 e 7.80 12.03 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 2.86 2.81 0 0 0 0 0 0 0 0 11 I ---G 10A -b 0.970 w 19.40 45.84 0 0 0 0 0 0 0 0 1A-hlom 1.270 w 25.40 66.89 0 0 0 0 0 0 0 0 1A-hlom 1.270 w 25.40 69.02 0 0 0 0 0 0 0 0 12B-Obw 0.097 - 1.94 1.03 32 32 62 33 50 50 97 52 D 1100 0.390 n 7.80 12.03 0 0 0 0 0 0 0 0 C 16D-30td 0.032 n 0.64 1.10 33 33 21 36 0 0 0 0 F 19A-llcscp 0.073 n 1.03 0.78 0 0 0 0 0 0 0 0 F 22A -cpm 1.180 n 23.60 0.00 33 4 83 0 39 4 83 0 6 c) AED excursion -3 -2 Envelope loss/gain 166 67 180 50 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants © 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 166 67 180 50 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 166 67 180 50 15 Duct loads 20% 10% 33 7 -0% 0% 0 0 Total room load 199 73 180 50 Air required (cfm) 17 3 16 2 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft- Right -Suite® Universal 2012 12.1.07 RSU08398 ��p` S:IPROJECTS ENERGYIA- MANUAL J1L1-1-C-ML 120.rup Calc = MJ8 Front Door faces: N 2014 -Jan -13 13:14:54 Page 3 Right -J® Worksheet Entire House Lindstrom Air Conditioning 3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com 1 Room name 2 Exposed wall 3 Room height 4 Room dimensions 5 Room area Ty Construction number U -value Or (Btuh/ft2-°F) Job: LH -C -ML Date: Mar 28, 2013 By: LINDSTROM MASTER BED MASTER BATH 0 ft 0 ft 9.0 ft heat/cool 9.0 ft heat/cool 18.0 x 15.0 ft 12.0 x 11.0 ft 270.0 ft' 132.0 ft2 HTM Area (ft2) Load Area (ft2) Load (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross NIP/S Heat Cool 6 V60 13A-4ocs 0.143 e 2.86 2.81 0 0 0 0 0 0 0 0 IA-hlom 1.270 e 25.40 60.62 0 0 0 0 0 0 0 0 11 DO 0.390 e 7.80 12.03 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 2.86 2.81 126 96 275 270 0 0 0 0 11 I- G 10A -b 0.970 w 19.40 45.84 0 0 0 0 0 0 0 0 1A-hlom 1.270 w 25.40 66.89 30 2 762 2007 0 0 0 0 1A-hlom 1.270 w 25.40 69.02 0 0 0 0 0 0 0 0 12B-Obw 0.097 - 1.94 1.03 0 0 0 0 0 0 0 0 D 11D0 0.390 n 7.80 12.03 0 0 0 0 0 0 0 0 C 16D-30td 0.032 n 0.64 1.10 270 270 173 297 132 132 84 145 F 19A-11 cscp 0.073 n 1.03 0.78 0 0 0 0 17 17 18 13 F 22A -cpm 1.180 n 23.60 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion 712 -6 Envelope loss/gain 1209 3285 102 152 12 a) Infiltration 373 140 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 1 230 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1582 3655 102 152 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1582 3655 102 152 15 Duct loads 20% 10% 318 364 20% 10% 21 15 Total room load 1900 4019 123 167 Air required (cfm) 166 183 11 8 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft• Right -Suite® Universal 2012 12.1.07 RSU08398 S:\PROJECTS ENERGY\A- MANUAL J\LH-C-ML 120.rup Calc = MJ8 Front Door faces: N 2014 -Jan -13 13:14:54 Page 4 ARlaxec :,.8,0.0.... �, • C01.1111.1.. Right -J® Worksheet Entire House Lindstrom Air Conditioning 3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com 1 Room name 2 Exposed wall 3 Room height 4 Room dimensions 5 Room