HomeMy WebLinkAboutBLDG1403-0024-Soil Bearing ReportsFIELD DENSITY TESTING REPORT
Report Number:
Service Date:
Report Date: ·
Task:
Client
HD 131567.0022
04/14114
04/14/14
FIELD TESTING
WCI Communities, Inc.
Attn: Vincent Veccharella
11825 Heron Bay Boulevard
Coral Springs, FL 33076
Lot 3 F
DUNKELBERGER
1225 Omar Rd.
West Palm Beach, FL 33405
\ '-\.0 ~ .... c:9{) 0:1 561-689-4299
Project
Heron Bay-Osprey Lakes
Parkland, FL
Project Number: HD 131567
Based on the results of the attached soil density test results and previously submitted soil borings, the foundation
soils for the subject building at the referenced location, plus a margin of 5 feet, are suitable to support shallow
foundations and a slab-on-grade designed for a net soil contact pressure of 2500 pounds per square foot (psf) and
are in conformance with the Florida Building Code, Chapter 18. Fill which becomes loosened as a result of
foundation excavation, construction traffic or other means shall be recompacted to 95 percent at the ASTM D-1557
maximum dry density prior to placing reinforcing steel and concrete for the substructure.
The representations made in this report are based on periodic observations and spot testing of completed, mass
earthwork. The attached test results reflect conditions at the time the tests were performed at the locations and
depths indicated on the data sheets. It should be recognized that soil conditions may differ locally from those shown
by our observations and tests, or as a result of weather and/or man-caused disturbances subsequent to the testing. If
differing conditions are found during construction, Dunkelberger Engineering & Testing, a TeiTacon Company
(Dunkelberger) should be notified immediately to determine if a change in foundation recommendations is
required. If Dunkelberger is not retained to perform these functions, Dunkelberger will assume no responsibility for
the impact of these conditions on the project.
Dunkelberger warrants that the findings, recommendations, or professional advice contained herein have been
made in accordance with generally accepted professional geotechnical practices in the local area. No other
warranties are implied or expressed.
Services: Perform in-place moisture and density retests as requested or as required by the project specifications to determine
degree of compaction and material moisture condition.
Dunkelberger Rep.: Dennis Torres Ayala
Reported To:
Contractor:
Report Distribution:
( 1) WCI Communities, Inc., Vincent (I) WCI Communities, Inc., Emailed
Vcccharclla
AP.R 1 6 2014 Reviewed By:
roject Manager I, FL Reg. No. 7078
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to
the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CTOOOI, 6·30-11, Rev.9 Page I of 1
FIELD DENSITY TEST REPORT
ReportNumber: HD131567.0022
Service Date: 04/14114
Report Date: 04114114
Task: FIELD TESTING
Client
WCI Communities, Inc.
Attn: Vincent Veccharella
I 1825 Heron Bay Boulevard
Coral Springs, FL 33076
Material Information
Mat.
No.
1
Proctor
Ref. No.
HD131567.0013
Classification and Description
Light gray fine SAND, some
fragmental limestone
Field Test Data
Test
No.
2
Test Location
Lot 3 F
Center of Garage
Cener of Slab
Datum: Final Grading Fill
Lift I
Elev.
Final
Final
Mat.
No.
Project
DUNKELBERGER
engineering & testing, inc.
A 1rerraccn coMPANY
1225 Omar Rd.
West Palm Beach, FL 33405
561-689-4299
Heron Bay -Osprey Lakes
Parkland, FL
Project Number: HD131567
Lab Test Data Project Requirements
Optimum
Water Max. Lab Water
Laboratory Content Density Content Compaction
Test Method {%) {pcf) {%) {%)
ASTM DI557 9.1 113.4 Min98
Probe Wet Water Water Dry Percent
Depth Density Content Content Density Compaction
{in) {pcf) {pcf) (%) (pcf) (%)
12 I 16.9 4.6 4.1 112.3 99
12 122.5 8.4 7.4 I 14.1 101
Serial No: 34268 Std. Cnt. M: 671 Std. Cnt. D: 2538
Comments: Test and/or retest results on this report meet project requirements as noted above.
