BLDG1404-0010-Energy CalculationsFORM 405-10
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name:
Street:
City, State, Zip:
Owner:
Design Location:
Osprey- HIBISCUS
Parkland , FL ,
WCI Communities, LLC
FL, Fort Lauderdale
1. New construction or existing
2. Single family or multiple family
3. Number of units, if multiple family
4. Number of Bedrooms
5. Is this a worst case?
6. Conditioned floor area above grade (ft2)
Conditioned floor area below grade (ft2)
7. Windows(476.2 sqft.)
a. U -Factor:
SHGC:
b. U -Factor:
SHGC:
c. U -Factor:
SHGC:
d. U -Factor:
SHGC:
New (From Plans)
Single-family
1
4
Yes
2731
0
Description Area
Dbl, U=0.60 358.84 ft2
SHGC=0.31
Dbl, U=0.68 72.00 ft2
SHGC=0.29
Dbl, U=0.38 24.00 ft2
SHGC=0.31
other (see details) 21.36 ft2
other (see details)
Area Weighted Average Overhang Depth:
Area Weighted Average SHGC:
8. Floor Types (2731.0 sqft.)
a. Slab -On -Grade Edge Insulation
b. N/A
c. N/A
Glass/Floor Area: 0.174
Insulation
R=0.0
R=
R=
6.775 ft.
0.304
Area
2731.00 ft2
ft2
112
Builder Name: WCI Communities
Permit Office: Parkland
Permit Number:
Jurisdiction: 163100
9. Wall Types (2819.5 sqft.)
a. Concrete Block - Int Insul, Exterior
b. Frame - Steel, Adjacent
c. N/A
d. N/A
10. Ceiling Types (2731.0 sqft.)
a. Under Attic (Vented)
b. N/A
c. N/A
11. Ducts
a. Sup: Attic, Ret: Attic, AH: AC1
12. Cooling systems
a. Central Unit
13. Heating systems
a. Electric Strip Heat
14. Hot water systems
a. Natural Gas Tankless
b. Conservation features
None
15. Credits
Total Proposed Modified Loads: 48.02
Total Standard Reference Loads: 73.48
I hereby certify that the plans and specifications covered by
this calculation are in compliance with the Florida Energy
Digitally signed by OSCAR L.
CALLEJA
DN: cn=OSCAR L. CALLEJA,
n-_FNGJNFFRFn AIR I I C rni
email=oscarc@eng ineeredairlIc.c
Code.
OSCAR L.
PREPARED BY:
DATE: CALLEJA
om, c=US
Date: 2013.06.04 18:33:01 -04'00'
I hereby certify that this building, as designed, is in compliance
with the Florida Energy ode.
OWN ER/AG
DATE:EBF
��r�y_�
Review of the plans and
specifications covered by this
calculation indicates compliance
with the Florida Energy Code.
Before construction is completed
this building will be inspected for
compliance with Section 553.908
Florida Statutes.
Insulation Area
R=4.1 2602.80 ft2
R=11.0 216.70 ft2
R= ft2
R= ft2
Insulation Area
R=38.0 2731.00 ft2
R= ft2
R= ft2
R ft2
6 300
kBtu/hr Efficiency
45.5 SEER:14.00
kBtu/hr Efficiency
33.0 COP:1.00
Cap: 1 gallons
EF: 0.820
Pstat
PASS
BUILDING OFFICIAL: tJ.,1eVft T
DATE* Y - 2 G
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with 403.2.2.1.1.
- Compliance requires completion of a Florida Air Barrier and Insulation Inspection Checklist
6/4/2013 5:01 PM
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 1 of 6
Title:
Building Type:
Owner:
# of Units:
Builder Name:
Permit Office:
Jurisdiction:
Family Type:
New/Existing:
Comment:
Osprey- HIBISCUS
User
WCI Communities, LLC
1
WCI Communities
Parkland
163100
Single-family
New (From Plans)
Design Location
TMY Site
PROJECT
Bedrooms:
Conditioned Area:
Total Stories:
Worst Case:
Rotate Angle:
Cross Ventilation:
Whole House Fan:
FL, Fort Lauderdale FL_FORT_LAUDERDALE
Number Name
1 Blockl
Number Name
1 AC1
V'
# Floor Type
1 Slab -On -Grade Edge Insulatio
Area
2731
IECC
Zone
Volume
1
27634.6
4 Address Type: Street Address
2731 Lot #
1 Block/SubDivision:
Yes PlatBook:
315 Street:
County:
City. State, Zip:
CLIMATE
Design Temp
97.5 % 2.5 %
Broward
Parkland ,
FL,
Int Design Temp Heating Design Daily Temp
Winter Summer Degree Days Moisture Range
43 91 70 75
BLOCKS
SPACES
Area Volume Kitchen
2731 27634.6 Yes
FLOORS
321.5
60
Low
Occupants Bedrooms InfiI ID Finished Cooled Heated
5
4
Space Perimeter R -Value Area
AC1 280 ft 0 2731 ft2
# Type Materials
1 Hip Barrel tile
# Type
1 Full attic
# Ceiling Type
1 Under Attic (Vented)
6/4/2013 5:01 PM
ROOF
Roof Gable
Area Area
Roof Solar
Color Absor.
