HomeMy WebLinkAbout2007010096-Product Approval114 - Checklist Print
PERMIT NUMBER: 2007010096
N/A 9/28/2007 BLD15 **FOR MASONRY FENCE Foundation Size 1819.2 &
Reinforcement 1819.3; Walls - Reinforcement; Beams
- prescriptive 2121; Beams - unit masonry 2122;
Top of footer depth below grade 16" 1819.2.3
NO 9/28/2007 BLD15 **FOR CHAIN LINK FENCE See Table 2224
SEE N N€ eC 3
N/A 9/28/2007 BLD15 **FOR WOOD FENCE 2328: maximum 6' high by this
section may be designed for 75mph fastest mile or
90mph 3 -second gust 1611.2.1; 4 x 4 posts
embedded 2' into concrete footing 10" in diameter,
Lumber grade #2 or better 2328.2
N/A 9/28/2007 BLD15 Wood Fence footing o/c spacing for fence
6' high is 4' o/c; 5' high 5' o/c; 4' high 6' o/c
2328.3; posts of naturally durable or pressure
treated 2326.1
N/A
N/A
N/A
N/A
9/28/2007 BLD15 **ALUMINUM RAILING
9/28/2007 BLD15 6. RETAINING WALL 1832
9/28/2007 BLD15
7. PERMIT TO RELOCATE POOL SAFETY BARRIER FENCE:
Protection needs to be shown for windows and doors
opening out to pool deck area, or child barrier
around pool 360 degrees, if fence is relocated
from original approved position.
9/28/2007 BLD15 8. Plans Examiner: IF pool barrier fence is
inclusive of "existing" fence section(s), fence
contractor to CERTIFY that the existing portion(s)
of fence comply with the requirements for the pool
barrier based on a site visit, site-specific to
this permit
City of Parkland Printed on 9/28/2007 4:47:20PM
CD -Plus for Windows 95/98/NT Page 2 of 3 Printed By:ADM09
N/A
- Checklist Print PERMIT NUMBER: 2007010096
9/28/2007 BLD15 9. Plans Examiner: For retrofit of a fence to
existing pool finaled before the pool safety
barrier requirements, effective date of 10-01-00,
please mark the plans to indicate to inspector
that replacement fence does not need to comply
with the safety act.
INFO 9/28/2007 BLD15 Updated 10-12-04
City of Parkland Printed on 9/28/2007 4:47:20PM
Page 3 of 3 Printed By:ADM09
CD -Plus for Windows 95/98/NT
PERMIT NBR:
2007010096
CITY OF PARKLAND
BUILDING DEPARTMENT
INSPECTION HISTORY PRINT
JOB DESC: SITE WORK - SITE LIGHTING. LANDSCAPING.
JOB LOCATION: 9909 OLD CLUB RD
SUBDIVISION:
MASTER NBR:
WATER:
OWNER NAME:
CERT NBR:
1063 / PARKLAND GOLF & COUNTRY CLUB - GOLF C BLOCK:
2007010096 UNIT: TRACT: 105
SEWER: COA:
TOLL PARKLAND GSC LLC
7474 DBA: TOLL ORLANDO LIMITED PARTNERSHIP
CONTACT PHONE:
CONTACT NAME:
IMPORTANT DATES:
APPLICATION
1/9/2007
DIRECTIONS:
ADDTL INFO:
SUBCONTRACTORS
CERT NBR
SUBPERMITS
PERMIT NBR
2007010096
2007010105
2007010107
2007010108
2007010109
200701011,0-
2007080408
2007090222
2011050309
2012010043
FLOOD ZONE:
APPROVAL
8/29/2007
SUB STATUS
ISSUED
8/29/2007
IRR STATUS:
LOT:
TAZ:
AH
INSPECT
JOB PHONE: (561)637-8890
JOB VALUE:
CO EXPIRATION CANCEL
6/28/2012
START DATE END DATE STATUS
STATUS TYPE
INSPECT CS
CANCEL EL
VOID PL
ISSUED LS
ISSUED SK
MP
FN
-APPLY
APPLY/
CANCEL
CANCEL EL
ISSUED EL
City of Parkland
SUB CLASS DBA
$1,500,000.00
EXTENDED
EXPIRATION
5/12/2009
CERT NBR DBA JOB DESC
(7:47,4 TO LL'ORLANDQ LIMITED SITE WORK - SITE LIGHTING, LANDSCAPID
5567 THOMPSON ELECTRICAL IN ELEC SUB
7474 TOLL ORLANDO LIMITED P LANDSCAPING (C OF C FROM WCI TO TOLL)
318 AQUAMATIC SPRINKLER SY IRRIGATION - EXISTING PUMP
6357 WCI COMMUNITIES INC
1667 COMET FENCE CORP
7608 DEL AIR ELECTRICAL SER COC
7559 CARNEY ELECTRIC INC COC
( FOR DUMPSTER
RETAIING WALL DUE TO CHANGE IN GRADE
TEMPORARY CHAIN LINK AROUND CLUBHOUSE
5 -?e 6 a 3
) 6
Printed on: 4/4/2012 3:54:45PM
CD -Plus for Windows CDPR2036 Page 1 of 3 Printed By: ADM02
FEES
FEE CODE STATUS