Services: Perfonn in-place moisture and density retests as requested or as required by the project specifications to
determine degree of compaction and material moisture condition.
Dunkelberger Rep.: Dennis Tones Ayala
Reported To:
Contractor:
Report Distribution:
(I) WCI Communities, Inc., Vincent Vcccharclla (I) WCI Communities, Inc .. Emailcd Reviewed By:
St hen Mrachek, P.E.
anager I, FL Reg. No. 70784
Test Methods: ASTM D6938
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 11·16-12. Rcv.l Page I of I
J1ream
P E S T t I I E I S t•
New Construction Subterranean Termite Treatment
This report is submitted for information purposes to the builder on (new) construction cases where treatment for
prevention of subterranean termite infestation is required by the Florida Building Code, Section 105.16
All contracts for services are between the Pest Control Operator and builder. unless stated otherwise.
Section 1: Hometeam Pest Defense
Company Address 11 00 Barnett Drive #28 City: Lake Worth State: FL Zip: 33461-2619
Company Phone No.: 561-547-1700 Business License No.: JB 166552
Section 2: Builder Information
Company Name: _---loi!JJ~CJ=-------------------
Phone No.:. _____________ _
Section 3: Property Information
Time In: _ ____c:IO~ZD~A_!_""'-
Time Out: _...!...JI/L.:O:....:O::...;.A..:....:.w..t~-
Building Permit No.: B J..!Z't /l{,.D 3 -aD?., y. I I ~~oo~&ru~reoo~~~:~L~I~S~2~'-~M~W-~l~'-~--~~~~-d~~--~~~''~--3~F ______ _
Type of Construction: p(slab D Basement 0 Crawl
Approximate Depth of Footing: Outside: I"'
D Other------------=-------
Type Fill: &_td' Inside: 16
Section 4: Treatment Information
Date(s)ofTreatment(s): uf,•{241i EPARegistrationNo.: 432-1332-AA-73748 I. --~~~~~~------
Brand Name of Product(s) Used: I Maxx Pro Active Ingredient: lmidacloprid
Final Mix Solution: Jl5% · Treatment Area Sq. Ft.: !:>W
ujA Linear Ft. of Masonry Voids: -.~Hf!!LJ~~----Linear Ft.
Total Gallons of Termiticide Applied: ___ ___._.3~~~·z==-------
Service Agreement Available?
Liquid treatment
Liquid Final exterior treatment
Borate treatment:
Bait in lieu of Pretreat
~es DNo
~Yes DNo
DYes ~o DYes o
DYes No
This building has received a complete treatment for the
prevention of subterranean termites. Treatment is in
accordance with the rules and laws established by the
Florida Department of Agricultural and Consumer Services.
Initial ~
Note: Some state laws require service agreements to be issued. This form does not preempt state law.
Attachments (List)------------------------------
Comments. _____ -1----------------------------
RH-NT9/05
.. _ ...
DUNKELBERGER
engineering & testing, inc.
www.dunkelberger-engineering.com
Project Name:
Project No.:
Client:
Attention:
Engineer's Summary Statement
Osprey Lake
Parkland, Florida
FTL-10-0637 (40.6)
WCI Communities, LLC
3001 PGA Blvd., Suite 101
Palm Beach Gardens, Florida 33410
Mr. Nelson Bennett
• Fort Lauderdale
• Port Saint Lucie
• Sarasota
• West Palm Beach
April3, 2013
Lot 3 -Block F
Sheet 1 of2
Based on the results of the attached Standard Penetration Test boring, the foundation soils for the
subject building at the referenced location, are suitable to support shallow foundations and a
slab-on-grade designed for a net soil contact pressure of 2500 pounds per square foot (psf) and
are in conformance with the Florida Building Code, Chapter 18 .. The upper one to two feet of
soils will require densification and should be uniformly compacted to 95 percent of the ASTM D
1557 maximum dry density.
