HomeMy WebLinkAboutBLDG1309-0165-Plans (4)I�`Toll Architecture!. August 26, 2014 Building Official City of Parkland Building Department RE: TRUSS LAYOUTS Parkland G&CC — Monogram, Lot 37D, Bolano, Dear Building Official, Our office has reviewed the truss placement and they quantity of plies of the girder truss on the Bolano Lot37D and finds the structure will adequately carry the load superimposed by the truss system. The truss shown on S3.02 and S4.02 is schematic and conceptual and the truss layouts from the truss engineer is supersede. The exact amount of plies of the girder truss shall be decided by the truss engineer. The spacing between the F4 and F4A trusses has been checked, and it's acceptable to have 24" o.c. in lieu of 16" o.c. Please call me if you have any questions. Sincerely, Sang-Yub Lee, P.E., M.S. (FL #72328) Toll Architecture 2966 Commerce Park Drive Suite 100 Orlando, FL 32819 /< 2_6 — (f. FLORIDA DIVISION 2966 Commerce Park Drive Suite 100 ■ Orlando, FL 32819 ■ (407) 248-5800 • FAX: (407) 248-5899 HORSHAM ■ PHILADELPHIA ■ ORLANDO • SCOTTSDALE ■ LOS ANGELES A Toll `Brothers COMPANY 3A1YA 38010 AOd In +P co N N 1-% `h 00 V 99 Cn ;.p W N !-+ rs > 421 O = ° rn n.._ �K .G N0 I-• EA, 0� ca 'C f. tD O O O n so o- e,) • - 2,0 : 0 - 0 oro O o K 0 '•7' p0j a 0' O 9. O O a' O a. ca `C• y -s O '-• .. e0n114D 03 E.n°cox'ir,g ,r'4e� � q=i o� K oc�o�° �y �`°ir° a.°�GQ� txn n T3 LL O y Oeqc 0 N O .1. 8. a n T C 'Ofl O OZ a O sv 0 Elf 0 o� qOyvi ° O coro O°�OytnQ, r�oEti �m°�o ° o • o r0. ii, QYy�°n5uo5a)a c*rd) oi¢; `�y�y• C,W y 1 tDy to RN _ bA°s'.vbnAD- O to4"NI-�O.an 41" to ss. r ,p 0 K -I O m Onc"��.. y r• 0 r ° o�==at .et..�'cac SDc� °mr,-°rn—mnOO art 2 0 r S -ss " v=C fp fy'1 =Dco .. • ea VI r 0 — O .s O tD Q,• y G' ? en e c P• as 0) a C "� o �s M, K `� �. t�Oip. r' n' y a O c. so 0 w lo !D �' 0 D .4 y arca 0. e a c tie ¢ ca A a y' 5. H, O '�° M ft. i s °a a- 8 C C' Q. C O. Cr�! ty-.i 0. a y vOi O" "`CSC cD ' tD 'Ot G C W O. fS. al O iD eC eT n C f......0- it y to 7 G. at O fl ny tri , ,a a• .o•tOx41H Oc1.L.OOr* cy OOo O O( P - -,r ncD 01 mc _ �� = a 5. �4o�floEn :Z.4 attRc.-a 0, OasQ5 " i ' °"n nwc�0�o_'Oft. yCCpy:rs�. mo a''C tD OC"O GmOiO.O w n. C ct O °yAQ CL v' m Q`b'Ca , n ° rm3im'`4 =.^' oK- t t .1° o ' an y D a A3 Dpn ymw. o C' O0 yR. n to C O OU:fl c is,°�C1. O SU f1 3.". �a3 ,m J tS ° 0 C o O y y nW iii p4O !t D R tDacDan 0-1 61' 'O3a is 0 cobe.O° , •a"c ,R rn a ; Q 4 ft• y it 82 s r :: a' — ' D..4. 'COo _Ooo,Et'arfsmy „w^'7. D 20T om.rto,yogm mo el 0.. n - . g- CT5. 7y°G s t� O n G 0a0pX, I.. i C. O 9, rt: = C' r- .. 0 D co Y co O e•e o co 0 o0estm^DC`N OA y Q (0 ,T,. a c ,A #D ea s1. c m 0.9' q s . 00 a' 0G r gcD O c+ c °as cD -t y to m m 9CD 03 tD 8010d cIJd D 0 NOTES AND DETtII S :SIJL.UN NUL.LvJttttli IRRIGATION LEGEND i� HUNTER SPRAY HEAD OR SHRUB ADAPTOR X HUNTER ROTOR HEAD HUNTER ELECTRIC VALVE GA HUNTER CONTROLLER WITH RAIN SENSOR PVB BACKFLOW PREVENTER NOT SHOWN: • CLASS 200 LA ffERAL PIPE • SCH 40 MAIN LINE WITH LOW VOLTAGE WIRE MINIMUM 16 GAUGE • SCH 40 SLEEVES 2 SIZES LARGER CHAPTER 16, SECTION 1524 HiGH VELOCITY HURRICANE ZONES REQUIRED OWNERS NOTIFICATION FOR ROOFING( CONSIDERATIONS 1524.1 Scope_ As it pertains to this section, it is the responsibility of the roofing contractor to provide the owner with the required roofing permit, and to explain to the owner tt le content of this section. The provisions of Chapfer 15 of the Florida Building Code, Building govern the minimum requirements and standards of the industry for roofing system installations. Additionally, he following items should be addressed as part of the agreement between the owner and the coNtractor. The owner's initials in the noted space indicates that the item has been explained. esthetics -workmanship: The workmanship provisions of Chapfer 15 (High -Velocity Hurricane Zone) are for the purpose of providing the roofing system mets the wind resistance and water intrusion performance standards. Aesthetics (appearance) ere not a consideration with respect to workmanship provisions. Aesthetic issues such as color or c rchitectural appearance, that are not part of a zoning code should be addressed as part of th.: agreement between the owner the contractor. 