BLDG1403-0069-Energy CalculationsFORM 405-10
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida -Department of Business and Professional Regulation - Residential Performance Method
Project Name:
Street:
City, State, Zip:
Owner:
Design Location:
Osprey- WILLOW
Parkland , FL ,
WCI Communities, LLC
FL, Fort Lauderdale
1. New construction or existing
2. Single family or multiple family
3. Number of units, if multiple family
4. Number of Bedrooms
5. Is this a worst case?
6. Conditioned floor area above grade (ft2)
Conditioned floor area below grade (ft2)
7. Windows(667.9
a. U -Factor:
SHGC:
b. U -Factor:
SHGC:
c. U -Factor.
SHGC:
d. U -Factor:
SHGC:
sqft.) Description
Dbl, U=0.60
SHGC=0.31
Dbl, U=0.38
SHGC=0.31
Dbl, U=0.68
SHGC=0.29
other (see details)
other (see details)
Area Weighted Average Overhang Depth:
Area Weighted Average SHGC:
8. Floor Types (4240.0 sqft.)
a. Slab -On -Grade Edge Insulation
b. Floor Over Other Space
c. other (see details)
Glass/Floor Area: 0.158
New (From Plans)
Single-family
1
5
Yes
4240
0
Insulation
R=0.0
R=0.0
R=
Area
387.56 ft2
132.37 ft2
128.00 ft2
20.00 ft2
4.508 ft.
Builder Name: WCI Communities, LLC
Permit Office: Parkland
Permit Number:
Jurisdiction: 163100
9. Wall Types (4404.0 sqft.)
a. Concrete Block - Int Insul, Exterior
b. Frame - Wood, Adjacent
c. Frame - Wood, Exterior
d. other (see details)
10. Ceiling Types (2771.0 sqft.)
a. Under Attic (Vented)
b. N/A
c. N/A
11. Ducts
a. Sup: Attic, Ret: AC1, AH: AC1
b. Sup: Attic, Ret: AC2, AH: AC2
12. Cooling systems
a. Central Unit
b. Central Unit
13. Heating systems
a. Electric Strip Heat
b. Electric Strip Heat
0.304 14. Hot water systems
a. Natural Gas Tankless
Area
2014.00 ft2
1616.00 ft2
610.00 ft2
Total Proposed Modified
Total Standard Reference
I hereby certify that the plans and specifications covered by
this calculation are in compliance with the Florida Energy
Code. OSCAR L Digitally signed by OSCAR L
CALLEIA
• DN: cn-0SCAR L CALLEIA,
PREPARED BY: a -ENGINEERED AIR LLC,ou,
DATE: CA L L EJ A email=oscarcPenaineeredaidlc.co
Date: 2013.06.19 13:07:42 -04'00'
I hereby certify that this building, as designed, is in compliance
with the Florida Energy'Code.
OWNER/AGEANI -\\�.�'`
DATE:\\'r-k
b. Conservation features
None
15. Credits
Loads: 73.08
Loads: 109.63
Review of the plans and
specifications covered by this
calculation indicates compliance
with the Florida Energy Code.
Before construction is completed
this building will be inspected for
compliance with Section 553.908
Florida Statutes.
Insulation Area
R=4.1 3639.00 ft2
R=11.0 355.00 ft2
R=19.0 340.00 ft2
R= 70.00 ft2
Insulation Area
R=38.0 2771.00 ft2
R= ft2
R= ft2
R ft2
6 300
6 240
kBtu/hr Efficiency
34.8 SEER:14.50
28.8 SEER:14.50
kBtu/hr Efficiency
33.0 COP:1.00
25.0 COP:1.00
Cap: 1 gallons
EF: 0.820
Pstat
PASS
BUILDING OFFICIAL: 3(yszk f T . A
DATE: 't
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with 403.2.2.1.1.
