2012100260-EngineeringHerman Eilberg Contractor, Inc
February 5, 2015
City of Parkland
6660 University Dr.
Parkland, FL 33067
Attn: Building Department
Re: Permit # 2012100260- 6019 NW 69th Way
Insulation Certification
sc
Let this letter serve as notification and certify that the insulation installed within the property
listed above regarding the permit in question was installed per Florida Building Code. Attic and
ceiling insulation installed was R-30 BATT insulation. Wall insulation was Fi-Foil VR Plus Shield
rated up to R-7.1 on 1.5" furring. The insulation was inspected by the Parkland building
department and was found to be satisfactory.
Please feel free to call 561-289-9853 with any questions or concerns.
At Your Service,
C. -I\.TED
FEB 10 2015
FEB 10,.
Engineer's Inspection Certification for Engineered Unit Masonry
9/5/13
City of Parkland
6600 University Drive
Parkland, FL 33067
RE: Lot ! 41-G Block Subdivision ��t�lrTR STQS
Street address (oc )'1 N WAY
Contractor
Peiuiit number ,20?X i 002,0
I have personally inspected the entire engineered unit masonry system for this building. At the time of
inspection, all concrete had been placed. Some reinforcement was still visible and size and spacing
corresponded with the contract drawings. Spacing of the masonry knockouts measured per contract
drawings. Reinforcement was provided at edges of all openings. Horizontal joint reinforcement was
visible in some locations where openings not finished.
I find that all aspects of this system conform to the '`Approved Plans" and the Florida Building Code.
Sincerely,
9./
William Erik Genz, P. E.
7/26/2013
To whom it may concern
The purpose of this letter is to specify that a precast lintel will be used instead of the concrete tie beam
located under the raked gable end for the O'Dwyer residence located at 6019 Northwest 69th Way,
Parkland. Florida (permit # 2012100260).
Please call me at 561-313-5251 if you have any questions.
Sincerely,
William Erik Genz, P. E.