2 Renalling wood decks: When replacing roofing, the existing wood roof deck may have io be renailed in accordance with current provisions of Chapter 1,; (High -Velocity Hurricane Zones) of the Florida Building Code, Building. (The roof deck is usual y concealed prior to Removing the existing roof system.) . Common roofs: Common roofs are those which have no visible delineation between neighboring units (ie., townhouses, condominiums, etc.). In buildings with :ommon roofs, the roofing contractor and/or owner should notify the occupants of adjacent units of roofing work to be performed. xposed ceilings: Exposed, open beam ceilings are where the underside of the roof decking can be viewed from below. The owner may wish to maintain the architectural appearance; therefore, o.;, -roofing nail penetrations of the underside of the decking ma,� not be acceptable. The owner provides the option of maintaining this appearance. Ponding water. The current roof system and/or deck of the building may not drain well and may cause water to pond (accumulate) in low-lying areas of the -oof. Ponding can be an indication of structural distress and may require the review of a professional structural engineer. Ponding may shorten the life expectancy and performance of the new roofing system. Ponding conditions may not be evident until the original roofing system is removed. Ponding conditions should be c.rrected. Overflow scuppers (wall outlets): It is required that rainwater flow off so that the roof is not overloaded from a buildup of water. Perimeter/edge walls or other roof extensions may block this discharge if overflow scuppers wall outlets) are not provided. It may be necessary to install overflow scuppers in accordance with the requirements of: Chapters 16 and 16 herein and the arida Building Code, Plumbing. 7. Ventilation: Most roof structures should have some ability to vent natural airflow through the interior of the structural assembly (the building itself). The exi,iing amount of attic ventilation shall not be reduced. Exception: Attic spaces, designed by a Florida -licensed engineer or r:istered architect to eliminate attic venting, venting shall not be required. 00 Ow'ner's/Agent's Signature D le Contractor's Signature Florida Building Code Edition 2010 High Velocity Hurricane Zone Uniform Permit Application Form Section A (General Inforjnation) Master Permit No. Process No. Contractor's Name '46,4-:0n .`a Job Address ❑ Low Slope ❑ Asphaltic Shingles ROOF CATEGORY on 41-2- XMechanically Fastened Tile 0 Metal Panel/Shingles vv► 3/2 l Mortar/Adhesive Set Tile 0 Wood Shingles/Shakes ❑ Prescriptive BUR -RAS 150 ROOF TYPE New Roof 0 Reroofing 0 Recovering 0 Repair ❑ Maintenance ROOF SYSTEM INFORMATION Low Slope Roof Area (SF) Steep Sloped Roof Arva (SF) Total (SF) 0900 SECTION B (Roof Plan) Sketch Roof Plan_ Illustrate all levels and sections, rpof drains, scuppers, overflow scuppers and overflow drains. Include dimensions of sections and levels, clearly identify dimensions of elevated pressure zones anc location of parapets. MEM NUMMI MOM RIM RN • • 1 L --i-r- 1 1 -- __Lt E ir 4, 3/ - mil ■ I I Florida Building Code 2010 Edition High Velocity Hurricane Zone Uniform Permit AppFication Form Section D (Steen Stoned Roof System) Roof System Manufacturer: 61 J? g f q Notice of Acceptance Number: !1-041 ei` 65 Minimum Design Wind Pressures, If Applicable (From RAS 127 or Calculations): P1: " P2: lGd, � P 0 Maximum Design Pressure (From the NOA Specific System): Method of tile attachment: L -1°'D `1/1/ ,. s, ,do;, "I‘?/- Pr 71, is P011 Y/0 41i lbv on 3/ft. 44." 5 Roof Slope: 6-<' 12 04 S/12 -- Steen Z Steep Stoned Roof System Description Deck T f Type: Ridge ventilation? ype Underiayment nsulation: 1 1- X5 -1-m 3 / L4/Ad y c Fire Barrer: N(A astener Type & Speck g:i beim 14 ) • Thr✓ 6-A/.1^ 117.7�r,''D•G. (�%L4(5 2(4./3 /2 ilo/ 1164-64 dhesive Type ype Cap Sheet: A-40, �o . �n&rl4,,u.h I < Mean Roof Height: oof Ccvering: I y;1 X19 Type & Size Drip dge: I 26 G- oc e a4/v 2 " X3' I (v P 2'e Abi(rd Florida Building Code Edition 2010 High Velocity Hurricane Zone Uniform Perm t Application Form Section E (Tile Calculations) For Moment based tile systems, choose either Method 1 or '"�Gompare the values for Mr with the vat es from M. if the Mr values are gr er than or equal to the Mr values, for each area o • roof, then the tile a. cahment method is acceptable. (P1: (P2: (P3: xA xA xA Method 1 "Moment B ile Calculations Per RAS 127" = Mr1 Pr educt Approval Mf - Mg: = Mr2 ,uct Approval Mf — M9: = MProduct Approval Mf Method 2 "Simplified Tile Calculation Per Table Below" 2 Required Moment of Resistance (Mr) From Table Below ) r IC Product Approval Mf IA 2 a 4"/' 7 3i 3/r2 Mf Required Moment Resistanc )* Mean Roof Height --f- Roof Slope 4. 2:12 3:12 4:12 5:12 6:12 7:12 15' 34A 32. 30.4 28.4 26.4 24.4 20' 36.5 34.4 32.2 30.1 28.0 25.9 25' 38.2 36.0 33.8 31.6, i 29.4 27.1 30' 39.7 37.4 35.1 32.8 30.5 28.2 *Must be used in conjunction with a list of moment based tile systems endorsed by the Broward County Board of Rules and Appeals. 