- Compliance requires completion of a Florida Air Barrier and Insulation Inspection Checklist
6/19/2013 12:50 PM
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 1 of 7
Title:
Building Type:
Owner:
# of Units:
Builder Name:
Permit Office:
Jurisdiction:
Family Type:
New/Existing:
Comment:
v
Osprey- WILLOW
User
WCI Communities, LLC
1
WCI Communities, LLC
Parkland
163100
Single-family
New (From Plans)
Design Location
TMY Site
PROJECT
Bedrooms:
Conditioned Area:
Total Stories:
Worst Case:
Rotate Angle:
Cross Ventilation:
Whole House Fan:
FL, Fort Lauderdale FL_FORT_LAUDERDALE
Number
1
2
Number
1
2
V
1
Name
Block1
Block2
Name
AC1
AC2
Area
2014
2226
Area
2014
2226
# Floor Type Space
IECC
Zone
1
Volume
25182.2
22260
5
4240
2
Yes
270
CLIMATE
Design Temp
97.5 % 2.5 %
43 91
BLOCKS
SPACES
Volume Kitchen Occupants
25182.2 Yes 1
22260 No 5
FLOORS
Perimeter Perimeter R -Value Area
1 Slab -On -Grade Edge Insulatio AC1
2 Floor over Garage
3 Floor Over Other Space
# Type
1 Hip
# Type
1 Full attic
6/19/2013 12:50 PM
AC2
AC2
--Materials
Barrel tile
Address Type:
Lot #
Block/SubDivision:
PlatBook:
Street:
County:
City, State, Zip:
Street Address
Broward
Parkland ,
FL ,
Int Design Temp Heating Design Daily Temp
Winter Summer Degree Days Moisture Range
70 75
Bedrooms InfiI ID
1 1
4 1
209 ft 0
ROOF
Roof Gable
Area Area
2014 ft2
610 ft2
1616 ft2
Roof Solar
Color Absor.
2842 ft2 0 ft2 Medium 0.75
ATTIC
Ventilation Vent Ratio (1 in)
Vented
300
321.5 60
Finished
Yes
Yes
Joist R -Value
Cooled
Yes
Yes
Low
Heated
Yes
Yes
Tile Wood Carpet
0 0 1
19 0 0 1
0
0 0 1
SA Emitt Emitt Deck Pitch
Tested Tested Insul. (deg)
Area RBS
2624 ft2 N
No 0.9 No 0 22.6
IRCC
N
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 2 of 7
CEILING
# Ceiling Type Space R-Vaiue
1 Under Attic (Vented) AC1 38
WALLS
Area
2771 ft2
Framing Frac Truss Type
u.11 Wood
Adjacent Cavity Width Height Sheathing Framing Solar Below
# Ornt To Wall Typa Space p_v_abi. Ft In Pt I . - - .. Le .. °.
1 NW=>S Exterior Concrete Block - Int Insul AC1 4.1 9 0 22 0 198.0 ft2 0 0 0.5 0
2 NE=>NW Garage Frame - Wood AC1 11 7 0 10 0 70.0 ft2 0 0.23 0.5 0
3 NW=>S Garage Frame - Wood AC1 11 17 0 10 0 170.0 ft2 0 0.23 0.5 0
4 NW=>S Exterior Concrete Block - Int Insul AC1 4.1 10 0 22 0 220.0 ft2 0 0 0.5 0
5 SW=>SE Exterior Concrete Block - Int Insul AC1 4.1 14 0 22 0 308.0 ft2 0 0 0.5 0
6 NW=>S Garage Frame - Wood AC1 11 5.5 0 10 0 55.0 ft2 0 0.23 0.5 0
7 SE=>NE Exterior Concrete Block - Int Insul AC1 4.1 13 0 12 0 156.0 ft2 0 0 0.5 0
8 NE=>NW Exterior Concrete Block - Int Insul AC1 4.1 14 0 10 0 140.0 ft2 0 0 0.5 0
9 NW=>S Garage Frame - Wood AC1 11 6 0 10 0 60.0 ft2 0 0.23 0.5 0
10 NE=>NW Exterior Concrete Block - Int Insul AC1 4.1 10 0 10 0 100.0 ft2 0 0 0.5 0
11 NW=>S Garage Frame - Wood AC1 19 7 0 10 0 70.0 ft2 0 0.23 0.5 0
12 SW=>SE Exterior Concrete Block - Int Insul AC1 4.1 8 0 10 0 80.0 ft2 0 0 0.5 0
13 SE=>NE Exterior Concrete Block - Int Insul AC1 4.1 19.5 0 12 0 234.0 ft2 0 0 0.5 0
14 SE=>NE Exterior Concrete Block - Int Insul AC1 4.1 5 0 12 0 60.0 ft2 0 0 0.5 0
15 NE=>NW Exterior Concrete Block - Int Insul AC1 4.1 8.5 0 10 0 85.0 ft2 0 0 . 0.5 0
16 SW=>SE Exterior Concrete Block - Int Insul AC1 4.1 26 0 12 0 312.0 ft2 0 0 0.5 0
17 SE=>NE Exterior Concrete Block - Int Insul AC1 4.1 5 0 10 0 50.0 ft2 0 0 0.5 0