area Job: LH -C -ML Date: Mar 28, 2013 By: LINDSTROM WIC MASTER 2ND FLR HALL 0 ft 0 ft 9.0 ft heat/cool 9.0 ft heat/cool 5.0 x 6.0 ft 4.0 x 29.0 ft 30.0 fV 116.0 ft2 Ty Construction U -value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 e 2.86 2.81 0 0 0 0 0 0 0 0 1A-hlom 1.270 e 25.40 60.62 0 0 0 0 0 0 0 0 1100 0.390 e 7.80 12.03 0 0 0 0 0 0 0 0 VV��JJ 13A-4ocs 0.143 w 2.86 2.81 0 0 0 0 0 0 0 0 11 I- G 10A -b 0.970 w 19.40 45.84 0 0 0 0 0 0 0 0 1A-hlom 1.270 w 25.40 66.89 0 0 0 0 0 0 0 0 1A-hlom 1.270 w 25.40 69.02 0 0 0 0 0 0 0 0 FL___12B-Obw 0.097 - 1.94 1.03 0 0 0 0 0 0 0 0 L- D 1100 0.390 n 7.80 12.03 0 0 0 0 0 0 0 0 C 160-30td 0.032 n 0.64 1.10 30 30 19 33 116 116 74 128 F 19A-llcscp 0.073 n 1.03 0.78 0 0 0 0 0 0 0 0 F 22A -cpm 1.180 n 23.60 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion -1 -51 Envelope loss/gain 19 32 74 77 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 1200 Subtotal (lines 6 to 13) 19 32 74 1277 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 19 32 74 1277 15 Duct loads 20% 10% 4 3 20% 10% 15 127 Total room load 23 35 89 1404 Air required (cfm) 2 2 8 64 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. Wrightsoft" Right -Suited) Universal 2012 12.1.07 RSU08398 At -6k S:\PROJECTS ENERGYIA- MANUAL J\LH-C-ML 120.rup Calc = MJ8 Front Door faces: N 2014 -Jan -13 13:14:54 Page 5 CL41112111411:2„,"1". CONDITIOXIMO, Right -J® Worksheet Entire House Lindstrom Air Conditioning 3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com 1 Room name 2 Exposed wall 3 Room height 4 Room dimensions 5 Room area Ty Construction number U -value Or (Btuh/ft2-°F) Job: LH -C -ML Date: Mar 28, 2013 By: LINDSTROM BED SML CLOSET BED W LRG CLOSET Oft Oft 9.0 ft heat/cool 9.0 ft heat/cool 12.0 x 15.0 ft 14.0 x 11.0 ft 180.0 ft' 154.0 ft2 HTM Area (ft2) Load Area (ft2) Load (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 e 2.86 2.81 95 80 229 225 45 30 86 84 1A-hlom 1.270 e 25.40 60.62 15 3 381 909 15 3 381 909 11D0 0.390 e 7.80 12.03 0 0 0 0 0 0 0 0 13A-4ocs0.143 w 2.86 2.81 0 0 0 0 0 0 0 0 11 10A -b 0.970 w 19.40 45.84 0 0 0 0 0 0 0 0 1A-hlom 1.270 w 25.40 66.89 0 0 0 0 0 0 0 0 1A-hlom 1.270 w 25.40 69.02 0 0 0 0 0 0 0 0 tl 12B-Obw 0.097 - 1.94 1.03 0 0 0 0 0 0 0 0 1-p 11 DO 0.390 n 7.80 12.03 0 0 0 0 0 0 0 0 C 16D-30td 0.032 n 0.64 1.10 180 180 115 198 154 154 99 169 F 19A-11cscp 0.073 n 1.03 0.78 180 180 186 140 154 154 159 119 F 22A -cpm 1.180 n 23.60 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion Envelope loss/gain 12 a) Infiltration b) Room ventilation 13 Intemal gains: Occupants @ 230 Appliances/other Subtotal (lines 6 to 13) Less external load Less transfer Redistribution 14 Subtotal 15 Duct loads Total room load Air required (cfm) -69 -60 911 1402 725 1223 281 105 133 50 0 0 0 0 1 230 1 230 0 0 1192 1738 858 1502 0 0 0 0 0 0 0 0 0 0 0 0 1192 1738 858 1502 20% 10% 240 173 20% 10% 172 150 1432 1911 1030 1652 125 87 90 75 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft` Right -Suite® Universal 2012 12.1.07 RSU08398 ACt' S:\PROJECTS ENERGY1A- MANUAL J\LH-C-ML 120.rup Calc = MJ8 Front Door faces: N 2014 -Jan -13 13:14:54 Page 6 Right -J® Worksheet .,. Co.