BRWD POSTED
PLRST POSTED
RECRE2 POSTED
RECRE3 POSTED
STRCT POSTED
ZONE2 POSTED
CHG01 POSTED
RPCD POSTED
VIOLATI POSTED
RENW POSTED
PARTP POSTED
PARTP POSTED
CHG01 POSTED
RPCD POSTED
PARTP POSTED
EXTEND POSTED
CHG01 POSTED
RPCD POSTED
DESCRIPTION
BROWARD COUNTY SURCHARGE
PLAN REVIEW STRUCTURAL
LARGE SHEET SURCHARGE
COMMERCIAL RECORDS STORAGE
STRUCTURAL
ZONING REVIEW
CHANGE OF CONTRACTOR
REPLACEMENT CARD
FNL INSP REQUIRED WRK DONE
EXPIRED PERMIT RENEWAL
PARTIAL INSPECTION FEE PL
PARTIAL INSPECTION FEE PL
CHANGE OF CONTRACTOR
REPLACEMENT CARD
PARTIAL INSPECTION FEE PL
PERMIT EXTENSION
CHANGE OF CONTRACTOR
REPLACEMENT CARD
REQ CLASS DESCRIPTION/REMARKS
260 EL
101 ST
181 ST
441 PL
441 PL
441 PL
441 PL
441 PL
441 PL
441 PL
441 PL
441 PL
441 PL
903 EN
903 EN
30 DAY FOR TESTING
NOTICE OF COMMENCEMENT
SIDEWALK
AMOUNT DUE
525.00
330.00
15.00
95.00
2,020.00
70.00
60.00
20.00
200.00
1,010.00
60.00
70.00
60.00
20.00
70.00
70.00
90.00
25.00
ENTER DATE
8/21/2007
8/21/2007
8/21/2007
8/21/2007
8/21/2007
8/21/2007
1/28/2008
1/28/2008
3/3/2008
3/10/2008
6/12/2008
8/27/2008
9/16/2008
9/16/2008
11/13/2008
2/4/2009
1/18/2011
1/18/2011
PRI REQ DATE RESULT CODE RES DATE INSPECTOR
0
1 9/6/2007 40
1 7/22/2011 90
IRRIGATION - ROUGH 1 5/8/2008 91
inspected 3" main from entrace to around the building to the right
of building 5/8/08
inspection 1 of 15
IRRIGATION - ROUGH 1 5/30/2008 91
THIS IS A REINSPECTION inspection 2 of 15
inspected main from rear by bridge to lest side of building rps
IRRIGATION - ROUGH 1 6/12/2008 91
THIS IS A REINSPECTION ne back of building to east side to south
IRRIGATION - ROUGH 1 8/27/2008 91
THIS IS A REINSPECTION
THIS IS A REINSPECTION north east back of building to east side
partial fee applied.
far suth from bldg.partil fee applied
IRRIGATION - ROUGH 1 11/13/2008 91
THIS IS A REINSPECTION
main tie in at rear of bldg. (will need pressure test on main)
IRRIGATION - ROUGH 1 2/8/2011 91
THIS IS A REINSPECTION
(will need pressure test on main)
IRRIGATION - ROUGH 1 2/10/2011
THIS IS A REINSPECTION
IRRIGATION - ROUGH 1 7/1/2011
THIS IS A REINSPECTION
IRRIGATION - ROUGH 1 12/14/2011
THIS IS A REINSPECTION
IRRIGATION - ROUGH 1 2/16/2012
THIS IS A REINSPECTION
ENG SIDEWALK / CURBS 1 7/22/2011
ENG SIDEWALK / CURBS
9/6/2007
7/25/2011
5/8/2008
PAID DATE
8/29/2007
8/29/2007
8/29/2007
8/29/2007
8/29/2007
8/29/2007
1/30/2008
1/30/2008
3/10/2008
3/10/2008
6/13/2008
12/4/2008
9/16/2008
9/16/2008
12/4/2008
2/4/2009
1/18/2011
1/18/2011
ADM02
BLD25
PLB05
just past the bridge in rear
5/30/2008 PLB05
5/30/08
6/12/2008 PLB04
east side partial.
8/27/2008 PLB04
to south east side partial.
11/13/2008 PLB04
2/8/2011 MECO5
91 2/10/2011 MECO5
91 7/5/2011 MECO5
91 12/14/2011 MECO5
90 2/16/2012 MECO5
8/8/2011 ENG09
1 8/15/2011 90I 8/15/2011 ENG05
91
City of Parkland Printed on: 4/4/2012 3:54:45PM
CD -Plus for Windows CDPR2036 Page 2 of 3 Printed By: ADM02
269 EL
269 EL
269 EL
270 EL
270 EL
270 EL
237 EL
237 EL
271 EL
279 EL
279 EL
455 PL
503 LS
703 ST
703 ST
902 ST
902 ST
999 PT
THIS IS A REINSPECTION
TIERRA conducted the Field Testing on Monday, August 15th 2011 @ 9:00 am
The Modified Protor Test (T-180) RESULTS = 122pcf ® 10.0% Optimum Moisture
Density for Compaction had to reach 98% for a "PASSED" value.
Field Test #1 - 125pcf @ 10.1% optimum moisture; 102.4% (PASSED)
Field Test #2 - 117pcf (4) 7.5% optimum moisture; 95.6% (test FAILED)
Field Test #3 - 123.4pcf @ 8.0% optimum moisture; 101.1% (PASSED)
Concrete to be poured within the next 24 - 48hrs as per TIERRA convesation with General
Contractor.