18 SW=>SE Exterior Concrete Block - Int Insul AC1 4.1 9.5 0 10 0 95.0 112 0 0 0.5 0
19 NE=>NW Exterior Concrete Block - Int Insul AC1 4.1 9.5 0 10 0 95.0 ft2 0 0 0.5 0
20 SE=>NE Exterior Concrete Block - Int Insul AC1 4.1 5.4 0 10 0 54.0 ft2 0 0 0.5 0
21 SW=>SE Exterior Concrete Block - Int Insul AC2 4.1 4.5 0 10 0 45.0 ft2 0 0 0.5 0
22 SW=>SE Exterior Concrete Block - Int Insul AC2 4.1 21 0 10 0 210.0 ft2 0 0 0.5 0
23 NE=>NW Exterior Concrete Block - Int Insul AC2 4.1 18.5 0 10 0 185.0 ft2 0 0 0.5 0
24 SE=>NE Exterior Concrete Block - Int Insul AC2 4.1 12.5 0 10 0 125.0 ft2 0 0 0.5 0
25 NW=>S Exterior Frame - Wood AC2 19 17 0 10 0 170.0 ft2 0 0.23 0.5 0
26 NE=>NW Exterior Concrete Block - Int Insul AC2 4.1 13.5 0 10 0 135.0 ft2 0 0 0.5 0
27 NE=>NW Exterior Concrete Block - Int Insul AC2 4.1 3.5 0 10 0 35.0 ft2 0 0 0.5 0
28 NW=>S Exterior Concrete Block - Int Insul AC2 4.1 14 0 10 0 140.0 ft2 0 0 0.5 0
29 SW=>SE Exterior Concrete Block - Int Insul AC2 4.1 14.2 0 10 0 142.0 ft2 0 0 0.5 0
30 SW=>SE Exterior Concrete Block - Int Insul AC2 4.1 4.5 0 10 0 45.0 ft2 0 0 0.5 0
31 SE=>NE Exterior Concrete Block - Int Insul AC2 4.1 15 0 10 0 150.0 ft2 0 0 0.5 0
32 NE=>NW Exterior Concrete Block - Int Insul AC2 4.1 10 0 10 0 100.0 ft2 0 0 0.5 0
33 NE=>NW Exterior Concrete Block - Int Insul AC2 4.1 9 0 10 0 90.0 ft2 0 0 0.5 0
34 SE=>NE Exterior Concrete Block - Int Insul - AC2 4.1 5 0 10 0 50.0 ft2 0 0 0.5 0
35 NW=>S Exterior Frame - Wood AC2 19 12 0 10 0 120.0 ft2 0 0.23 0.5 0
36 NE=>NW Exterior Frame - Wood AC2 19 5 0 10 0 50.0 ft2 0 0.23 0.5 0
6/19/2013 12:50 PM
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 3 of 7
v'
DOORS
# Ornt Door Type Space Storms U-Vaiue Width Height Area
Ft In Ft In
1 NW=>S Insulated AC1 None .6 6 8 48 ft2
2 NW=>S Insulated AC1 None .35 2.8 8 22.4 ft2
WINDOWS
Orientation shown is the entered orientation (=>) changed to Worst Case.
Wall Overhang
V# Ornt ID Frame Panes NFRC U -Factor SHGC Area Depth Separation Int Shade Screening
1 NW=>SW 1 Metal Low -E Double Yes 0.38 0.31 24.0 ft2 6 ft 0 in 0.01 ft 0 i None None
2 NW=>SW4 Metal Low -E Double Yes 0.6 0.31 39.0 ft2 1.67 ft 0 i 14 ft 0 in None None
3 SW=>SE 5 Metal Low -E Double Yes 0.6 0.31 39.0 ft2 1.67 ft 0 i 14 ft 0 in None None
4 NW=>SW4 Metal Low -E Double Yes 0.38 0.31 32.3 ft2 1.67 ft 01 2 ft 0 in None None
5 SW=>SE 5 Metal Low -E Double Yes 0.38 0.31 32.3 ft2 1.67 ft 0 i 2 ft 0 in None None
6 SE=>NE 7 Metal Low -E Double Yes 0.6 0.31 32.5 ft2 1.67 ft 0 i 14 ft 0 in None None
7 NE=>NW10 Metal Low -E Double Yes 0.6 0.31 16.2 ft2 1.67 ft 0 i 2 ft 0 in None None
8 SE=>NE 13 Metal Low -E Double Yes 0.68 0.29 128.0 ft2 11 ft 0 in 1 ft 0 in None None
9 SE=>NE 14 Metal Low -E Double Yes 0.6 0.31 16.2 ft2 1.67 ft 0 i 14 ft 0 in None None
10 NE=>NW15 Metal Low -E Double Yes 0.6 0.31 16.2 ft2 1.67 ft 0 i 14 ft0 in None None
11 SW=>SE 16 Metal Low -E Double Yes 0.6 0.31 16.2 ft2 1.67 ft0 i 14 ft 0 in None None
12 SE=>NE 17 Metal Low -E Double Yes 0.6 0.31 16.2 ft2 11 ft 0 in 1 ft 0 in None None
13 SW=>SE18 Metal Low -E Double Yes 0.6 0.31 9.0 ft2 1.67 ft 0 i 14 ft 0 in None None
14 NE=>NW19 Metal Low -E Double Yes 0.75 0.25 20.0 ft2 24 ft 0 in 1 ft 0 in None None