2958 ft2 0 ft2 Medium 0.75
ATTIC
Ventilation Vent Ratio (1 in)
Vented
300
CEILING
Space R -Value
AC1 38
1
SA
Tested
Area RBS
2731 ft2 N
Area
2731 ft2
Yes
Yes
Yes
Tile Wood Carpet
1 0 0
Emitt Emitt Deck Pitch
Tested Insul. (deg)
No 0.9 No 0 22.6
IRCC
N
Framing Frac
0.11
Truss Type
Wood
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 2 of 6
1
1
WALLS
Adjacent Cavity Width Height Sheathing Framing Solar Below
# (lmf Tn Wall Type Space R-VaIUP Ft In Ft In Area R -Valle Fraction Absor GradP%
1 NE=>N Exterior Concrete Block - Int Ir:sul AC1 4.1 8.5 0 12 0 102.0 ft2 0 0 0.5 0
2 NE=>N Exterior Concrete Block - Int Insul AC1 4.1 12.7 0 10 0 127.0 ft2 0 0 0.5 0
3 NW=>W Exterior Concrete Block - Int Insul AC1 4.1 12.67 0 10 0 126.7 ft2 0 0 0.5 0
4 SE=>E Exterior Concrete Block - Int Insul AC1 4.1 14.2 0 10 0 142.0 ft2 0 0 0.5 0
5 SE=>E Exterior Concrete Block - Int Insul AC1 4.1 6 0 10 0 60.0 ft2 0 0 0.5 0
6 SE=>E Exterior Concrete Block - Int Insul AC1 4.1 13 0 10 0 130.0 ft2 0 0 0.5 0
7 SE=>E Exterior Concrete Block - Int Insul AC1 4.1 15 0 10 0 150.0 ft2 0 0 0.5 0
8 W=>SW Exterior Concrete Block - Int Insul AC1 4.1 4 0 10 0 40.0 ft2 0 0 0.5 0
9 NW=>W Exterior Concrete Block - Int Insul AC1 4.1 4.6 0 10 0 46.0 ft2 0 0 0.5 0
10 SW=>S Exterior Concrete Block - Int Insul AC1 4.1 2.5 0 10 0 25.0 ft2 0 0 0.5 0
11 SW=>S Exterior Concrete Block - Int Insul AC1 4.1 16 0 10 0 160.0 ft2 0 0 0.5 0
12 SE=>E Exterior Concrete Block - Int Insul AC1 4.1 17 0 10 0 170.0 ft2 0 0 0.5 0
13 NW=>W Exterior Concrete Block - Int Insul AC1 4.1 13 0 10 0 130.0 ft2 0 0 0.5 0
14 SW=>S Exterior Concrete Block - Int Insul AC1 4.1 12.4 0 11.3 0 140.1 ft2 0 0 0.5 0
15 NE=>N Exterior Concrete Block - Int Insul AC1 4.1 5 0 10 0 50.0 ft2 0 0 0.5 0
16 SE=>E Exterior Concrete Block - Int Insul AC1 4.1 12 0 10 0 120.0 ft2 0 0 0.5 0
17 NE=>N Garage Frame - Steel AC1 11 6.67 0 10 0 66.7 ft2 0 0.26 0.5 0
18 NW=>W Exterior Concrete Block - Int Insul AC1 4.1 6.1 0 10 0 61.0 ft2 0 0 0.5 0
19 NE=>N Garage Frame - Steel AC1 11 15 0 10 0 150.0 ft2 0 0.26 0.5 0
20 NW=>W Exterior Concrete Block - Int Insul AC1 4.1 14.5 0 10 0 145.0 ft2 0 0 0.5 0
21 SW=>S Exterior Concrete Block - Int Insul AC1 4.1 8 0 10 0 80.0 ft2 0 0 0.5 0
22 W=>SW Exterior Concrete Block - Int Insul AC1 4.1 5 0 10 0 50.0 ft2 0 0 0.5 0
23 S=>SE Exterior Concrete Block - Int Insul AC1 4.1 5 0 10 0 50.0 ft2 0 0 0.5 0
24 NW=>W Exterior Concrete Block - Int Insul AC1 4.1 14 0 10 0 140.0 ft2 0 0 0.5 0
25 SE=>E Exterior Concrete Block - Int Insul AC1 4.1 14.5 0 10 0 145.0 ft2 0 0 0.5 0
26 NW=>W Exterior Concrete Block - Int Insul AC1 4.1 10 0 10 0 100.0 ft2 0 0 0.5 0
27 NW=>W Exterior Concrete Block - Int Insul AC1 4.1 11.3 0 10 0 113.0 ft2 0 0 0.5 0
DOORS
# Omt Door Type Space Storms U -Value Width Height Area
Ft In Ft In
1 NE=>N Insulated AC1 None .6 3 8 24 ft2
2 NE=>N Insulated AC1 None .6 2.8 8 22.6 ft2
WINDOWS
Orientation shown is the entered orientation (=>) changed to Worst Case.