40' 42.2 39.8 37.3 34.9 32.4 30.0 For Uplift based tile systems use Method 3. Compare the values for F' with the values for Fr. If the F' values are greater than or equal to the Fr values, `or each area of the roof, then the tile attachment method is acceptable. Method 3 "Uplift Based Tile Calculations Pl;r RAS 127" (P1: x 1: = x w:= ) - W: x cos O: - = Fr1 Product Approval F' (P2: x 1: = x w:= ) - W: x cos 0: - = Fre Product Approval F' (P3: x 1: = w:= ) - W: x cos 0: - = Fra Product Approval F' Description Design Pressure Mean Roof Height 1 Roof Slope 1 Aerodynamic Multiplier 1 Restoring Moment due to Gravi 1 Attachment Resist ce Required Moment Resistance I Minimum Attachment Resistance Required Uplift Resistance Average Tile Weight 1 Tile Dimensions { Sym P1 or P2 MU M, M, F' Where to_Obtain Information oI Where to find P3\ RAS 127 Table 1 or by an engineering analysis prepared by PE based on ASCE 7 Qb Site Josue Produ Approval Product proval Product Appval Calculated Product Approval F, 1 Calculated W 1 Product Approval I =length Product Approval w = width All calculations must be submitted to the Building Official at the lime of permit application. MIAMI DADir VisMt ii j BUILDING AND NEIGHBORHOOD COMPLIANCE DEPARTMENT (BNC) BOARD AND CODE ADMINISTRATION DIVISION NOTICE OF ACCEPTANCE (NOA) Entegra Roof Tile, Inc. 1289 NE 9th Ave. Okeechobee, FL. 34972 MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 Miami, Florida 33175-2474 T (786) 315-2590 F (786) 315-2599 www.miant ade.2ov/buildinv/ SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed and accepted by Miani-Dade County BNC - Product Control Section to be used in Miami Dade County and other areas where allowa:d by the Authority Having Jurisdiction (AHJ). This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section (In Miami Dade County) and/or the AHJ (in areas other than lv:iami Dade County) reserve the right to have this product or material tested for quality assurance purposes. If tliis product or material fails to perform in the accepted manner, the manufacturer will incur the expense of such t.:sting and the AHJ may immediately revoke, modify, or suspend the use of such product or material within t:1eir jurisdiction. BNC reserves the right to revoke this acceptance, if it is determined by Miami -Dade County Product Control Section that this product or material fails to meet the requirements of the applicable building code. This product is approved as described herein, and has been designed to comply with the Florida Building Code including the High Velocity Hurricane Zone of the Florida Building Code. DESCRIPTION: Bella "High S" Tile LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein. RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building code negatively affecting the performance of this product. TERMINATION of this NOA will occur after the expiration date or i "there has been a revision or change in the materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by the words Mia mi -Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be provided to the uswr by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the 3uiiding Official. This renews NOA # 09-0512.15 and consists of pages 1 through 7. The submitted documentation was reviewed by Alex Tigera. MIAMI DADE COUNTY NOA No.: 11-0414.08 Expiration Date: 07/13/16 Approval Date: 06/02/11 Page 1 of 7 ROOFING ASSEMBLY APPROVAL Category: Sub-Cateeorv: Material: Deck Tyne: Roofing Roofing Tiles Concrete Wood 1. SCOPE This approves a roofing system using Entegra Bella "High S" concrete roof tile as manufactured in Okeechobee, FL and described in Section 2 of this Notice of Acceptance. For Locations where the pressure requirements, as determined by applicable Building Code does not exceed the design pressure values obtained by calculations in compliance with RAS 127 using the values listed in section 4 herein. The attachment calculations shall be done tv a moment based system. 2. PRODUCT DESCRIPTION Manufactured by Applicant Bella "High S" Trim Pieces Test Dimensions Specifications L= 16'/2" W=13-114" Thickness = V2" 1= varies w = varies varying thickness 2.1 MANUFACTURING LOCATION 2.1.1. Okeechobee, FL. 2.2 EVIDENCE SUBMITTED Test Agency IBA Consultants, Inc. Redland Technologies Redland Technologies Redland Technologies Redland Technologies MIAMI-DADE COUNTY MIWAGIVoi TAS 112 Product Descrintion High profile, interlocking, extruded concrete roof tile quipped with two nail holes. For mechanic A, mortar or adhesive set applications. TAS 112 Accessor;: trim, concrete roof pieces for use at hips, raker, ridges and valley terminations. Test Identifier 2421-94 7161-03 Appendix III Letter Dated Aug. 1, 1994 P09647-01 P0402 Test NamelReport A:TM C 1167 Static Uplift Testing TAS 102 & 102(A) Wind Tunnel Testing TAS 108 (Nail -On) Wind Tunnel Testing TAS 108 (Mortar Set) Withdrawal Resistance Testing o F screw vs. smooth s lank nails Date June 2006 Dec. 1991 Aug. 1994 Aug. 1994 Sept. 1993 NOA No.: 11-0414.08 Expiration Date: 07/13/16 Approval Date: 06/02/11 Page 2 of 7 The Center for Applied Engineering, Inc. The Center for Applied Engineering, Inc. The Center for Applied Engineering, Inc. The Center for Applied Engineering, Inc. The Center