15 SW=>SE22 Metal Low -E Double Yes 0.6 0.31 32.3 52 1.67 ft 0 i 2 ft0 in None None
16 SW=>SE22 Metal Low -E Double Yes 0.38 0.31 16.2 ft2 1.67 ft 0 i 2 ft 0 in None None
17 NE=>NW23 Metal Low -E Double Yes 0.6 0.31 32.3 ft2 1.67 ft 0 i 2 ft 0 in None None
18 SE=>NE 24 Metal Low -E Double Yes 0.6 0.31 32.5 52 1.67 ft 01 2 ft 0 in None None
19 NW=>SW25 Metal Low -E Double Yes 0.38 0.31 20.6 ft2 1.67 ft 01 2 ft 0 in None None
20 NE=>NW26 Metal Low -E Double Yes 0.38 0.31 6.9 52 1.67 ft 01 2 ft 0 in None None
21 NE=>NW27 Metal Low -E Double Yes 0.6 0.31 9.0 52 1.67 ft 0 i 2 ft 0 in None None
22 NW=>SW28 Metal Low -E Double Yes 0.6 0.31 16.2 ft2 1.67 ft 01 2 ft 0 in None None
23 SW=>SE29 Metal Low -E Double Yes 0.6 0.31 16.2 ft2 1.67 ft 01 2 ft 0 in None None
24 SE=>NE 31 Metal Low -E Double Yes 0.6 0.31 16.2 52 1.67 ft 0 i 2 ft 0 in None None
25 NE=>NW32 Metal Low -E Double Yes 0.6 0.31 16.2 52 1.67 ft 01 2 ft 0 in None None
26 NW=>SW35 Metal Low -E Double Yes 0.6 0.31 16.2 52 1.67 ft 01 2 ft 0 in None None
GARAGE
Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation
1 747.00003 52 137 52 64 ft 10 ft 1
6/19/2013 12:50 PM
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 4 of 7
INFILTRATION
# Scope Method SLA. CFM 50 ELA E -LA ACH ACH 50-
1 Wholehouse Best Guess .0005 5560.8 305.28 574.12 .4247 7.0327
HEATING SYSTEM
# System Type Subtype Efficiency Capacity Block Ducts
1 Electric Strip Heat None COP: 1 33 kBtu/hr 1 sys#1
2 Electric Strip Heat None COP: 1 25 kBtu/hr 2 sys#2
COOLING SYSTEM
V # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit Split SEER: 14.5 34.8 kBtu/hr 1044 cfm 0.78 1 sys#1
2 Central Unit Split SEER: 14.5 28.8 kBtu/hr 864 cfm 0.75 2 sys#2
v
HOT WATER SYSTEM
# System Type SubType Location EF Cap Use SetPnt
1 Natural Gas Tankless Garage 0.82 1 gal 80 gal 120 deg
FSEC
Cert #
Company Name
None None
SOLAR HOT WATER SYSTEM
System Model #
DUCTS
Conservation
None
Collector Storage
Collector Model # Area Volume FEF
ft2
— Supply -- — Retum — Air CFM 25 CFM25 HVAC #
# Location R -Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool
1 Attic 6 300 ft2 AC1 50 ft2 Default Leakage AC1 (Default) (Default) 1 1
2 Attic 6 240 ft2 AC2 106 ft2 Default Leakage AC2 (Default) (Default) 2 2
TEMPERATURES
Programable Thermostat: Y Ceiling Fans: jX
HeatingCooling Jan Feb Mar Apr May Jun
Jul
Aug
Sep Oct Nov Dec
entinJan X Feb Feb X Mar X1 Aar pr 1 1 May l 1 Jun X] Jr ul Aul g x] Sep Oct X X Oct X Nov X Dec
6/19/2013 12:50 PM
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 5 of 7
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling (WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling (WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating (WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
Heating (WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
6/19/2013 12:50 PM
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 6 of 7
FORM 405-10
Florida Code Compliance Checklist
Florida Department of Business and Professional Regulations
Residential Whale Building Performance Method
ADDRESS: PERMIT #:
Parkland, FL,
MANDATORY REQUIREMENTS SUMMARY - See individual code sections for full details.
COMPONENT SECTION SUMMARY OF REQUIREMENT(S) CHECK
Air leakage 402.4 To be caulked, gasketed, weatherstripped or otherwise sealed.