Wall Overhang
# Omt ID Frame Panes NFRC U -Factor SHGC Area Depth Separation Int Shade Screening
1 NE=>N 1 Metal Low -E Double Yes 0.38 0.31 24.0 ft2 6 ft 0 in 0.2 ft 0 in None None
2 NE=>N 2 Metal Low -E Double Yes 0.6 0.31 47.2 ft2 1.67 ft 0 i 2 ft 0 in None None
3 SE=>E 5 Metal Low -E Double Yes 0.6 0.31 9.0 ft2 1.67 ft 0 i 2 ft 0 in Drapes/blinds None
4 SE=>E 6 Metal Low -E Double Yes 0.6 0.31 33.1 ft2 1.67 ft 0 i 2 ft0 in None None
5 W=>SW 8 Metal Low -E Double Yes 0.6 0.31 16.2 ft2 12 ft 0 in 1 ft 0 in None None
6 NW=>W 9 Metal Low -E Double Yes 0.6 0.31 16.2 ft2 3 ft 0 in 1 ft 0 in None None
6/4/2013 5:01 PM
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 3 of 6
WINDOWS
Orientation shown is the entered orientation (=>) changed to Worst Case.
/ Wall Overhang
�/ # Ornt ID Frame Panes NFRC U -Factor- SHGC Area Depth Separation Int Shade Screening
7 SW=>S 11 Metal Low -E Double Yes 0.6 0.31 32.3 ft2 1.67 ft 0 i 2 ft 0 in None None
8 SE=>E 12 Metal Low -E Double Yes 0.6 0.31 32.3 ft2 1.67 ft 0 i 2 ft 0 in None None
9 NW=>W 13 Metal Low -E Double Yes 0.6 0.31 16.2 ft2 35 ft 0 in 1 ft 0 in None None
10 NW=>W 13 Metal Low -E Double Yes 0.75 0.25 21.4 ft2 35 ft 0 in 1 ft 0 in None None
11 SW=>S 14 Metal Low -E Double Yes 0.68 0.29 72.0 ft2 14 ft 0 in 1 ft 0 in None None
12 NE=>N 15 Metal Low -E Double Yes 0.6 0.31 23.6 ft2 1.67 ft 0 i 2 ft 0 in None None
13 NW=>W 18 Metal Low -E Double Yes 0.6 0.31 11.4 ft2 1.67 ft 0 i 2 ft 0 in None None
14 NW=>W 20 Metal Low -E Double Yes 0.6 0.31 16.2 ft2 1.67 ft 0 i 2 ft 0 in Drapes/blinds None
15 SW=>S 21 Metal Low -E Double Yes 0.6 0.31 33.1 ft2 1.67 ft 0 i 2 ft 0 in Drapes/blinds None
16 W=>SW 22 Metal Low -E Double Yes 0.6 0.31 16.2 ft2 1.67 ft 0 i 2 ft 0 in Drapes/blinds None
17 S=>SE 23 Metal Low -E Double Yes 0.6 0.31 16.2 ft2 1.67 ft 0 i 2 ft 0 in Drapes/blinds None
18 NW=>W 24 Metal Low -E Double Yes 0.6 0.31 16.2 ft2 1.67 ft 0 i 2 ft 0 in Drapes/blinds None
19 NW=>W 27 Metal Low -E Double Yes 0.6 0.31 23.6 ft2 1.67 ft 0 i 2 ft 0 in Drapes/blinds None
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation
1 492 ft2 492 ft2 64 ft 10 ft 1
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Best Guess .0005 3581.7 196.63 369.8 .345 7.7766
HEATING SYSTEM
V # System Type Subtype Efficiency Capacity Block Ducts
1 Electric Strip Heat None COP: 1 33 kBtu/hr 1 sys#1
COOLING SYSTEM
# System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit Split SEER: 14 45.5 kBtu/hr 1850 cfm 0.78 1 sys#1
HOT WATER SYSTEM
# System Type SubType Location EF Cap Use SetPnt Conservation
1 Natural Gas Tankless Garage 0.82 1 gal 70 gal 120 deg None
6/4/2013 5:01 PM
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 4 of 6
1
1
FSEC
Cert #
Company Name
SOLAR HOT WATER SYSTEM
System Model #
Collector Storage
Collector Model # Area Volume FEF
None None ft'
1
DUCTS 1
-- Supply -- -- Retum -- Air CFM 25 CFM25 HVAC #