LIGHT POLE BASE INSTALLATION 3 3/16/2012 81
no plans on site
LIGHT POLE BASE INSTALLATION 3 3/19/2012 74
THIS IS A REINSPECTION
need revised plans
LIGHT POLE BASE INSTALLATION 3 3/30/2012
THIS IS A REINSPECTION
PARKING AREA U.G ROUGH 3 3/16/2012
no plans on site
PARKING AREA U.G ROUGH 3 3/19/2012
THIS IS A REINSPECTION
need revised plans
PARKING AREA U.G ROUGH 3 3/30/2012
THIS IS A REINSPECTION
SITE LIGHTING 7
THIS IS A REINSPECTION
IGHTING 7 3/30/2012
fron
-7'1`v e FINAL
HOTOMETRIC CERTIFICAT
TH
S A REINSPECTION
PHOTOMETR ION
pending signed, sealed report
7
7
3/16/2012 ELE06
3/22/2012 ELE02
50 3/30/2012 ELE02
81 3/16/2012 ELE06
74 3/22/2012 ELE02
90 3/30/2012 ELE02
91 3/30/2012 ELE02
7 4/3/2012 91
IRRIGATION - FINAL 7 4/5/2012
.day �,c� - �e�„ o .lan for new location fo tie into supply
7
FINAL FENCE
THIS IS A REINSPECTION
for dumpster gate
4-3-12 Gates not inst
FINAL FENCE
for dumpster gat
car, no
AP RAMP
lled
THIS IS A PECTION
Dectable warnings required
HANDICAP RAMP
Dectable warnings required
FINAL INSPECTION
lled
to be
to be
7
7 4/3/2012 81
7
completed at
7
completed at
9
front entry of building.
4/3/2012 81
front entry of building.
4/3/2012 ELE02
4/3/2012 BLD16
4/3/2012 BLD16
City of Parkland Printed on: 4/4/2012 3:54:45PM
CD -Plus for Windows CDPR2036 Page 3 of 3 Printed By: ADM02
Ch; cklist Print
CDPR1014 - Checklist Print
PLAN.MP - MISCELLANEOUS STRUCTURAL - RETAINING WALL
STATUS DATE USER
INFO 9/7/2007 BLD16
PERMIT NUMBER: 2007010096
ITEM
PLAN REVIEW BY: WTH
first review 9-7-07
NO 9/7/2007 BLD16 DESCRIPTION OF WORK: RETAINING WALL
YES
YES
YES
N/A
N/A
N/A
N/A
NO
Permit Application submitted for retaining wall
only
Plans submitted indicate several changes in plans
that affect other disiplines. Please see Item # 8
for further details.
9/7/2007 BLD16 1. 2 sets of plans signed and sealed by architect
or engineer.
Architect Steve Phil Sammons Regestered Landscape
Architect
Engineer Mark Leblanc P.E.
9/7/2007 BLD16 2. Site plan or survey.
New survey and Pages GR -1, PL -1, PL -2, PD -1, PD -2
and Engineering page 1 of 1 for retaining wall
submitted.
9/7/2007 BLD16 3. Check permit type; GC required to pull permit?
9/7/2007 BLD16 4. If on septic tank, Health Dept stamps for
addition.
9/7/2007 BLD16 5. DPEP stamps & form; Note this is mandatory for
CONSTRUCTION TRAILERS
9/7/2007 BLD16 6. Energy calculations for additions under air.
9/7/2007 BLD16 7. SHUTTERS OVER OPENINGS REQ.FOR ADDITIONS.
9/7/2007 BLD16 8. Items that require clarification or revision:
City of Parkland Printed on 4/5/2012 9:33:12AM
CD -Plus for Windows 95/98/NT Page 1 of 2 Printed By:ADM02
CDPR1014 - Checklist Print
56
p
3;• 2. w5
PERMIT NUMBER: 2007010096
1. New page CR -1 submitted shows 12 wide concrete
path
(cart path). and refers to civil drawings for
cross section. Please note: there is no cross
section for cart path in submitted plans or plans
in city file. Please note; this change is not
indicated on permit application.
2. Emergency turnaround area is not labeled on new
sheet GR -1 and has been moved further away from
building. on sheet GR -1 and new survey
submitted.Please note; this change has not been
indicated on permit application .
3. New landscape plans submitted . This change not
indicated on permit application.
4. New riser steps are shown on revised page GR -1
at pathway between clubhouse and cartpath. there
are no details for steps. This change not
indicated on permit application.
This change not shown on existing approved plans
on pages LA -1 and ADA -1.
5. length of Retaining Wall not shown on plans
6. Locations of 12 in. wide and 8 in. wide
retaining wall not shown on plans.
7. Depth of concrete for footers not shown on
plans. See engineering page.
8. Safeguards are required at retaining wall where
differences in level exceed 30 in. and are
required to be shown on plans FBC
1618.4.1
City of Parkland Printed on 4/5/2012 9:33:12AM
CD -Plus for Windows 95/98/NT Page 2 of 2 Printed By:ADM02
;hecklist Print
JPR1014 - Checklist Print
PLAN.ZNCOMM - ZONING CHECKLIST FOR COMMERCIAL
STATUS DATE USER
NO 1/26/2007 PLN05
PEND
PEND
PEND
PEND
PEND
PEND
PEND
PEND
PERMIT NUMBER: 2007010096
ITEM
1. FRONT SETBACK
does not match approved site plan.
2. SIDES SETBACK
3. REAR SETBACK
4. HEIGHT OF STRUCTURE
5. ZONING DISTRICT
6. DRIVEWAY LOCATION
7. WELL AND SEPTIC LOCATION
8. Check Legal Discription and address
9. review out buildings
T of Parkland Printed on 1/2 007 11:06:17AM
1us for Windows 95/98/NT Page 1 of 1 Pri e By:ADM09
:hecklist Print
2DPR1014 - Checklist Print
PLAN.ENGSFR - SFR DRAINAGE PTE & RANCHES
STATUS
PEND
PEND
DATE
1/11/2007
City of Parkland
CD -Plus for Windows 95/98/NT Page 1 of 1 Printed By:ADM09
USER
ENG03
PERMIT NUMBER: 2007010096
ITEM
1. PURSUANT TO PARKLAND CITY CODE 16-22 FOR
PINETREE NORTH & 16-42 FOR PINETREE SOUTH:
Architect's drainage plan submitted showing
drainage to sides and from front of property to
rear drainage swale, typical
1/11/2007
A Land Development/Engineering Permit is required
prior to issuance of a building permit. Please
contact the Public Services Department to process
the permit.