for Applied Engineering, Inc. The Center for Applied Engineering, Inc. The Center for Applied Engineering, Inc. Celotex Corporation Testing Services Celotex Corporation Testing Services Walker Engineering, Inc. Walker Engineering, Inc. 94-083 Sta is Uplift Testing TAS 101 (Adhesive Set) 94-084 Sta tie Uplift Testing TA:' 101 (Mortar Set) 25-7094-(3, 6 & 9) Sta tic Uplift Testing 25-7120-(1 & 2) 25-7183-(3 & 4) 25-7214-(3, 4, &7) 25-7804-4 520111-3 520191-2-1 Calculations Calculations TAS 102 Sta.ic Uplift Testing TAS 102 Sta.ic Uplift Testing TAS IO2 Static Uplift Testing TAS 102 Static Uplift Testing TAS 102 Static Uplift Testing TAS 101 Static Uplift Testing TAS 101 Aerocynamic Multiplier Re:;toring Moment April 1994 May 1994 Oct. 1994 Nov. 1994 Feb. 1995 March, 1995 Sep. 1996 Dec. 1998 March 1999 March 1999 June 2007 3. LIMITATIONS: 3.1 Fire classification is notpart of this acceptance. 3.2 For mortar or adhesive set tile applications, a static field uplift test in accordance with TAS 106 may required, refer to applicable building code. 3.3 Applicant shall retain the services of a Miami -Dade Count) Certified Laboratory to perform quarterly test in accordance with TAS 112, appendix 'A', Such testing shall be submitted to the Building and Neighborhood Compliance Department — Product Control Section for review. 3.4 Minimum underlayment shall be in compliance with the applicable Roofing Applications Standards listed section 4.1 herein. 3.5 30/90 hot mopped underlayment applications may be instat ed perpendicular to the roof slope unless stated otherwise by the underlayrnent material manor acturers published literature. 3.6 This acceptance is for wood deck applications. Minimum deck requirements shall be in compliance with applicable building code. MIAMI-DADE COUNTY APPROVED NOA No.: 11-0414.08 Expiration Date: 07/13/16 Approval Date: 06/02/11 Page 3 of 7 4. INSTALLATION 4.1 Entegra Sales, Inc.'s Bella "High S" concrete roof ti le and its components shall be installed in strict compliance with Roofing Application Standard RAS 118, RAS 119 and RAS 120. 4.2 Data For Attachment Calculations Tile Profile Bella "High S" Tile Table 1: Average Weight (W) and Dimensions (1 x w ) Welght-W (lbf) Longfh-I (ft) Width -w (ft) 10.5 1.375 1.08 Table 2: Aerodynamic Multip_ti_e_es - A (ft) Tile A (ft3) A (ft3) Profile Batten Application Direct Deck Application Bella "High S" Tile 0.349 0.378 Table 3: Restoring Moments due to Gravity - Ma (ft-Ibf) 'tile 2":12" I 3":12" 4":12" I 5":12" 6":12" Greater than Profile 7":12" Bella "High Battens DirectBattens Direct Battens Direct Battens l Direct Battens Direct Battens Direct S" Tile Deck I Deck I Deck I I Deck I Deck Deck 619 6.89 1 6.11 6.801 5.99 1 6.67 I 5.85 1 6.51 1 5.68 1 6.33 5.50 6.13 Table 4: Attachment Resistance Expressed as a Moment - M1 (ft-Ibf) for Nail -On Systems Tile Fastener Type Direct Deck Direct Deck Profile (min 15/32" plywood) (min. 19/32" plywood) Bella "High 2-10d Ring Shank Nails 28.6 41.2 S" Tile 1-10d Smooth or Screw 5.1 6.8 Shank Nail 2-10d Smooth or Screw 6.9 9.2 Shank Nails _ 1 #8 Screw 20.7 20.7 2 #5 Screw I 43.2 43.2 1-10d Smooth or Screw 23.1 23.1 Shank Nail (Field Clip) 1-10d Smooth or Screw 29.3 29.3 Shank Nail (Eave Clip) 2-10d Smooth or Screw 27,6 27.6 Shank Nails (Field Clip) 1 2-10d Smooth or Screw 38.1 38.1 Shank Nails (Eave Clip) I 1 12-10d Ring Shank Nails' 1 33.1 48.1 1. Installation with a 4" tile headcap and fasterners are located a nin. of 2%" from head of tile. Battens 19.4 2.8 7.3 18.1 29.8 19.0 24.0 38.6 41.8 50.9 MIAM !DARE COUNTY NOA No.: 11-0414.08 Expiration Date: 07/13/16 Approval Date: 06/02/11 Page 4of7 Table 5: Attachment Resistance Expressed its a Moment Mf (ft-Ibf) for Two Patty Adhesive Set S istems Tile I Tile Application Minimum Attachment Profile Resistance Bella "High S" Tile ( Adhesive 29.3` 1 See manufactures component approval for installation requirements. 2 Flexible Products Company TileBond Average weight per patty 10.7 trams. Polyfoam Product. Inc. Average weight per patty 8 drams. Table 6: Attachment Resistance Expressed as a.Moment - Mf (ft-Ibf) for Single Patty Adhesive Set E'ystems Tile Tile Application Minimum Attachment Profile Resistance Bella "High S' Tile Polyfoam PolyProTM 66.54 Polyfoam PolyProTM 38.74 3 Large patty placement of 63grams of POIVProTM. 14 Medium patty placement of 24nrams of PolyProTM. Table 7: Attachment Resistance Expressed a a Moment - Mf(ft-1bf) for Mortar Set Systems Tile Tile Attachment Profile Application Resistance Bella "High S" Tile Mortar Set5 24.5 Tile-Tite Roof Tile Mortar. MIAMMADE COUNTY APPROVED NOA No.: 11-0414.08 Expiration Date: 07/13/16 Approval Date: 06/02/11 Page 5 of 7 5. LABELING 5.1 All tiles shall bear the imprint or identifiable marki zg of the manufacturer's name or logo as seen in detail below, or following statement: Miami -Dade County Product Control Approved". OR C_) ENTE /a\ z, ENTEGRA SALES BELLA "HIGH S" CONCRETE TILE LABEL (LOCATED UNDERNEATH TILE) 6. BUILDING PERMIT REQUIREMENTS 6.1 Application for building permit shall be accompaniec f by copies of the following: 6.1.1 This Notice of Acceptance. 