# Location R -Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool
1 Attic 6 300 ft2 Attic 40 ft2 Default Leakage AC1 (Default) (Default) 1 1
TEMPERATURES
Programable Thermostat: Y Ceiling Fans:
Cooling
Heating X
Venting
Jan
Jan
Jan
X
Feb
Feb
Feb
MarA r MayX Jun Jul X Auge
X Mar Apr MaJun JuAug Sep
x Mar Apr May Jun Jul Aug Sep
Oct
Oct
Oct
Nov Dec
Nov X Dec
Nov Dec
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling (WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling (WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating (WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
Heating (WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
6/4/2013 5:01 PM
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 5 of 6
FORM 405-10
Florida Code Compliance Checklist
Florida Department of Business and Professional Regulations
Residential Whole Building Performance Method
ADDRESS: PERMIT #:
Parkland, FL,
MANDATORY REQUIREMENTS SUMMARY - See individual code sections for full details.
COMPONENT SECTION SUMMARY OF REQUIREMENT(S) CHECK
Air leakage
402.4 To be caulked, gasketed, weatherstripped or otherwise sealed.
Recessed lighting IC -rated as meeting ASTM E 283. Windows and
doors = 0.30 cfm/sq.ft. Testing or visual inspection required.
Fireplaces: gasketed doors & outdoor combustion air. Must complete
envelope leakage report or visually verify Table 402.4.2.
Thermostat & 403.1 At least one thermostat shall be provided for each separate heating
controls and cooling system. Where forced -air furnace is primary system,
programmable thermostat is required. Heat pumps with supplemental
electric heat must prevent supplemental heat when compressor can
meet the load.
Ducts 403.2.2 All ducts, air handlers, filter boxes and building cavities which form the
primary air containment passageways for air distribution systems shall
be considered ducts or plenum chambers, shall be constructed and
sealed in accordance with Section 503.2.7.2 of this code.
Water heaters
403.3.3 Building framing cavities shall not be used as supply ducts.
403.4 Heat trap required for vertical pipe risers. Comply with efficiencies in
Table 403.4.3.2. Provide switch or clearly marked circuit breaker
(electric) or shutoff (gas). Circulating system pipes insulated to =
R-2 + accessible manual OFF switch.
Mechanical 403.5 Homes designed to operate at positive pressure or with mechanical
ventilation ventilation systems shall not exceed the minimum ASHRAE 62 level.
No make-up air from attics, crawlspaces, garages or outdoors adjacent
to pools or spas.
403.9 Pool pumps and pool pump motors with a total horsepower (HP) of = 1
HP shall have the capability_of operating at two or more speeds. Spas
and heated pools must have vapor -retardant covers or a liquid cover or
other means proven to reduce heat Toss except if 70% of heat from
site -recovered energy. Off/timer switch required. Gas heaters minimum
thermal efficiency=78% (82% after 4/16/13). Heat pump pool heaters
minimum COP= 4.0.