2. Easements: Pinetree, dedicated 5' side swale
easements and 17.5 dedicated drainage swale at
rear of property.
Printed on 1/26/2007 11:06:28AM
E?JkAMM
Consulting
Headauarters Office
1407 West Newport Center Drive
Deerfield Beach, FL 33442
954-949-2200
954-949-2201 FAX
August 2, 2007
City of Parkland
Building Department — Electrical Plans Review
6600 University Drive
Parkland, FL 33067
ATTN: STEVE MITCHELL
RE: PARKLAND GOLF AND COUNTRY CLUB
1.
Art Kamm, P.E.-LEED®
Bradly Brown, P.E.-LEED®
Rick Gonzalez
Lon T. Carter, P.E.
Mike Pella, P.E.
Scott Meriwether, P.E.
Nevena Parsons, P.E. - LEED®
Enrique Uribe, P.E.
Gordon Myers, P.E.- LEED®
Paul Bohres, P.E.
REVISION #2 DATED 08/02/07
Comment: Panel schedules for each panel including wire size and ocp FBC BCAP
104.6.4.8.1.
Response: Revised size of panel "LW1B", "LE1C: and "LE1AA". 5tAfecfaue
2. Comment: Provide detail for pole bases and handholds. (1) Provide dimensions for pole
with luminaire from grad. (2) provide base details.
Response: Provided required details. See revised Sheet E1.3.
3. Comment: Provide engineer's wind load cal for light poles. FBC Chapter 16 for hvhz.
Response: Shall be submitted by Contractor. See note indicated under "Decorative
Pole Detail" on Sheet E1.3.
If you have any questions or require additional information, please contact this office.
Sincerely,
KAMM CONSULTING, INC.
-67
Bill Weaver
Project Manager
BW:tas
Florida
6859 Belfort Oaks Place
Jacksonville, FL 32216
904-285-2009
904-285-3009 Fax
Florida
1408 Orange Avenue
Fort Pierce, FL 34950
772-595-1744
772-595-1745 Fax
2006-0313 (08.02.07)Rev 2 Itr.doc
BRANCH OFFICES
Florida
3808 Gunn Highway, Ste. C
Tampa, FL 33618
813-265-9550
813-963-3187 Fax
www.kammconsultino.com
Georgia
2050 Marconi Drive, Ste. 300
Alpharetta, GA 30005
770-752-7083
770-752-7084 Fax
Check ist Print
CDPR1014 - Checklist Print
PLAN.PLUMBING MISC - PLUMBING MISCELLANEOUS
STATUS DATE USER ITEM
3/23/2007 PLB04 1.
NEw 7.QAt4. FL )5 LE'5E4 Pm-Aclatt
City of Parkland
CD -Plus for Windows 95/98/NT
PERMIT NUMBER: 2007010096
Irrigation:
provide number of head
provide approval letter from Broward cty. for lake
usage for this area.
provide pump location for project
Printed on
Page 1 of 1
/2067 12:41:27P
nted By:ADM07
E?IRAMM
Consulting
Headquarters Office
1407 West Newport Center Drive
Deerfield Beach, FL 33442
954-949-2200
954-949-2201 FAX
Reply to: Deerfield Beach
July 5, 2007
Steve Mitchell
City of Parkland
Building Department — Electrical Plans Review
6600 University Drive
Parkland, FL 33067
Art Kamm, P.E.-LEED®
Bradly Brown, P.E.-LEED®
Rick Gonzalez
Lon T. Carter, P.E.
Mike Pella, P.E.
Scott Meriwether, P.E.
Nevena Parsons, P.E. - LEED®
Enrique Uribe, P.E.
Gordon Myers, P.E.- LEED®
Paul Bohres, P.E.
RE: PARKLAND GOLF AND COUNTRY CLUB SITE
PERMIT NUMBER: 2007010096
Below are our responses to Building Department comments pertinent only to our portion of the design of the
referenced project.
ELECTRICAL:
6. Comment: Provide short circuit analysis FBC BCAP 104.6.4.8.1.
Response: Provided short circuit analysis. See revised Sheet E1.1.
14. Comment: Provide detail for pole bases and handholes.
Response: Provided requested details. See revised Sheet E1.3.
15. Comment: Show compliance with Parkland lighting ordinance Sec.
statement of compliance.
Response: Added requested Note. See Sheet E1.2.
4-53; include positive
16. Comment: Provide engineer's wind load calc for light poles. FBC Chapter 16 for HVHZ.
Response: Added pole detail with Note. See Sheet E1.3.
21. Comment: Indicate compliance with Florida Energy Code requirements for electrical equipment.
Response: Added Note #11. See electrical specifications Part IC on Sheet E0.1.
Sincerely,
KAM ��I�ING, I C.