Recessed lighting IC -rated as meeting ASTM E 283. Windows and
doors = 0.30 cfm/sq.ft. Testing or visual inspection required. Fireplaces:
gasketed doors & outdoor combustion air. Must complete envelope
leakage report or visually verify Table 402.4.2.
Thermostat & 403.1 At least one thermostat shall be provided for each separate heating and
controls cooling system. Where forced -air furnace is primary system,
programmable thermostat is required. Heat pumps with supplemental
electric heat must prevent supplemental heat when compressor can
meet the load.
Ducts 403.2.2 All ducts, air handlers, filter boxes and building cavities which form the
primary air containment passageways for air distribution systems shall
be considered ducts or plenum chambers, shall be constructed and
sealed in accordance with Section 503.2.7.2 of this code.
403.3.3 Building framing cavities shall not be used as supply ducts.
Water heaters 403.4 Heat trap required for vertical pipe risers. Comply with efficiencies in
Table 403.4.3.2. Provide switch or clearly marked circuit breaker
(electric) or shutoff (gas). Circulating system pipes insulated to = R-2
+ accessible manual OFF switch.
Mechanical 403.5 Homes designed to operate at positive pressure or with mechanical
ventilation ventilation systems shall not exceed the minimum ASHRAE 62 level.
No make-up air from attics, crawlspaces, garages or outdoors adjacent
to pools or spas.
Swimming Pools 403.9 Pool pumps and pool pump motors with a total horsepower (HP) of = 1
& Spas HP shall have the capability of operating at two or more speeds. Spas-
and
pasand heated pools must have vapor -retardant covers or a liquid cover or
other means proven to reduce heat Toss except if 70% of heat from
site -recovered energy. Off/timer switch required. Gas heaters minimum
thermal efficiency=78% (82% after 4/16/13). Heat pump pool heaters
minimum COP= 4.0.
Cooling/heating 403.6 Sizing calculation performed & attached. Minimum efficiencies per
Tables 503.2.3. Equipment efficiency verification required. Special
equipment occasion cooling or -heating capacity requires separate system or
variable capacity system. Electric heat >10kW must be divided into two
or more stages.
Ceilings/knee walls 405.2.1 R-19 space permitting.
6/19/2013 12:50 PM
1
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 7 of 7
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 67
The lower the EnergyPerformance Index, the more efficient the home.
1. New construction or existing
2. Single family or multiple family
3. Number of units, if multiple family
4. Number of Bedrooms
5. Is this a worst case?
6. Conditioned floor area (ft2)
7. Windows"
a. U -Factor:
SHGC:
b. U -Factor:
SHGC:
c. U -Factor:
SHGC:
d. U -Factor:
SHGC:
Area Weighted Average
Area Weighted Average
Description
Dbl, U=0.60
SHGC=0.31
Dbl, U=0.38
SHGC=0.31
Dbl, U=0.68
SHGC=0.29
other (see details)
other (see details)
Overhang Depth:
SHGC:
8. Floor Types
a. Slab -On -Grade Edge Insulation
b. Floor Over Other Space
c. other (see details)
New (From Plans)
Single-family
1
5
Yes
4240
Insulation
R=0.0
R=0.0
R=
Area
387.56 ft2
132.37 ft2
128.00 ft2
20.00 ft2
4.508 ft.
0.304
Area
2014.00 ft2
1616.00 ft2
610.00 ft2
, Parkland, FL,
9. Wall Types
a. Concrete Block - Int Insul, Exterior
b. Frame - Wood, Adjacent
c. Frame - Wood, Exterior
d. other (see details)
10. Ceiling Types
a. Under Attic (Vented)
b. N/A
c. N/A
11. Ducts
a. Sup: Attic, Ret: AC1, AH: AC1
b. Sup: Attic, Ret: AC2, AH: AC2
12. Cooling systems
a. Central Unit
b. Central Unit
13. Heating systems
a. Electric Strip Heat
b. Electric Strip Heat
14. Hot water systems
a. Natural Gas
b. Conservation features
None
15. Credits
I certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded)
in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code compliant features.
Builder Signatur.
Address of New Hom
Date:
Insulation Area
R=4.1 3639.00 ft2
R=11.0 355.00 ft2
R=19.0 340.00 ft2
R= 70.00 ft2
Insulation Area
R=38.0 2771.00 ft2
R= ft2
R= ft2
R ft2
6 300
6 240
kBtu/hr Efficiency
34.8 SEER:14.50
28.8 SEER:14.50
kBtu/hr Efficiency
33.0 COP:1.00
25.0 COP:1.00
Cap: 1 gallons
EF: 0.82
Pstat
City/FL Zip:
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at (321)
638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's
support staff.