The representations made in this report are based on the attached Standard Penetration Test
boring. The attached test results reflect conditions at the time the boring was performed at the
locations and depths indicated on the data sheets. It should be recognized that soil conditions
may differ locally from those shown by our observations and tests, or as a result of weather
and/or man-caused disturbances subsequent to the testing. If differing conditions are found
during construction, Dunkelberger Engineering & Testing, Inc. (Dunkelberger) should be
notified immediately to determine if a change in foundation recommendations is required. If
Dunkelberger is not retained to perform these functions, Dunkelberger will assume no
responsibility for the impact of these conditions on the project.
Dunkelberger warrants that the fmdings, recommendations, or professional advice contained
herein hav,I\\~Y~~i'JI,~ccordance with generally accepted professional geotechnical practices
in the l~rlo~f.t:~"'~'l~.c~anties are implied or expressed. ~~~~G '·/:' •• -~', ~A:. •• " -•• 1-, S0:" No 707B4 ·.. ~ = ..• : -
Michael J. O'Connor, P.E.
Executive Vice President
FL Registration No. 44082
/ .. ·-0 3 2014
State of Florida Board of Professional Engineers Authorization No. 6870
Toll Free (877) 643.6832
DUNKELBERGER ENGINEERING & TESTING, INC. TEST BORING LOG BORING NO. TB-3 F
Project: Osprey Lake Sheet No.: 2 of2
Client: WCI Communities, LLC ProjectNo.: FTL-10-0637
Boring Location: Center of Lot# 3 Block F Casing_ Rock Core Elevation: N/A
Type: Boring Depth: 10.0'
Diam: Water Depth: 4.7'
Depth: Drilled Date: 12-4-12
Drill Rig: DR2 CME 55 Driller: JM
Contractor: DET Drilling, Inc. Logged By: JM
Depth Sample Blows On Sample "N" Material Description Remarks
(feet) No. Spoon Per 6" Value
1
2 1 6-7-8-9 15 0.0-3.0-Gray fine SAND, trace to some
3 fragmental limestone and trace shell
4 2 7-10-13-38 23 fragments (SP)
5
6 3 38-37-49-31 86 3.0-4.0-Gray well cemented limestone
7
8 4 12-11-11-9 22 4.0-6.0-Gray fme SAND, trace to some
9 fragmental limestone and trace shell
10 5 15-19-18-16 37 fragments (SP)
11
12 6.0-10.0-Gray well cemented limestone
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
DUNKELBERGER DET 52 (Rev. 05/13/2008)
r:')
Home Team
P l S l I) I r I ft S &•
New Construction Subterranean Termite Treatment
This report is submitted for information purposes to the builder on (new) construction cases where treatment for
prevention of subterranean termite lnfestat!on Is required by the Florida Building Code, Section 1 05.16
All contracts for services are between the Pest Control Operator and builder. unless stated otherwise.
Section 1: Hometeam Pest D~fe~se
Company Address 11 00 Barnett Drive #28
Company Phone No.: 561-547-1700
City: Lake Worth State: FL
Business License No.: JB 166552
Zip: 33461-2619
Section 2: Builder lnformatio,~
Company Name: -~W~<:.-~1:.~-----------------Time In: ll~ 3 Z. ·
Phone No.: ,J{l • Time Out: --=--=' !_,_S"" __ _
Section 3: Property Information
Building Permit No.: * B ~Qc, ft.(D~ -cJ 0 ZJ.-1
Location of Structure(s) Treated: J if8tt P,) 12 ~ H~uiY'1V
Type of Construction: 0 Slab 0 Basement 0 Crawl 0 Other ------------------
out 'd j/ lns1'de· lb Type All: ~4 ,l Approximate Depth of Footing: s1 e:¥« · --=-----
! '
Section 4: Treatment Information
-.n !I ''l l-'1 EPA Registration No.: ~4~3:£2-~13~3:=.:2-~M~-7!_:::_3~7 4~8:.__ ____ _ Oate(s) of Treatment(s): _ _:""~O~f-:..L-..1.'~-:...:_.1..-----
Brand Name of Product(s) Used: I Maxx Pro Active Ingredient: lmidacloprid
Anal Mix Solution: .-:.·0~5~%:.____ Treatment Area Sq. Ft.: -~,J~~~-----
..., a. U Linear Ft. of Masonry Voids: _;J~ll\ll----Linear Ft. "7 1-M~G*~~~~~~~~~-~/L/~f~~~----==~~-------~7~~~~
This building has received a complete tni\tment fo~ ~e
prevention of subterranean termites. Treatment IS In
accordance with the rules and laws established by the
Florida Department of Agricultural and Consumer Services.