Bill eaver
Project Manager
BW:tas
Florida
6859 Belfort Oaks Place
Jacksonville, FL 32216
904-285-2009
904-285-3009 Fax
Florida
1408 Orange Avenue
Fort Pierce, FL 34950
772-595-1744
772-595-1745 Fax
2006-0313 (07.05.07) comments Itr.doc
BRANCH OFFICES
Florida
3808 Gunn Highway, Ste
Tampa, FL 33618
813-265-9550
813-963-3187 Fax
www.kammconsultina.com
Georgia
C 2050 Marconi Drive, Ste. 300
Alpharetta, GA 30005
770-752-7083
770-752-7084 Fax
Checklist Print
CDPR1014 - Checklist Print
PLAN.ELCOM - ELECTRIC COMMERCIAL
PERMIT NUMBER: 2007010096
STATUS DATE USER ITEM
YES 4/3/2007 ELE02 1. site plan showing locations of structures and
equip FBC BCAP 104.6.4.8.1
YES
YES
YES
N/A
YES
YES
YES
N/A
4/3/2007 ELE02 2. architect / engineer signature and seal FBC
BCAP 104.6.3.7
4/3/2007 ELE02 3. electrical floor plan matches structural
4/3/2007 ELE02 4. riser diagram showing size of service, feeder
wire and conduit, overcurrent protection and
grounding NEC 250 FBC BCAP 104.6.4.8.1
4/3/2007 ELE02 5. mech plans to match load calc, exhaust fans
located per mech plan
4/3/2007 ELE02 6. provide short circuit analysis FBC BCAP
104.6.4.8.1
4/3/2007 ELE02 7. load calculations for service and each panel
including general lighting load, equip and
required receptacles FBC BCAP 104.6.4.8.1
4/3/2007 ELE02 8. panel schedules for each panel including wire
size and ocp FBC BCAP 104.6.4.8.1
4/3/2007 ELE02 9. floor plan including location of all equip and
circuitry of all devices FBC BCAP 104.6.4.8.1
4/3/2007 ELE02 10. provide show window receptacles NEC 210.52
City of Parkland Printed on 6/7/2007 12:41:42PM
CD -Plus for Windows 95/98/NT Page 1 of 3 Printed By:ADM07
CDPR1014 - Checklist Print
N/A
N/A
N/A
N/A
YES
N/A
YES
PERMIT NUMBER: 2007010096
4/3/2007 ELE02 11. GFI where required (rooftop, AC equip,
kitchen, etc.) NEC 210.8
4/3/2007 ELE02 12. provide sign outlets with FEC compliant
timeclock NEC 600.5/ Florida Energy Code
4/3/2007 ELE02 13. provide relevant material and equip listing
4/3/2007 ELE02 14. provide detail for pole bases and handholes
4/3/2007 ELE02 15. show compliance with Parkland lighting ord Sec
4-53
include positive statement of compliance
4/3/2007 ELE02 16. provide engineer's wind load calc for light
poles FBC Chapter 16 for hvhz
4/3/2007 ELE02 17. verify fire -rating of electric rooms
4/3/2007 ELE02 18. provide ventilation for electric room
4/3/2007 ELE02 19. verify notes
4/3/2007 ELE02 20. seperate permit required for signs
4/3/2007 ELE02 22. verify panel locations and clearances
City of Parkland Printed on 6/7/2007 12:41:42PM
CD -Plus for Windows 95/98/NT Page 2 of 3 Printed By:ADM07
CDPR1014 - Checklist Print
PERMIT NUMBER: 2007010096
4/3/2007 ELE02 21. indicate compliance with Florida Energy Code
requirements for electrical equipment
City of Parkland
CD -Plus for Windows 95/98/NT
Printed on 6/7/2007 12:41:42PM
Page 3 of 3 Printed By:ADM07
The following are the responses to the City of Parkland Building Department
comments for Permit # 2007010096.
Fire Marshal
Water mains.
Fire Hydrant needs to be supplied with and 8" line up to the Hydrant. 8"x 6" Reducer has been
relocated. See Sheet C-3
Minimum Coverage
Over the Hydrant mains is 36" under roads. See Note on Sheet C-7
013 Provide Blue RPM's
In the middle of the drive -aisle next to the hydrant See Sheet C-2 and C-3
Ken Mason
5. FBC 1820.3.6: Slab for Dumpster to be minimum 1' larger on all sides than receptacle and
minimum 6" thick. See sheet C-5
1. Details provided on sheet C-5, however no dumpster location provided on site plan
Gates and Note added. See sheets C-1, C-2 and C-3
2. Note service yard area appears to be enclosed, however the building plans for the structure do
not show this as being the case. See Arch. For details
3. Please remove or void details on sheet C-5 which are not applicable to dumpster walls.
Note deleted and details have been removed. See sheet C-5 and C-7
--:Theckiist Print
CDPR1014 - Checklist Print
PLAN.FR - REVIEW FIRE MARSHAL
PERMIT NUMBER: 2007010096
STATUS DATE USER ITEM
INFO 5/9/2007 FRM02 PLAN REVIEW BY: BRUCE BOWERS
954-344-1077
5/9/2007 FRM02 1. WATER MAINS
Fire Hydrants need to supplied with an 8" line up
to the hydrant
5/9/2007 FRM02 2.MINIMUM COVERAGE
Over the hydrant mains is 36" under roads
5/9/2007 FRM02 3. PROVIDE BLUE RPM'S
In the middle of the drive -aisle next to the
hydrants.
City of Parkland Printed on 6/7/2007 12:41:35PM
CD -Plus for Windows 95/98/NT Page 1 of 1 Printed By:ADM07
Checklist Print
CDPR1014 - Checklist Print PERMIT NUMBER: 2007010096
PLAN.FBC:SITE COMMERCIAL - SITE PLANS COMMERCIAL PROJECT
STATUS DATE USER
YES 6/7/2007 BLD15
YES
YES
YES
N/A
N/A
ITEM
PLAN REVIEW BY: KRM #HOURS 4
6/7/2007 BLD15 1. Two Sets Signed and Sealed Plans showing all
buildings and facilities on property
Engineering plans by John R McKune, PE sealed
7/31/06
Landscape plans by Steve Paul Sammons, Landscape
architect sealed 9/22/07
6/7/2007 BLD15 2. FBC Chapter 11: Accessible Route complying with
11-4.3 into and through site from public
transportation stops, streets or sidewalks, and
from accessible parking spaces & loading zones, to
accessible building entrance
6/7/2007 BLD15 3. FBC Chapter 11: Maximum slopes and cross -slopes
specified for all parking spaces, walks,and ramps
6/7/2007 BLD15 4. FBC Table 600: Building Separation Distance
Compliance
6/7/2007 BLD15 5. FBC 1820.3.6: Slab for Dumpster to be minimum
1' larger on all sides than receptacle and minimum
6" thick
1) Details provided on sheet C-5, however no
dumpster location provided on site plan.