**Label required by Section 303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software
Project Report
mearogrovitimow
Project Title:
Designed By:
Project Date:
Client Name:
Company Name:
Company Representative:
Company Address:
Company City:
Company Phone:
Company Fax:
Company E -Mail Address:
Company Comment:
r De t a_Dat
Reference City:
Building Orientation:
Daily Temperature Range:
Latitude:
Elevation:
Altitude Factor:
Winter:
Summer:
rreS
Osprey- WILLOW
Oscar L. Calleja
6/15/13
WCI Communities, LLC
Engineered Air, LLC
Oscar L. Calleja
2520 N Andrews Ave. Ext
Pompano Beach, FI 33064
954-449-1600
954-973-1883
oscarc@engineeredairlIc.com
License No. CAC045860
Outdoor
Dry Bulb
46
90.9
Total Building Supply CFM:
Square ft. of Room Area:
Volume (ft3) of Cond. Space:
Total Heatingequired Including Ventilation ir:
Total Sensible Gain:
Total Latent Gain:
Total Cooling Required Including Ventilation Air:
Outdoor
Wet Bulb
43.16
78.4
26
10
1.000
E. Fort Lauderdale, Florida
Front door faces Northwest
Medium
Degrees
ft.
Outdoor
Rel.Hum
n/a
58%
Indoor
Rel.Hum
n/a
50%
Indoor
Dry Bulb
70
75
Grains
Difference
n/a
62
Development, Inc.
Osprey WILLOW
Page 2
2,600
4,240
45,777
CFM Per Square ft.:
Square ft. Per Ton:
41,:41 Btuh
46,738 Btuh
12,952 Btuh
59,690 Btuh
0.613
852
41.841 MBH
78 %
22
4.97 Tons (Based On Sensible + Latent)
Ifit . tv
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\Users\Oscarc\Documents\Elite Software\Rhvac 9 Projects\WCI-Willow.rh9 Wednesday, June 19, 2013, 1:04 PM
vac - Residential & Light:Gommercial HVAC Loads
Engineered Air LIC
Margate, FL, -3 3
Total Building Summary Loads (cont'd)
e Software Developnent, Inc.
M1t1LiOW'
1?ag�4
�m
,� ,-.� .., mow?, ..: � v rnk �� 11111
Be sure to select a unit that meets both sensible and latent Toads according to the manufacturer's performance data at
your design conditions.
C:\Users\Oscarc\Documents\Elite Software\Rhvac 9 Projects\WCI-Wllow.rh9 Wednesday, June 19, 2013, 1:04 PM
Rhvac Residential & 1
Eri neefed Air L1.0
of ate L_ 33 3
Total Building Summary Loads
htGommerciai HVAC Loads
1te.,S ?ftware pevet.opplent
Osbre W#'Lt
0UV
Palle 31
WCI-FixGl: Glazing-WCI-Fixed Glass, u -value 0.38,
SHGC 0.31
WCI-SH: Glazing-WCI-SH-dbl-low-e, u -value 0.6, SHGC
0.31
WCI-FixGI: Glazing-WCI-Fixed Glass, u -value 0.38,
SHGC 0.31
WCI-SlidinfGl: Glazing-WCI-Sliding GI dbl-low e, u -value
0.68, SHGC 0.29
WCI-SH: Glazing-WCI-SH, u -value 0.6, SHGC 0.31 97.2 1,401
WCI-French: Glazing-WCI-French Door, u -value 0.75, 20 360
SHGC 0.25 48
11J: Door -Metal - Fiberglass Core
11N: Door -Metal - Polystyrene Core 22.4
13A-4ocs: Wall -Block, board insulation only, R-4 board 2959.9
insulation, open core, siding finish
12B-Obw: Part -Frame, R-11 insulation in 2 x 4 stud 332.6
cavity, no board insulation, brick finish, wood studs 70
12B-Osw: Part -Frame, R-11 insulation in 2 x 4 stud
cavity, no board insulation, siding finish, wood studs
12E-Obw: Wall -Frame, R-19 insulation in 2 x 6 stud 303.2
cavity, no board insulation, brick finish, wood studs
16D-38: Roof/Ceiling-Under Attic with Insulation on Attic 2771.8
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark Tile,
Slate or Concrete, R-38 insulation
22A-pI-c: Floor -Slab on grade, No edge insulation, no 113 2,682
insulation below floor, carpet covering, passive, light
dry soil
22A -p►: Floor -Slab on grade, No edge insulation, no 96 2,280
insulation below floor, any floor cover, passive, light
dry soil
20P -19-c: Floor -Over open crawl space or garage, 610.2 732