°,.,•., Entire House yule Lindstrom Air Conditioning 3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com 1 Room name 2 Exposed wall 3 Room height 4 Room dimensions 5 Room area Job: LH -C -ML Date: Mar 28, 2013 By: LINDSTROM BACK BED BY MAST ADDED BATH FRONT Oft Oft 9.0 ft heat/cool 9.0 ft heat/cool 14.0 x 11.0 ft 9.0 x 6.0 ft 154.0 ft2 54.0 ft2 Ty Construction U -value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 13A-4ocs 0.143 e 2.86 2.81 0 0 0 0 0 0 0 0 1A-hlom 1.270 e 25.40 60.62 0 0 0 0 0 0 0 0 D 11D0 0.390 e 7.80 12.03 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 2.86 2.81 99 84 240 236 0 0 0 0 11 I -C 10A -b 0.970 w 19.40 45.84 0 0 0 0 0 0 0 0 1A-h1om 1.270 w 25.40 66.89 15 1 381 1003 0 0 0 0 1A-hlom 1.270 w 25.40 69.02 0 0 0 0 0 0 0 0 12B-Obw 0.097 - 1.94 1.03 0 0 0 0 0 0 0 0 D 11D0 0.390 n 7.80 12.03 0 0 0 0 0 0 0 0 C 16D-30td 0.032 n 0.64 1.10 154 154 99 169 54 54 35 59 F 19A-11 cscp 0.073 n 1.03 0.78 0 0 0 0 54 54 56 42 F 22A -cpm 1.180 n 23.60 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion 345 -4 Envelope loss/gain 720 1754 90 97 12 a) Infiltration 293 110 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 1 230 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1013 2094 90 97 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1013 2094 90 97 15 Duct loads 20% 10% 204 209 20% 10% 18 10 Total room load 1216 2302 109 107 Air required (cfm) 106 105 9 5 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft• Right -Suite® Universal 2012 12.1.07 RSU08398 '��p` S:\PROJECTS ENERGY\A- MANUAL J\LH-C-ML 120.rup Calc = MJ8 Front Door faces: N 2014 -Jan -13 13:14:54 Page 7 :Olgzumajc t. Right -J® Worksheet •IN CONDITIONING. INC , Entire House Lindstrom Air Conditioning 3581 W MCNAB RD, POMPANO BEACH, FL 33069 Phone. 954-421-4117 Fax 954-420-0064 Web: www.lindstromair.com 1 Room name 2 Exposed wall 3 Room height 4 Room dimensions 5 Room area Job: LH -C -ML Date: Mar 28, 2013 By: LINDSTROM BATH BY BACK BED INT MASTER WIC Oft Oft 9.0 ft heat/cool 9.0 ft heat/cool 9.0 x 6.1 ft 6.0 x 4.0 ft 55.2 ft2 24.0 ft Ty Construction U -value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A flocs 0.143 e 2.86 2.81 0 0 0 0 0 0 0 0 1A-hlom 1.270 e 25.40 60.62 0 0 0 0 0 0 0 0 11D0 0.390 e 7.80 12.03 0 0 0 0 0 0 0 0 �_._r� 13A-4ocs 0.143 w 2.86 2.81 0 0 0 0 0 0 0 0 11 10A -b 0.970 w 19.40 45.84 0 0 0 0 0 0 0 0 1A-hlom 1.270 w 25.40 66.89 0 0 0 0 0 0 0 0 1A-hlom 1.270 w 25.40 69.02 0 0 0 0 0 0 0 0 12B-Obw 0.097 - 1.94 1.03 0 0 0 0 0 0 0 0 D 11D0 0.390 n 7.80 12.03 0 0 0 0 0 0 0 0 C 16D-30td 0.032 n 0.64 1.10 55 55 35 61 24 24 15 26 F 19A-llcscp 0.073 n 1.03 0.78 0 0 0 0 0 0 0 0 F 22A -cpm 1.180 n 23.60 0.00 0 0 0 0 0 0 0 0 6 c) AED excursion Envelope loss/gain 12 a) Infiltration b) Room ventilation 13 Internal gains: Subtotal (lines 6 to 13) Less external