2) Note service yard area appears to be enclosed,
however the building plans for the structure do
not show this as being the case
3) Please remove or void details on sheet C-5
which are not applicable to site
6/7/2007 BLD15
6. FBC 2122.4: Letter of intent stating scope of
work from Special Inspector, FL registered A/E,
must inspect and certify reinforced masonry
structures, applicable to dumspter walls
6/7/2007 BLD15 7. Outside Agency Approvals, i.e: Broward County,
Copy of Application for construction of Lake on
site; Health Department approval for construction
of Lift Station or Septic System
City of Parkland Printed on 6/7/2007 12:41:47PM
CD -Plus for Windows 95/98/NT Page 1 of 2 Printed By:ADM07
CDPR1014 - Checklist Print
INFO
PERMIT NUMBER: 2007010096
6/7/2007 BLD15 8. Area Calculations for square footage of site,
of paved area, of pervious area, linear feet of
sidewalks
Pervious area 88,363 sf = 2.03 acres
Impervious area 93,389 sf = 2.14 acres
Lineal ft of sidewalks:
4' = 291f, 5' = 681f, 6' = 6051f, 8' = 831f, 12' =
1701f
City of Parkland Printed on 6/7/2007 12:41:47PM
,?D -Plus for Windows 95/98/NT Page 2 of 2 Printed By:ADM07
Checklist Print
CDPR1014 - Checklist Print
PLAN.ENGSFR - SFR DRAINAGE PTE & RANCHES
STATUS
PEND
PEND
DATE
1/11/2007
USER
ENG03
PERMIT NUMBER: 2007010096
ITEM
1. PURSUANT TO PARKLAND CITY CODE 16-22 FOR
PINETREE NORTH & 16-42 FOR PINETREE SOUTH:
Architect's drainage plan submitted showing
drainage to sides and from front of property to
rear drainage swale, typical
1/11/2007
A Land Development/Engineering Permit is required
prior to issuance of a building permit. Please
contact the Public Services Department to process
the permit.
2. Easements: Pinetree, dedicated 5' side swale
easements and 17.5 dedicated drainage swale at
rear of property.
City of Parkland Printed on 6/7/2007 12:41:54PM
CD --Plus for Windows 95/98/NT Page 1 of 1 Printed By:ADM07
Checklist Print
CDFR1014 - Checklist Print
PLAN.ELCOM - ELECTRIC COMMERCIAL
STATUS DATE USER
YES 4/3/2007 ELE02
YES
YES
YES
N/A
YES
YES
YES
YES
N/A
PERMIT NUMBER: 2007010096
ITEM
1. site plan showing locations of structures and
equip FBC BCAP 104.6.4.8.1
4/3/2007 ELE02 2. architect / engineer signature and seal FBC
BCAP 104.6.3.7
4/3/2007 ELE02 3. electrical floor plan matches structural
4/3/2007 ELE02 4. riser diagram showing size of service, feeder
wire and conduit, overcurrent protection and
grounding NEC 250 FBC BCAP 104.6.4.8.1
4/3/2007 ELE02 5. mech plans to match load calc, exhaust fans
located per mech plan
4/3/2007 ELE02 6. provide short circuit analysis FBC BCAP
104.6.4.8.1
4/3/2007 ELE02 7. load calculations for service and each panel
including general lighting load, equip and
required receptacles FBC BCAP 104.6.4.8.1
8/10/2007 ELE02 8. panel schedules for each panel including wire
size and ocp FBC BCAP 104.6.4.8.1
provided corrected E6.1 from building plans
4/3/2007 ELE02 9. floor plan including location of all equip and
circuitry of all devices FBC BCAP 104.6.4.8.1
4/3/2007 ELE02 10. provide show window receptacles NEC 210.52
City of Parkland
Ali
V
Printed on 8 0/2007 11:39:08AM
Page 1 of 3 ri ed By:ELE02
CDPR1014 - Checklist Print
N/A
N/A
PERMIT NUMBER: 2007010096
4/3/2007 ELE02 11. GFI where required (rooftop, AC equip,
kitchen, etc.) NEC 210.8
4/3/2007 ELE02 12. provide sign outlets with FEC compliant
timeclock NEC 600.5/ Florida Energy Code
INFO 7/11/2007 ELE02 13. provide relevant material and equip listing
NO 8/10/2007 ELE02 14. provide detail for pole bases and handholes
SEe ATco
KAmm RCsPoasE
sNEET"
YES
✓1.provide dimensions for pole with luminaire from
grade
8/10/07 include luminaire and base in dimension
(see base detail)
.provide base details
8/10/07 precast or poured in place?
4/3/2007 ELE02 15. show compliance with Parkland lighting ord Sec
4-53
include positive statement of compliance
NO 8/10/2007 ELE02
N/A
N/A
YES
N/A
/rrAcjo
16. provide engineer's wind load calc for light
poles FBC Chapter 16 for hvhz
not provided t ed S t 4, c 4— 5C L+' T �'�
8/10/07 h P.r a
FArrt.-)clf{tom 'LiI�'
•I"s
4/3/2007 ELE02 17. verify fire -rating of electric rooms
4/3/2007 ELE02 18. provide ventilation for electric room
4/3/2007 ELE02 19. verify notes
4/3/2007 ELE02 20. seperate permit required for signs
City of Parkland Printed on 8/10/2007 11:39:08AM
Page 2 of 3 Printed By:ELE02
CDPR1014 - Checklist Print
YES
YES
PERMIT NUMBER: 2007010096
4/3/2007 ELE02 22. verify panel locations and clearances
4/3/2007 ELE02 21. indicate compliance with Florida Energy Code
requirements for electrical equipment
City of Parkland Printed on 8/10/2007 11:39:08AM
Page 3 of 3 Printed By:ELE02
c?JkAMM
Consulting
Headauarters Office
1407 West Newport Center Drive
Deerfield Beach, FL 33442
954-949-2200
954-949-2201 FAX
August 16, 2007
City of Parkland
Building Department — Plans Review
6600 University Drive
Parkland, FL 33067
Art Kamm, P.E.-LEED®
Bradly Brown, P.E.-LEED®
Rick Gonzalez
Lon T. Carter, P.E.