Passive, R-19 blanket insulation, carpet covering
Subtotals for structure:
People:
Equipment:
Lighting:
Ductwork:
Infiltration: Winter CFM: 221, Summer CFM: 173
Ventilation: Winter CFM: 0, Summer CFM: 0
AED Excursion:
Total Building Load Totals:
Total Building Supply CFM:
Square ft. of Room Area:
Volume (ft3) of Cond. Space:
30.9 281
290.3
101.5
128
4,183
924
2,089
691
157
10,156
645
136
495
1,728
2,600
4,240
45,777
Total Heating Required Including Ventilation Air:
Total Sensible Gain:
Total Latent Gain:
Total Cooling Required Including Ventilation Air:
41,841
46,738
12,952
59,690
6
80
28,940
7,057
5,844
0
0
855 855
0 8,750 8,750
0 2,636 2,636
0 2,169 2,169
0 2,658 2,658
0 588 588
0 775 775
0 118 118
0 6,854 6,854
0 484 484
0 102 102
0 254 254
0 2,227 2,227
0 0 0
0 0 0
0 333 333
0 28,803
1,560 1,380
2,300 5,000
273
1,763 7,457
7,329 3,029
0 0
0 796
41,841 12,952 46,738
CFM Per Square ft.:
Square ft. Per Ton:
Btuh
Btuh
Btuh
Btuh
28,803
2,940
7,300
273
9,220
10,358
0
796
59,690
0.613
852
111,11
41.841 MBH
78 %
22 %
4.97 Tons (Based On Sensible + Latent)
` bt1 i -fa ft -01 > d ee M..,. Sof Ste C''. .3 .
Rhvac is an AC8A approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
C:\Users\Oscarc\Documents\Elite Software\Rhvac 9 Projects\WCI-Willow.rh9 Wednesday, June 19, 2013, 1:04 PM
Rhvac Res dentiat &Light Commercial MVAC Loads
Engineered Air LLC'
Margate, FL.;
Rhvac Res denfiatl
Engineer
Margate,
Equipment Data - System 1 - AC -1
Light "Corrnme
ctal HVAC Loads
Cooling
System Type:
Outdoor Model:
Indoor Model:
Tradename:
Outdoor Manufacturer:
AHRI Reference No.:
Nominal Capacity:
Efficiency:
Heating
System Type:
Model:
Capacity:
Efficiency:
Standard Air Conditioner
CA16NA036****A
FB4CNF042
16 SEER PURON AC
CARRIER AIR CONDITIONING
4584647
34800
14.5 SEER
Electric Resistance
10 KW
0
0%
are Develop,?nenj
Osprey-
This system's equipment was selected in accordance with ACCA Manual S.
Manual S equipment sizing data: SODB: 90.9F, SOWB: 78.4F, WODB: 46F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen.
gain: 24,997 Btuh, Lat. gain: 7,041 Btuh, Sen. loss: 21,856 Btuh, Entering clg. coil DB: 75F, Entering clg. coil WB: 62.5F,
Entering htg. coil DB: 70F, Clg. coil TD: 20F, Htg. coil TD: 20F, Req. clg. airflow: 1137 CFM, Req. htg. airflow: 994 CFM
e7:1
C:\Users\Oscarc\Documents\Elite Software\Rhvac 9 Projects\WCI-Willow.rh9 Wednesday, June 19, 2013, 1:04 PM
Rhvac Residential^& Light Commercial HVAC Loads T
Engineered Air, LIC'`_
Margate, FL; 33063
Equipment Data - System 2 - AC -2
ofware Deveiopthent
Cooling
System Type:
Outdoor Model:
Indoor Model:
Tradename:
Outdoor Manufacturer:
AHRI Reference No.:
Nominal Capacity:
Efficiency:
Heating
System Type:
Model:
Capacity:
Efficiency:
Standard Air Conditioner
CA16NA030****A
FB4CNF036
16 SEER PURON AC
CARRIER AIR CONDITIONING
4584321
28800
14.5 SEER
Electric Resistance
8 KW
0
0%
ge;8
This system's equipment was selected in accordance with ACCA Manual S.
Manual S equipment sizing data: SODB: 90.9F, SOWS: 78.4F, WODB: 46F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen.
gain: 21,741 Btuh, Lat. gain: 5,910 Btuh, Sen. loss: 19,985 Btuh, Entering clg. coil DB: 75F, Entering clg. coil WB: 62.5F,
Entering htg. coil DB: 70F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 989 CFM, Req. htg. airflow: 260 CFM
C:\Users\Oscarc\Documents\Elite Software\Rhvac 9 Projects\WCI-Willow.rh9 Wednesday, June 19, 2013, 1:04 PM
Rhvac - Residential& Light Commercial; HVAC Loads
Eng€neered'Air;
Narrate;. F
Building Rotation Report
lite Softwa
3eve1o) menu Inc.