load Less transfer Redistribution 14 Subtotal 15 Duct loads Total room load Air required (cfm) Occupants @ 230 Appliances/other -2 -1 35 58 15 25 O 0 0 0 O 0 0 0 0 0 0 0 0 0 35 58 15 25 O 0 0 0 O 0 0 0 O 0 0 0 35 58 15 25 20% 10% 7 6 20% 10% 3 3 42 64 18 28 4 3 2 1 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft' Right -Suite® Universal 2012 12.1.07 RSU08398 S:\PROJECTS ENERGY- MANUAL J\LH-C-ML 120.rup Calc = MJ8 Front Door faces: N 2014 -Jan -13 13:14:54 Page 8 0244.....14,41.4oU4,•sa, 41.1• CONDMONIXO .C. • 14a4 1•11161.111•11.16 3581 W MCNAB RD, POMPANO 1 Room name 2 Exposed wall 3 Room height 4 Room dimensions 5 Room area Ty Construction number 6 1 13A-4ocs 1A-hlom 1100 13A -flocs 10A -b 1A-hlom 1A-hlom RL-3 12B-Obw 1100 C 16D-30td F 19A-llcscp F 22A -cpm 6 c) AED excursion Envelope loss/gain 12 a) Infiltration b) Room ventilation 13 Internal gains: Subtotal (lines 6 to 13) Less extemal load Less transfer Redistribution 14 Subtotal 15 Duct loads Total room load Air required (cfm) Right -J® Worksheet Entire House Lindstrom Air Conditioning BEACH, FL 33069 Phone: 954-421-4117 Fax: 954-420-0064 Web: www.lindstromair.com WIC AT BED 0 ft 9.0 ft heat/cool 6.0 x 6.8 ft 40.8 fe U -value Or HTM Area (ft2) Load (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S 0.143 e 2.86 2.81 108 1.270 e 25.40 60.62 0 0.390 e 7.80 12.03 0 0.143 w 2.86 2.81 0 0.970 w 19.40 45.84 0 1.270 w 25.40 66.89 0 1.270 w 25.40 69.02 0 0.097 - 1.94 1.03 0 0.390 n 7.80 12.03 0 0.032 n 0.64 1.10 41 0.073 n 1.03 0.78 0 1.180 n 23.60 0.00 0 Occupants @ 230 Appliances/other 108 0 0 0 0 0 0 0 0 Heat Cool 309 303 O 0 0 0 O 0 O 0 O 0 O 0 O 0 0 0 41 26 45 O 0 0 O 0 0 -18 335 330 319 120 0 0 0 0 0 654 450 0 0 0 0 0 0 654 450 20% 10% 132 45 786 495 69 23 Job: LH -C -ML Date: Mar 28, 2013 By: LINDSTROM Area Load or perimeter Gross NIP/S Heat Cool Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsoft" Right -Suite® Universal 2012 12.1.07 RSU08398 °'LX:41/4 S:\PROJECTS ENERGY\A- MANUAL J\LH-C-ML 120.rup Calc = MJ8 Front Door faces: N 2014 -Jan -13 13:14:54 Page 9 January 9, 2014 NODAL STRUCTURES, INC. Structural Engineering Consultants and Construction Inspectors City of Parkland Building Department 6600 University Drive Parkland, Florida 33067 Attention: Building Official Please be advised that Nodal Structures, Inc. shall supervise the setting and erection of trusses having a bottom chord in excess of 35' long or 6' high, including all permanent bracing, for the structure at the following location: Mira Lago at Parkland — by Lennar Homes. Lot: 1 Block: 5 Permit #: TBD Should you req 're additional information, please do not hesitate to contact our office. ,`•tt%% is liii,i Respe�.a ul y. ' �' ed,''•,� No kOtr•i,� res �nc..••' %. Ct1 SA. 'oda P.E., S.l:.0 StSt- df. F orida i etiged• essional Engineer: 0049285 Stae44 lorida,gicensgif ' ' shold/Special Inspector: 001093 . ES111T111(1:1\1'40‘%% 10316 N.W. 55th Street, Sunrise, Florida 33351 Phone: (954) 741-2572 Fax: (954) 741-8635