6.1.2 Any other documents required by the Building Official or applicable building code in order to properly evaluate the installation of this system. MIAMI DADE COUNTY Wi;nl'!1►1 NOA No.: 11-0414.08 Expiration Date: 07/13/16 Approval Date: 06/02/11 Page 6of7 PROFILE DRAWING. END OF THIS ACCEPTAT CE MIAMI'•DADE COUNTY uun ni�b�f�'y Ytll'4 �� NOA No.: 11-0414.08 Expiration Date: 07/13/16 Approval Date: 06/02/11 Page7of7 DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY AFFAIRS (I' ERA) BOARD AND CODE ADMINISTRATION DIVISION NOTICE OF ACCEPTANCE (NOA) 3M Company 3M Center Building 0220-05-E-06 St. Paul, MN. 55144-1000 MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 1 1805 SW 26 Street, Room 208 Miami, Florida 33175-2474 T (786) 315-2590 F (786) 315-2599 www .miamidadc.eov/cera SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed and accepted by Miami -Dade County PERA - Product Control Section to be used in Miami Dade County and other areas where allowed by the Autho: ity Having Jurisdiction (AHJ). This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section (In Miami Dade County) and/or the AHJ (in areas other than Mil mi Dade County) reserve the right to have this product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the manufacturer will incur the expense of such toasting and the AHJ may immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. PERA reserves the right to revoke this acceptance, if it is determined by Miami -Dade County Prodt ct Control Section that this product or material fails to meet the requirements of the applicable building code. This product is approved as described herein, and has been designed to comply with the Florida Building Code including the High Velocity Hurricane Zone of the Florida Building Code. DESCRIPTION: 3MTM 2 -Component Foam Roof Tile Adhesive AH -1611 LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein. RENEWAL of this NOA shall be considered after a renewal application ha; been tiled and there has been no change in the applicable building code negatively affecting the performance of this product. TERMINATION of this NOA will occur after the expiration date or if therW has been a revision or change in the materials, use, and/or manufacture of the product or process. Misuse of this T 1OA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of :he NOA is displayed, then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be provided to the user by he manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This renews and revises NOA# 11-0124.04 and consists of pages 1 through 7. The submitted documentation was reviewed by Alex Tigera. NOA No.: 12-0228.18 Expiration Date: 05/10/17 Approval Date: 05/10/12 Page 1 of 7 ROOFING COMPONENT APPROVAL: Category: Sub Category: Materials: Roofing Rooftile adhesive Polyurethane SCOPE: This approves 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 as manufactured by 3M Company as described in Section 2 of this Notice of Acceptance. For the locations when the design pressure requirements, as determined by applicable building code, does not exceed the design pressure values obtained by calculations in compliance with Roofing Application Standard RAS 127, for use with approved flat, low, and high profile roof tiles system using 2 -Component Foam Roof Tile Adhesive AH -160. Where the rttachment calculations are done as a moment based system for single patty placement, and as an uplift based system for double patty systems PRODUCTS MANUFACTURED BY APPLICANT: Product Dimensions Test Product Description Specifications 3MTM 2 -Component Foam N/A TAS 101 Two component polyurethane foam adhesive Roof Tile Adhesive AH - 160 Foam Dispenser RTF 1000 ProPack® 30 & 100 N/A Dispensing Equipment N/A Dispensing Equipment PRODUCTS MANUFACTURED BY OTHERS: Any Miami -Dade County Product Control Accepted Roof Tile Assembly hewing a current NOA which list moment resistance values with the use of 2 -Component Foam Roof Tile Adhesive A -1-160 roof tile adhesive. MANUFACTURING LOCATION: 1. Tomball, TX. PHYSICAL PROPERTIES: Property Density Compressive Strength Tensile Strength Water Absorption Moisture Vapor Transmission Dimensional Stability Closed Cell Content Test ASTM D 1622 ASTM D 1621 ASTM D 1623 ASTM D 2127 ASTM E 96 ASTM D 2126 ASTM D 2856 Results 1.6 lbs./ft.3 18 PSI Parallel to rise 12 PSI Pertendicular to rise 28 PSI Par illel to rise 0.08 Lbs./Ft2 3.1 Perm /nch +0.07% Volume Change @ -40° F., 2 weeks +6.0% Volume Change @158°F., 100% Humidity, 2 weeks 86% NOA No.: 12-0228.18 Expiration Date: 