Osprey- WILLOW'.
Page 9,.
All rotation degree values in this report are clockwise with respect to the project's original orientation.
Building orientation as entered (zero degrees rotation): Front door faces Northwest
At least one system with its System Air Type input set to Fixed was changed to Auto during the building rotation. If you
want to change this behavior uncheck the option on the General tab of the Select Reports dialog called "Always use Auto
for System Air Type for Building Rotation Report."
System 1:
Zone 1:
1 Foyer-Grd FI 110 101 *119 101 101 101 101 101 1--7
2 Powder & Hall *39 39 39 39 39 39 39 39 1-4
3 Living Room 289 269 *320 293 291 265 275 265 1--10
4 Dining *11 11 11 11 11 11 11 11 1--4
5 Den 130 111 140 *157 132 111 128 141 1-8
6 Den WIC *12 12 12 12 12 12 12 12 1--4
7 Bathroom #4 *55 55 55 55 55 55 55 55 1--5
8 Grd FI Stairs *26 26 26 26 26 26 26 26 1--4
9 Family Room 240 232 258 254 *336 229 326 229 2--8
10 Kitchen & Nook 200 205 *216 203 214 202 207 183 1-9
11 Cabana Bath *97 97 97 97 97 97 97 97 1--6
System 2:
Zone 1:
12 Loft WIC 9 9 9 9 9 9 *9 9 1-4
13 Stairs -Loft 135 *167 145 101 145 167 135 101 1--8
14 Laundry 17 17 17 17 17 17 *17 17 1-4
15 Master Bedroom 238 230 231 232 238 230 *246 232 1--10
16 Master WIC 16 16 16 16 16 16 *16 16 1-4
17 Master Bath 104 88 101 *107 94 88 97 107 1--7
18 Master Toilet 23 *28 21 15 21 28 23 15 1--4
19 Bathroom #2 3 3 3 3 3 3 *3 3 1-4
20 Bedroom #2 149 144 *152 146 149 144 146 146 1-8
21 WIC #2 13 13 13 13 13 13 *13 13 1-4
22 Bedroom #3 144 139 140 141 144 139 *148 141 1--8
23 Bathroom #3 4 4 4 4 4 4 *4 4 1--4
24 WIC #3 29 29 29 29 29 29 *29 29 1--4
25 Bedroom #4 98 83 98 *106 95 83 95 106 1--6
26 WIC #4 5 5 5 5 5 5 *5 5 1-4
* Indicates highest CFM of all rotations.
Northwest
45° North
90° Northeast
135° East
180° Southeast
225° South
270° Southwest
315° West
* Indicates highest value of all rotations.
2,125
2,042
*2,203
2,098
2,201
2,026
2,176
1,986
46,742
44,902
*48,445
46,143
48,398
44,561
47,847
43,685
12,953
12,957
12,955
12,955
*12,959
12,957
12,955
12,955
4.97
4.82
*5.12
4.92
5.11
4.79
5.07
4.72
C:\Users\Oscarc\Documents\Elite Software\Rhvac 9 Projects\WCI-Willow.rh9 Wednesday, June 19, 2013, 1:04 PM
Rhvac Residential
Engtneered Art L#
Ma ate, FL 3063
Building Rotation Report (cont'd)
- erdial HVAC loads
lite Software Developmentlne:
Osprey WILLOW
ege l0'
0° Northwest
45°
90°
135°
180°
225°
270°
315°
North
Northeast
East
Southeast
South
Southwest
West
* Indicates highest value of all rotations.
1,137
1,067
1,218
1,153
*1,219
1,051
1,189
1,041
24,997
23,460
26,782
25,356
*26,814
23,119
26,157
22,898
*7,041
7,041
7,041
7,041
7,041
7,041
7,041
7,041
k[I
2.67
2.54
2.82
2.70
*2.82
2.51
2.77
2.49
45°
90°
135°
1800
225°
270°
315°
Northwest
North
Northeast
East
Southeast
South
Southwest
West
* Indicates highest value of all rotations.
5.2
5.1
F,- 5.0
F-
4.8
*989 21,745 5,912 *2.30
975 21,442 5,916 2.28
985 21,663 5,914 2.30
945 20,787 5,914 2.23
981 21,584 *5,918 2.29
975 21,442 5,916 2.28
986 21,691 5,913 2.30
945 20,787 5,914 2.23
Building Rotation Tonnage
4.7
Northwest
North
--$ Building Net Tonnage
Northeast East Southeast South Southwest West
Direction Front door Faces