Mike Pella, P.E.
Scott Meriwether, P.E.
Enrique Uribe, P.E.
Gordon Myers, P.E.- LEED®
Paul Bohres, P.E.
RE: PARKLAND GOLF AND COUNTRY CLUB
Permit 2007010096
Below are our responses to Building Department comments pertinent only to our portion of the
design of the referenced project.
14. Comment: Provide detail for pole bases and handholes.
1) Provide dimensions for pole with luminaire from grade — 8/11/07 include
luminarie and base in dimension (see base detail).
2) Provide base details — 8/10/07 precast or poured in place?
Response: 1) Provided requested details with dimensions. Refer to revised Sheet
E1.3.
2) Provided base is precast type. Added note "precast 4500 psi
concrete base". Refer to Sheet E1.3.
16. Comment;
provided.
Response;
Provide engineer's wind load calc for light poles. FBC Chapter 16 for hvhz. Not
Wind load calc for light poles are provided by structural engineer.
If you have any questions or require additional information, please contact this office.
Sincerely,
KAMM CONSULTING, INC.
Bill Weaver
Project Manager
BW:tas
Florida
6859 Belfort Oaks Place
Jacksonville, FL 32216
904-285-2009
904-285-3009 Fax
Florida
1408 Orange Avenue
Fort Pierce, FL 34950
772-595-1744
772-595-1745 Fax
2006-0313 (08.16.07) Rev 4.doc
BRANCH OFFICES
Florida
3808 Gunn Highway, Ste. C
Tampa, FL 33618
813-265-9550
813-963-3187 Fax
www.kammconsultino.com
Georgia
2050 Marconi Drive, Ste. 300
Alpharetta, GA 30005
770-752-7083
770-752-7084 Fax
Checklist Print
CDPR1014 - Checklist Print \/ PERMIT NUMBER: 2007010096
PLAN.P.3C:SITE COMMERCIAL - SITE PLANS,C MMERCIAL PROJECT
STATUS DATE USER
YES 7/30/2007 BLD15
YES
YES
ITEM
PLAN REVIEW BY:_KRM_#HOURS_4
2nd review 7/30/07 KRM 1 hr
6/7/2007 BLD15 1. Two Sets Signed and Sealed Plans showing all
buildings and facilities on property
Engineering plans by John R McKune, PE sealed
7/31/06
Landscape plans by Steve Paul Sammons, Landscape
architect sealed 9/22/07
6/7/2007 BLD15 2. FBC Chapter 11: Accessible Route complying with
11-4.3 into and through site from public
transportation stops, streets or sidewalks, and
from accessible parking spaces & loading zones, to
accessible building entrance
6/7/2007 BLD15 3. FBC Chapter 11: Maximum slopes and cross -slopes
specified for all parking spaces, walks,and ramps
6/7/2007 BLD15 4. FBC Table 600: Building Separation Distance
Compliance
)/2007 BLD15 5. FBC 1820.3.6: Slab for Dumpster to be minimum
1' larger on all sides than receptacle and minimum
6" thick
1) Details provided on sheet C-5, however no
dumpster location provided on site plan.
P,Ut 2) Note service yard area appears to be enclosed,
however the building plans for the structure do
not show this as being the case
3) Please remove or void details on sheet C-5
which are not applicable to site
BLD15
7/30/07 Items 1 and 3 above have been corrected
Item 2 above has not been addressed. Require
structural drawings for the footings and walls
surrounding the Service Yard
6. FBC 2122.4: Letter of intent stating scope of
work from Special Inspector, FL registered A/E,
must inspect and certify reinforced masonry
structures, applicable to dumspter walls
Printed on 7/31/2007 2:39:41PM
Page 1 of 2 Printed By:ADM09
CDPR1014 - Checklist Print PERMIT NUMBER: 2007010096
N/A 6/7/2007 BLD15 7. Outside Agency Approvals, i.e: Broward County,
Copy of Application for construction of Lake on
site; Health Department approval for construction
of Lift Station or Septic System
INFO
6/7/2007 BLD15 8. Area Calculations for square footage of site,
of paved area, of pervious area, linear feet of
sidewalks
Pervious area 88,363 sf = 2.03 acres
Impervious area 93,389 sf = 2.14 acres
Lineal ft of sidewalks:
4' = 291f, 5' = 681f, 6' = 6051f, 8' = 831f, 12' =
1701f
City of Parkland Printed on 7/31/2007 2:39:41PM
CD -Plus for Windows 95/98/NT Page 2 of 2 Printed By:ADM09
Checklist Print
CDPR1014 - Checklist Print
PLAN.ELCOM - ELECTRIC COMMERCIAL
PERMIT NUMBER: 2007010096
STATUS DATE USER ITEM
YES 4/3/2007 ELE02 1. site plan showing locations of structures and
equip FBC BCAP 104.6.4.8.1
YES
YES
YES
N/A
YES
YES
4/3/2007 ELE02 2. architect / engineer signature and seal FBC
BCAP 104.6.3.7
4/3/2007 ELE02 3. electrical floor plan matches structural
4/3/2007 ELE02 4. riser diagram showing size of service, feeder
wire and conduit, overcurrent protection and
grounding NEC 250 FBC BCAP 104.6.4.8.1
4/3/2007 ELE02 5. mech plans to match load calc, exhaust fans
located per mech plan
4/3/2007 ELE02 6. provide short circuit analysis FBC BCAP