Swimming Pools
& Spas
Cooling/heating 403.6 Sizing calculation performed & attached. Minimum efficiencies per
Tables 503.2.3. Equipment efficiency verification required. Special
equipment occasion cooling or heating capacity requires separate system or
variable capacity system. Electric heat >10kW must be divided into two
or more stages.
Ceilings/knee walls
6/4/2013 5:01 PM
405.2.1 R-19 space permitting.
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 6 of 6
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 65
The lower the EnergyPerformance Index, the more efficient the home.
1. New construction or existing
2. Single family or multiple family
3. Number of units, if multiple family
4. Number of Bedrooms
5. Is this a worst case?
6. Conditioned floor area (ft2)
7. Windows"
a. U -Factor:
SHGC:
b. U -Factor:
SHGC:
c. U -Factor:
SHGC:
d. U -Factor:
SHGC:
Area Weighted Average
Area Weighted Average
8. Floor Types
a. Slab -On -Grade Edge
b. N/A
c. N/A
New (From Plans)
Single-family
1
4
Yes
2731
Description Area
Dbl, U=0.60 358.84 ft2
SHGC=0.31
Dbl, U=0.68 72.00 ft2
SHGC=0.29
Dbl, U=0.38 24.00 ft2
SHGC=0.31
other (see details) 21.36 ft2
other (see details)
Overhang Depth: 6.775 ft.
SHGC: 0.304
Insulation Area
Insulation R=0.0 2731.00 ft2
R= ft2
R= ft2
, Parkland, FL,
9. Wall Types
a. Concrete Block - Int Insul, Exterior
b. Frame - Steel, Adjacent
c. N/A
d. N/A
10. Ceiling Types
a. Under Attic (Vented)
b. N/A
c. N/A
11. Ducts
a. Sup: Attic, Ret: Attic, AH: AC1
12. Cooling systems
a. Central Unit
13. Heating systems
a. Electric Strip Heat
14. Hot water systems
a. Natural Gas
b. Conservation features
None
15. Credits
I certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded)
in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code compliant features.j
Date: 3 I �� tet"
LVA \fR\33P,p\s c City/FL Zip:
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at (321)
638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's
support staff.
Builder Signatu e
Address of New Home:
Insulation
R=4.1
R=11.0
R=
R=
Insulation
R=38.0
R=
R=
Area
2602.80 ft2
216.70 ft2
ft2
ft2
Area
2731.00 ft2
112
ft2
R ft2
6 300
kBtu/hr Efficiency
45.5 SEER:14.00
kBtu/hr Efficiency
33.0 COP:1.00
Cap: 1 gallons
EF: 0.82
Pstat
**Label required by Section 303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software
Osprey- HIBISCUS
HVAC Load Calculations
for
WCI Communities, LLC
Eir:ilio".."It
RHVACRicenniamm.
HVAC LOADS
PreparedJ3y:
Oscar L. Calleja
Engineered Air, LLC
2520 N Andrews Ave. Ext
Pompano Beach, FI 33064
954-449-1600
Tuesday, June 04, 2013
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Rhvac - Residential & Light Commercial HVAC Loads
Engineered Air, LLC
Margate, FL 33063
Project Report
[General Praiectklfontiation
Project Title:
Designed By:
Project Date:
Client Name:
Company Name:
Company Representative:
Company Address:
Company City:
Company Phone:
Company Fax:
Company E -Mail Address:
Company Comment:
[Desiga.Data
Reference City:
Building Orientation:
Daily Temperature Range:
Latitude:
Elevation:
Altitude Factor:
Winter:
Summer:
•
Osprey- HIBISCUS
Oscar L. Calleja
5/30/2013
WCI Communities, LLC
Engineered Air, LLC
Oscar L. Calleja
2520 N Andrews Ave. Ext
Pompano Beach, FI 33064
954-449-1600
954-973-1883
oscarc@engineeredairlIc.com
License No. CAC045860
Outdoor
Dry Bulb
46
90.9
Outdoor
Wet Bulb
43.16
78.4
E. Fort Lauderdale, Florida
Front door faces Northeast
Medium
26 Degrees
10 ft.
1.000
Outdoor
Rel.Hum
n/a
58%
Elite Software Development, Inc.