05/10/17 Approval Date: 05/10/12 Page 2 of 7 Note: The physical properties listed above are presented as typi ;a1 average values as determined by accepted ASTM test methods and are subject to normal manufacturing variation. EVIDENCE SUBMITTED: Test Aeenev Center for Applied Engineering Miles Laboratories Polymers Division Ramtech Laboratories, Inc. Southwest Research Institute Trinity Engineering Celotex Corp. Testing Services Test Identifier #94-060 257818-1 PA 25-7438-3 25-7438-4 25-7438-7 25-7492 NB -589-631 9637-92 01-6743-011 01-6739-062b[1] 7050.02.96-1 528454-2-1 528454-9-1 528454-10-1 520109-1 520109-2 520109-3 520109-6 520109-7 520191-1 520109-2-1 Test Name/Reuort TAS 101 TAS 101 SSTD 11-93 &STD 11-93 S:STD 11-93 ASTM D 1623 ASTM E 108 ASTM E 108 ASTM E 84 TAS 114 TAS 101 TAS 101 Date 04/08/94 12/16/96 10/25/95 11/02/95 12/12/95 02/01/94 04/30/93 11/16/94 01/16/95 03/14/96 10/23/98 12/28/98 TAS 101 03/02/99 LIMITATIONS: 1. Fire classification is not part of this acceptance. Refer to the Prepared lhoof Tile Assembly for fire rating. 2. 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 shall solely be used with flat, low, & high tile profiles. 3. Minimum underlayment shall be in compliance with the Roofing Appl cation Standard RAS 120. 4. Roof Tile manufactures acquiring acceptance for the use of 3MTM 2 -Component Foam Roof Tile Adhesive AH - 160 roof tile adhesive with their tile assemblies shall test in accordance with TAS 101. 5. Roof Tile manufactures acquiring acceptance for the use of HANDL-STICK roof file adhesive with their tile assemblies shall test in accordance with TAS 101 with section 10.4 as modified herein. F'= F 2 MS NOA No.: 12-0228.18 Expiration Date: 05/10/17 Approval Date: 05/10/12 Page 3 of 7 INSTALLATION: 1. 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 may be used with any rooftile assembly having a current NOA that lists uplift resistance values with the use of 3MTM 2 -Component Foam Roof Tile Adhesive AH -160. 2. 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 shall be applii:d in compliance with the Component Application section and the corresponding Placement Details noted herein. The rooftile assembly's adhesive attachment with the use of 3MTM 2 -Component Foam Roof Tile Adhe;ive AH -160 shall provide sufficient attachment resistance, expressed as an uplift based system, to meet or exceed the uplift resistance determined in compliance with Miami -Dade County Roofing Application Standards RAS 127. The adhesive attachment data is noted in the roof tile assembly NOA. 3. 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 and its components shall be installed in accordance with Roofing Application Standard RAS 120, and 3M Company's 3MTM 2 -Component Foam Roof Tile Adhesive AH - 160 Operating Instruction and Maintenance Booklet. 4. Installation must be by a Factory Trained 'Qualified Applicator' appro'fed and licensed by 3M Company. 3M Company shall supply a list of approved applicators to the authority having jurisdiction. 5. Calibration of the Foam Dispenser RTF1000 dispensing equipment is required before application of any adhesive. The mix ratio between the "A" component and the "B" component shad! be maintained between 1.0-1.15 (A): 1.0 (B). The dispense timer shall be set to deliver 0.0175 to 0.15 pounds per tile as determined at calibration. No other settings shall be approved. 6. 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 shall be applied with Foam Dispenser RTF1000 or ProPack® 30 & 100 dispensing equipment only. 7. 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 shall not be eyposed permanently to sunlight. 8. Tiles must be adhered in freshly applied adhesive. Tile must be set within 2 to 3 minutes after 3MTM 2 - Component Foam Roof Tile Adhesive AH -160 has been dispensed. 9. 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 placement anc minimum patty weight shall be in accordance with the Placement Details' herein. Each generic tile profile requires the specific placement noted herein. Table 1: Adhesive Placement For Each Generic Tile Profile Tile Profile Flat, Low, High Profiles High Profile (2 Piece Barrel) Flat, Low, High Profiles Flat, Low, High Profiles Placement Detail Single Paddy Weight Min. (grams) 35 17/side on cap and 34/pan 24 Two Paddy Weight per paddy Min. (grams) N/A N/A N/A 8 NOA No.: 12-0228.18 Expiration Date: 05/10/17 Approval Date: 05/10/12 Page 4 of 7 LABELING: All 3MT 12 -Component Foam Roof Tile Adhesive AH -160 containers sha: l comply with the Standard Conditions listed herein. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or applicable building code in order to properly evaluate the installation of this system. ADHESIVE PLACEMENT DETAIL 1 SINGLE PATTY NaH through plastic cement Paddy (Beneath Tile) Nail through plastic cement NN41,} 41%* • j Faye Cours 'Nt. Fascia Weephde Eave closure Dnp edge Underlayment Underlayment 0 Eave Course Eave Closure Nail through plastic cement Underlayment Fascia Eave course only: Keep adhesive approx. 