104.6.4.8.1
4/3/2007 ELE02 7. load calculations for service and each panel
including general lighting load, equip and
required receptacles FBC BCAP 104.6.4.8.1
N0 7/11/2007 ELE02 8. panel schedules for each panel including wire
size and ocp FBC BCAP 104.6.4.8.1
provided corrected E6.1 from building plans
NEw SAEt- tOStRTEP
YES
N/A
4/3/2007 ELE02 9. floor plan including location of all equip and
circuitry of all devices FBC BCAP 104.6.4.8.1
4/3/2007 ELE02 10. provide show window receptacles NEC 210.52
City of Parkland Printed on 7/31/2007 2:39:58PM
CD -Plus for Windows 95/98/NT Page 1 of 3 Printed By:ADM09
CDPR1014 - Checklist Print PERMIT NUMBER: 2007010096
N/A
N/A
INFO
NO
4/3/2007 ELE02 11. GFI where required (rooftop, AC equip,
kitchen, etc.) NEC 210.8
4/3/2007 ELE02 12. provide sign outlets with FEC compliant
timeclock NEC 600.5/ Florida Energy Code
7/11/2007 ELE02 13. provide relevant material and equip listing
7/11/2007 ELE02 14. provide detail for pole bases and handholes
N tiw S I4 €t E 13 Tom-rE0
YES
NO
1.provide dimensions for pole with luminaire from
grade
2.provide base details
4/3/2007 ELE02 15. show compliance with Parkland lighting ord Sec
4-53
include positive statement of compliance
4/3/2007 ELE02
NtW ci4ccC f1.3 rrNi ED
N/A
N/A
YES
N/A
YES
16. provide engineer's wind load calc for light
poles FBC Chapter 16 for hvhz
4/3/2007 ELE02 17. verify fire -rating of electric rooms
4/3/2007 ELE02 18. provide ventilation for electric room
4/3/2007 ELE02 19. verify notes
4/3/2007 ELE02 20. seperate permit required for signs
4/3/2007 ELE02 22. verify panel locations and clearances
City of Parkland Printed on 7/31/2007 2:39:58PM
CD -Plus for Windows 95/98/NT Page 2 of 3 Printed By:ADM09
CDPR1014 - Checklist Print
YES
PERMIT NUMBER: 2007010096
4/3/2007 ELE02 21. indicate compliance with Florida Energy Code
requirements for electrical equipment
City of Parkland
CD -Plus for Windows 95/98/NT
Printed on 7/31/2007 2:39:58PM
Page 3 of 3 Printed By:ADM09
Checklist Print
CDPR1014 - Checklist Print PERMIT NUMBER: 2007010096
PLAN.FBC:SITE COMMERCIAL - SITE PLANS COMMERCIAL PROJECT
STATUS DATE USER ITEM
YES 8/7/2007 BLD15 PLAN REVIEW BY:_KRM_#HOURS_4
YES
YES
YES
N/A
YES
YES
2nd review 7/30/07 KRM 1 hr
3rd review 8/6/07 KRM 1 hr
6/7/2007 BLD15 1. Two Sets Signed and Sealed Plans showing all
buildings and facilities on property
Engineering plans by John R McKune, PE sealed
7/31/06
Landscape plans by Steve Paul Sammons, Landscape
architect sealed 9/22/07
6/7/2007 BLD15 2. FBC Chapter 11: Accessible Route complying with
11-4.3 into and through site from public
transportation stops, streets or sidewalks, and
from accessible parking spaces & loading zones, to
accessible building entrance
6/7/2007 BLD15 3. FBC Chapter 11: Maximum slopes and cross -slopes
specified for all parking spaces, walks,and ramps
6/7/2007 BLD15 4. FBC Table 600: Building Separation Distance
Compliance
8/6/2007 BLD15 5. FBC 1820.3.6: Slab for Dumpster to be minimum
1' larger on all sides than receptacle and minimum
6" thick
1) Details provided on sheet C-5, however no
dumpster location provided on site plan.
2) Note service yard area appears to be enclosed,
however the building plans for the structure do
not show this as being the case
3) Please remove or void details on sheet C-5
which are not applicable to site
7/30/07 Items 1 and 3 above have been corrected
Item 2 above has not been addressed. Require
structural drawings for the footings and walls
surrounding the Service Yard
Service yard walls are part of building plans see
5100
7/30/2007 BLD15 6. FBC 2122.4: Letter of intent stating scope of
work from Special Inspector, FL registered A/E,
must inspect and certify reinforced masonry
structures, applicable to dumspter walls
City of Parkland Printed on 8/20/2007 4:05:11PM
CD -Plus for Windows 95/98/NT Page 1 of 2 Printed By:ADM04
CDPR1014 - Checklist Print
N/A
INFO
PERMIT NUMBER: 2007010096
6/7/2007 BLD15 7. Outside Agency Approvals, i.e: Broward County,
Copy of Application for construction of Lake on
site; Health Department approval for construction
of Lift Station or Septic System
8/7/2007 BLD15 8. Area Calculations for square footage of site,
of paved area, of pervious area, linear feet of
sidewalks
Pervious area 88,363 sf = 2.03 acres
Impervious area 93,389 sf = 2.14 acres
City of Parkland
CD -Plus for Windows 95/98/NT
Asphault areas 49,600 sf
Paver areas 8,000 sf
Lineal ft of sidewalks:
4' = 291f,
5' = 681f,
6' = 6051f,
8' = 831f,
12' = 1701f