Osprey- HIBISCUS
Page 2
Indoor Indoor Grains
Rel.Hum Dry Bulb Difference
n/a 70 n/a
50% 75 62
[Chet* 9 ,:::-, ' : ' --: : -.!,-;::;,-;,-- ,,, -:.,--A': '..:-i: .;,:-; : -
Total Building Supply CFM: 1,850 CFM Per Square ft.:
Square ft. of Room Area: 2,731 Square ft. Per Ton:
• Volume (ft3) of Cond. Space: 28,078
j1.Rs.-.-: , ' r :: 7., :;°:?°:;-:; --',,",' • :,--,,:'• Yi'
Total Heating Required Including Ventilation Air: 26,526 Btuh
Total Sensible Gain: 35,356 Btuh
Total Latent Gain: 6,892 Btuh
Total Cooling Required Including Ventilation Air: 42,247 Btuh
0.677
776
26.526 MBH
84 %
16 %
3.52 Tons (Based On Sensible + Latent)
Otet .
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\Users\Oscarc\Documents\Elite Software\Rhvac 9 Projects\WCI-Hibiscus.rh9 Tuesday, June 04, 2013, 6:30 PM
Rhvac - Residential & Light Commercial HVAC Loads
Engineered Air, LLC
Margate, FL 33063
System 1 AC -1 Summary Loads
WCI-FixGI: Glazing-WCI-Fixed GI-dbl-low-e, u -value
0.38, SHGC 0.31
WCI-SH: Glazing-WCI-SH-dbl-low-e, u -value 0.6, SHGC
0.31
WCI-SH: Glazing-WCI-SH-dbl-low-e, light color blinds at
45° with 50% coverage, u -value 0.6, SHGC 0.31
WCI-FrenchD: Glazing-WCI-French Door-dbl-low-e, u -
value 0.75, SHGC 0.25
WCI-SlidinfGl: Glazing-WCI-Sliding GI-dbl-low-e, u -value
0.68, SHGC 0.29
11J: Door -Metal - Fiberglass Core
13A-4ocs: Wall -Block, board insulation only, R-4 board
insulation, open core, siding finish
12B-Obw: Part -Frame, R-11 insulation in 2 x 4 stud
cavity, no board insulation, brick finish, wood studs
16D-30: Roof/Ceiling-Under Attic with Insulation on Attic
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark Tile,
Slate or Concrete, R-30 insulation
22A-pl-c: Floor -Slab on grade, No edge insulation, no
insulation below floor, carpet covering, passive, light
dry soil
Subtotals for structure:
People:
Equipment:
Lighting:
Ductwork:
Infiltration: Winter CFM: 103, Summer CFM: 51
Ventilation: Winter CFM: 0, Summer CFM: 0
AED Excursion:
System 1 AC -1 Load Totals:
1 Chi° Figures "
Supply CFM: 1,850
Square ft. of Room Area: 2,731
Volume (ft3) of Cond. Space: 28,078
1 System LearW
Total Heating Required Including Ventilation._Air:
Total Sensible Gain:
Total Latent Gain:
Total Cooling Required Including Ventilation Air:
■
Elite Software Development, Inc.
Osprey- HIBISCUS
Page 3
Area Selt Lai ;Seta ' Total
Quan.
24 218 0 664 664
228.4 3,291 0 6,523 6,523
130.4 1,878 0 3,063 3,063
21.4 384 0 628 628
72 1,175 0 1,220 1,220
46.6 618 0 591 591
2102.6 7,216 0 4,871 4,871
194.1 376 0 282 282
2613.4 2,008 0 2,584 2,584
280 6,646 0 0 0
23,810 0 20,426 20,426
5 1,400 1,150 2,550
2,000 4,200 6,200
0 0 0
0 1,315 6,492 7,807
2,716 2,177 900 3,077
0 0 0 0
0 0 2,188 2,188
26,526 6,892 35,356 42,247
CFM Per Square ft.:
Square ft. Per Ton:
26,526 Btuh
35,356 Btuh
6,892 Btuh
42,247 Btuh
0.677
776
26.526 MBH
84 %
16 %
3.52 Tons (Based On Sensible + Latent)
1:Tei' - .-'l . --. .,�3ry t - - -
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather -may vary.
Be sure to select a unit that meets both sensible and latent Toads according to the manufacturer's performance data at
your design conditions.