4 in. up from weepholes Paddy (Beneath Tile) 10 in. Eave Course 101n. Paddy (Beneath Tile) Eave course only: Keep adhesive approx. 4 in. up from weepholes 1) Place enough adhesive to acdieve 17 to 23 Ophonal 2x4's for square inches in contact with he pan the steep pitch applications 2) Turn covers upside down. Pla :e adhesive 1l2 in. To 1 in. From outside edge of cover tile. Then install the tile. Underlayment i Nati through plastic cement Eave course only: Keep adhesive approx. 41n. up from weepholes Fascia Eave Closure Remov top portion of the eave course cover tile. Abut to second course of pan files. Ensure eave end o pan and cover tiles are flush at eave line. Eave closure (mortar shown) Weephole Fascia Boa Sheathing Optional Point -up Mortar on longitudinal edges of the NOA No.: 12-0228.18 Expiration Date: 05/10/17 Approval Date: 05/10/12 Page 5 of 7 Nail through plastic cement ADHESIVE PLACEMENT DETAIL 2 SINGLE PATTY Paddy (Beneath He) Nail through plastic cone 4411° .,•••••r. Underlayment fln' Paddy (Beneath Tde) N. 2 in. Fascia Eve Closure Nail through plastic cement Underlayment Eave 0 urse 2111111°":"-IIIP Paddy (Beneath He) 7 In. Eave Course MIAMI-DADE COUNTY ptiVasrilij Fascia Eave Closure Fascia Weephole Eave closure Drip edge NOA No.: 12-0228.18 Expiration Date: 05/10/17 Approval Date: 05/10/12 Page 6 of 7 Nail through plastic cement ADHESIVE PLACEMENT DETAIL 3 DOUBLE PATTY Paddy (between tile) Paddy (under tile) CLAN - in. x3in. Single paddy on under. layment Single paddy under tile Single paddy on top of tile Eave course 2 In. X 7 in. medium size paddy eave Fascia course only Nail through plastic cement Nail through plastic cer lent Underlayment Single paddy under tile Single paddy between tile 2 in. x 7 in. medium size paddy eave course only } 3 in. x 3 in. Single 4 in. paddy on under- layment Single paddy on top of tile Eave Course Single paddy under tile Single paddy between tile Jrin. x 3 in. Single /paddy on underlayment Single paddy on top of tile Eave Course Eave Closure 2 in. x 7 n. medium size pad iy eave course only Fascia END OF THIS ACCEPTANCE Fascia Weephole Eave closure Drip edge NOA No.: 12-0228.18 Expiration Date: 05/10/17 Approval Date: 05/10/12 Page 7 of 7 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) BOARD AND CODE ADMINISTRATION DIVISION NOTICE OF ACCEPTANCE (NOA) O'Hagin Manufacturing, LLC 210 Classic Court, Suite #100 Rohnert Park, CA 94928 MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 Miami, Florida 33175-2474 T (786) 315-2590 F (786) 315-2599 ww w.miamidadr.gov9aoaomv SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed and accepted by Miami -Dade County RER - Product Control Section to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ). This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this product or material tested for quality assurance purposes. If this product or material Lils to perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. RER reserves the right t ) revoke this acceptance, if it is determined by Miami -Dade County Product Control Section that this product or material fails to meet the requirements of the applicable building code. This product is approved as described herein, and has been designed to comp: y with the Florida Building Code including the High Velocity Hurricane Zone of the Florida Building Code. DESCRIPTION: O'Hagin's Cloaked Vent Tile LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein. RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building code negatively affecting the performance of this product. TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NO k. Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by the words Miami -D rde County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This renew NOM09-0316.04 and consists of pages 1 through 9. The submitted documentation was reviewed by Alex Tigera. MIAMI-DADE COUNTY %112:01144 NOA No.: 13-0122.07 Expiration Date: 04/04/18 Approval Date: 04/11/13 Page of 9 ROOFING COMPONENT APPROVAL Category: Sub -Category: Material: Minimum Slope: Roofing Ventilation 26ga. Steel; 0.032" Aluminum; 16 oz. Copper 2:12 TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT Product O'Hagin's Cloaked Vent Tile S -Profile O'Hagin's Cloaked Vent Tile M -Profile O'Hagin's Cloaked Vent Tile Flat -Profile Primary Vent - Standard Flange Primary Vent - Diverter Flange Dimensions 29" x 19" x 2" 26-1/4" x 19" x 2" 26" x 19-1/2" x 4" 24" x 11" x '/2" 24" x 11" x'/2" MANUFACTURING LOCATION 1. Rohnert Park, CA 2. Lakeland, FL EVIDENCE SUBMITTED Test Agency/Identifier PRI Construction Materials Technologies Center For Applied Engineering, Inc. MIAMI•DADE COUNTY