Service Agreement Available?
Liquid treatment
Liquid Anal exterior treatment
Borate treatment:
Bait in lieu of Pretreat
dYes
~es
~es
DYes
DYes
ONo
ONo
QNo
!i'No
i!!'No Initial 4
t to be issued. This form does not preempt state law. Note: Some state laws require service agreemen s
Attachmenttss~(L:ist~) ======;~---------~==-=~~~::~==
Comments_ Certification No.: -j i 5$b" 'I
Name of Applicator(s): _ii.~M~'U.~~-----:Da:::te:: 08 /t '1/ tV
Authorized Signature
1\11-N'T 9105
-.,. ,.,
Home Team
. P I $ T D I f I • S 1•
New Construction Subterranean Termite Treatment
This report is submitted for information purposes to the builder on (new) construction cases where treatment for
prevention of subterranean termite infestation is required by the Florida Building Code, Section 105.16
All contracts for services are between the Pest Control Operator and builder. unless stated otherwise.
Section 1: Hometeam Pest Defense
Company Address 11 00 Barnett Drive #28 City: Lake Worth State: FL Zip: 33461-2619
Company Phone No.: 561-547-1700 Business License No.: JB 166552
Section 2: Builder Information
Company Name: J.. Time In: 0 L/ {) .4-Nf
Phone No.: _____________ _ TimeOut: 1000 A-,...
Section 3: Property Information
BuildingPermitNo.: B<..P"'J JC/03-002-Y ,
Location of Structure(s) Treated: liSt~ )#} 11 ;-lj d.A"""
Type of Construction: ~Slab D Basement D Crawl D Other -------------..-------
Approximate Depth of Footing: Outside: I"' Inside: 1 c.. Type Fill: s,J
Section 4: Treatment lnf~rmation
Date(s) of Treatment(s): lf{ I ) { 2tJ I~ EPA Registration No.: _4_3_2_-1_33_2_-M_-7_3_7 4_8 _____ _
Brand Name of Product(s) Used: I Maxx Pro Active Ingredient: lmidacloprid
Final Mix Solution: ......:·..::..;05::...;0
/c.:-o __ _
Linear Ft. Jl /1 ,
Treatment Area Sq. Ft.: --"2~1 ___ _
Linear Ft. of Masonry Voids: ~.PM,f£/A_.___ __ _
Total Gallons of Termiticide Applied:------""-'-------
Service Agreement Available?
Liquid treatment
Liquid Final exterior treatment
Borate treatment:
Bait in lieu of Pretreat
)(Yes
~Yes
DYes
DYes
DYes
DNo
DNo
li:No
~No ~0
This building has received a complete treatment for the
prevention of subterranean termites. Treatment is in
accordance with the rules and laws established by the
Florida DepaQ~ent of Agricultural and Consumer Services.
Initial iJ)')
Note: Some state laws require service agreements to be issued. This form does not preempt state law.
Attachments (List)------------------------------
Comments·----+----------------------------
Name of Applicator(s): -+=~=-----....o::....;._____..;._-+-#,rf'-""-~,.__-.------
Authorized Signature --------Dtf.~E::,...~::::.=---Date: ____ l....lf-''-L.../-----'-'-:.........!.-----
RH-NT 9/05