C:\Users\Oscarc\Documents\Elite Software\Rhvac 9 Projects\WCI-Hibiscus.rh9 Tuesday, June 04, 2013, 6:30 PM
Rhvac - Residential & Light Commercial HVAC Loads
Engineered Air, LLC
Margate, FL 33063
Equipment Data - System 1 - AC -1
Cooling
System Type:
Outdoor Model:
Indoor Model:
Tradename:
Outdoor Manufacturer:
AHRI Reference No.:
Nominal Capacity:
Efficiency:
Heating
System Type:
Model:
Capacity:
Efficiency:
■
Standard Air Conditioner
CA 13 NA048*"'(A, B)
FB4CNF060
13 SEER PURON AC
CARRIER AIR CONDITIONING
4542180
45500
14 SEER
Electric Resistance
10 KW
0
0%
Elite Software Development, Inc.
Osprey- HIBISCUS
Page 4
This system's equipment was selected in accordance with ACCA Manual S.
Manual S equipment sizing data: SODB: 90.9F, SOWB: 78.4F, WODB: 46F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen.
gain: 35,356 Btuh, Lat. gain: 6,892 Btuh, Sen. Toss: 26,526 Btuh, Entering clg. coil DB: 75F, Entering clg. coil WB: 62.5F,
Entering htg. coil DB: 70F, Clg. coil TD: 20F, Htg. coil TD: 20F, Req. clg. airflow: 1608 CFM, Req. htg. airflow: 1206 CFM
C:\Users\Oscarc\Documents\Elite Software\Rhvac 9 Projects\WCI-Hibiscus.rh9 Tuesday, June 04, 2013, 6:30 PM
Rhvac - Residential & Light Commercial HVAC Loads
Engineered Air, LLC
Margate, FL 33063
Building Rotation Report
All rotation degree values in this report are clockwise with respect to the project's original orientation.
Building orientation as entered (zero degrees rotation): Front door faces Northeast
At least one system with its System Air Type input set to Fixed was changed to Auto during the building rotation. If you
want to change this behavior uncheck the option on the General tab of the Select Reports dialog called "Always use Auto
for System Air Type for Building Rotation Report."
Individual -Rooms
Elite Software Development, Inc.
Osprey- HIBISCUS
Page 5
7
Rlxl': R
.11 ' C
System 1:
Zone 1:
1 Foyer
2 Den/Bed #4
3 Powder Bath
4 Dining
5 Kitchen
6 Breakfast Nook
7 Family Room
8 Living Room
Zone 2:
57 62 61 54 71 *94 75 52 1--6
161 171 169 154 223 *253 205 154 2-7
26 26 35 *44 35 26 26 26 1--4
74 65 115 *133 98 63 63 72 1--7
*139 136 136 133 132 133 133 133 1--7
*112 74 57 62 65 61 82 109 1-7
313 294 *314 296 265 228 234 274 2--8
198 *253 186 105 112 131 129 113 2--7
9 Bathroom #2 *5 5 5 5 5 5 5 5 1--4
10 Bedroom #2 107 143 132 89 137 *151 128 99 1--8
11 Laundry 68 68 68 68 68 68 68 *73 1--5
12 Bedroom #3 113 80 85 115 83 79 105 *124 1--7
13 Hallway & Closet *3 3 3 3 3 3 3 3 1--4
Zone 3:
14 Master Bedroom 347 *362 318 242 285 314 262 294 2--9
15 HER WIC *33 33 33 33 33 33 33 33 1--4
16 HIS WIC *5 5 5 5 5 5 5 5 1--4
. 17 Master Toilet *1 1 1 1 1 1 1 1 1--4
18 Master Bath 91 53 53 98 84 53 94 *111 1--7
* Indicates highest CFM of all rotations.
1 vie SUiIdhig. ; -
Frt> door
Faces
° Northeast
45° East
90° Southeast
135° South
180° Southwest
225° West
270° Northwest
315° North
* Indicates highest value of all rotations.
*1,609
1,516
1,590
1,465
1,510
1,442
1,481
1,461
*35,390
33,342
34,957
32,227
33,212
31,717
32,562
32,129
6,899
6,898
6,892
6,892
6,897
*6,899
6,899
6,894
-TonsNet
*3.52
3.35
3.49
3.26
3.34
3.22
3.29
3.25
C:\Users\Oscarc\Documents\Elite Software\Rhvac 9 Projects\WCI-Hibiscus.rh9 Tuesday, June 04, 2013, 6:30 PM