vuulttelgq Test Product Specification Description TAS 100 Metal roof vent for tile roofs TAS 100 Metal roof vent for tile roofs TAS 100 Metal roof vent for tile roofs TAS 100 Primary metal vent flashing for Flat, M, and S Profile vents TAS 100 Primary metal vent flashing with a diverter for Flat, M, and S Profile vents Name TAS 100(A) TAS 100(A) TAS 100(A) PA 100A Report Date CHI -025-02-01 01/10/08 CHI -014-02-02 12/08/07 CHI -026-02-01 01/10/08 M i S No. 257732b 07/30/96 NOA No.: 13-0122.07 Expiration Date: 04/04/18 Approval Date: 04/11/13 Page 2 of 9 APPROVED APPLICATIONS: Trade Name: O'Hagin's Cloaked Vent Tile System Type A: Mechanical attachment of vent under tile. Slot: Mark a 19" x 7" opening centered between layout I [nes and aligned approximately as shown on exposure lines as seen in Detail A. Set blade to thickness of sheathing and cut opening. Brush away sawdust and debris. Installation: Ventilation Calculations: Set primary vent (with or without diverter) in a 1/8 ' (2.54cm) bed of asphalt roofing cement. Secure primary vent to the roof deck with 1-1/4" x 3/8" (3.16 x .953cm) galvanized ring shank roofing nails spaced 4" (10.16cm) o.c. Seal nails with an approved ASTM D 4586 roofing cement, sealing primary vent flange with a layer of Perma glass mesh buttered into the roof cement around the flange. The tile vent can now be centered over the primary vent and nailed at the head with 2 ea. 1- 1/4" x 3/8" (3.16 x .953cm) galvanized ring shank roofing nails. See Detail A. See manufacturer's published literature for net free area LIMITATIONS: 1. Refer to applicable Building Code required ventilation. 2. The installation shall be applied in compliance with the manufacturer's current published application instruction and the requirements set forth in applicable building code. 3. Wind Clip hooks shall be fully engaged under head of preceding tiles. 4. O'Hagin's Cloaked vent tile may be installed on roofs up to roof mean heights of 40 ft. 5. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and Rule 9N-3 of the Florida Administrative Code. MIAMI•DADE COUNTY APPROVED NOA No.: 13-0122.07 Expiration Date: 04/04/18 Approval Date: 04/11/13 Page 3 of 9 DETAIL A PRIMARY VENT (WITH OR WITHOUT DIVERTER FLANGE) INSTALLATION 1.Mark and cut a 19" x 7" hole in the roof deck Centered between layout lines and aligned Approximately as shown on the exposure lines. (Set blade to the thickness of the sheathing) 2. Seal using $. ufficient amount of locally approved sealant around outer flange of Primary vent. 3. Attach at 4 -inch centers using approved roofing 4. Flash using locally approved peel and Nails of sufficient length to penetrate the stick. Sheathing. MIAMI•DADE COUNTY APPROVED NOA No.: 13-0122.07 Expiration Date: 04/04/18 Approval Date: 04/11/13 Page 4 of 9 S -TILE VENT INSTALLATION :111,11111111 1111ilii 1. Install secondary vent cover, bending the 2. Secure with : pproved roofing nails of Wind clip tightly under the preceeding course sufficient le gth to penetrate the Of tile, adjusting for head lap. Sheathing. M -TILE VENT INSTALLATION 1. Tile is inserted between perforated top of secondary vent cover . nd bottom flanged with water channel. Bend the wind clip tightly under the preceding course of tile, asjusting for head lap. The secondary vent cover takes the place of two field tiles. MIAMI•DADE COUNTY APPROVED NOA No.: 13-0122.07 Expiration Date: 04/04/18 Approval Date: 04/11/13 Page 5 of 9 FLAT -TILE VENT INSTALLATION 1. Tile is inserted between louvered top of secondary vent cover • nd bottom flanged with water channel. Bend the wind clip tightly under the preceding course of tile, asjusting for head lap. Remove 2 to 3 inches of the tile batten lug on either side of the secondary vent cover for proper fit. For tiles with continuous lugs, a portion of the lug may be rem weed as needed for wind clip installation. The secondary vent cover takes the place of two fielc tiles. MIAMI•DADE COUNTY [X IiItelliq NOA No.: 13-0122.07 Expiration Date: 04/04/18 Approval Date: 04/11/13 Page 6 of 9 goo ogg. 0 0 ogo 00 000 ogo 8g3 gog gig 000 go • i ° DETAIL "B" M -PROFILE - 261/4 TOP FRONT 1 2' — 4 1/2" 1 - 4 t/2 BAC}( =8= 5/4- - 28 3/4" TOP BOTTOM S -PROFILE 19 1/2 — 21 s/2" FRONT MIAMI.DADE COUNTY APPROVED 3 vr -4 1/2- LEFT 3 1/2" - 4 1/2" RIGHT 1/2 NOA No.: 13-0122.07 Expiration Date: 04/04/18 Approval Date: 04/11/13 Page 7 of 9 If• MIAMI-DADE COUNTY APPROVED t9' — 32' TOP FRONT BACK FLAT -PROFILE 29i — 32" BOTTOM 17 1/2" - SS" id VI" — 2" NOA No.: 13-0122.07 Expiration Date: 04/04/18 Approval Date: 04/11/13 Page 8 of 9 STANDARD FLANGE 24 - TOP r BOTTOM FRONT BACK LEFT RIGHT MIAMI•DADE COUNTY vulttu 44 PRIMARY VENT DETAIL 11' 3/r DNERTER FLANGE 1/2' - 314" t. • BOTTOM FRONT LEFT RIGHT END OF THIS ACCEPTANCE 6' NOA No.: 13-0122.07 Expiration Date: 04/04/18 Approval Date: 04/11/13 Page 9 of 9