HomeMy WebLinkAboutBLDG1403-0111-EngineeringBroward County Board of Rules and Appeals
One North University Drive, 3500-B
Fort Lauderdale, Florida 33324
Effective: March 15, 2012
Telephone: 954.765.4500
Facsimile: 954.765.4504
FORM FOR "SPECIAL BUILDING INSPECTOR"
SECTION 1 10.10 — BROWARD COUNTY ADMINISTRATIVE CODE
AND THE 2010 FLORIDA BUILDING CODE
NOTICE TO PROPERTY OWNER:
You are hereby directed in accordance with Section 110.10.1 of the Broward County Administrative Code and the Florida Building
Code to retain a Special Structural Inspector (A Florida Registered Architect or Licensed Engineer) to perform the
following mandatory or discretionary inspections, as outlined in Sections 110.10, 1822, 2122.2.4, 2218.2, R4407.5.4, 2223.1 1.1,
1927.12.1, 1927.12.2, R4405.9.12.1, R4405.9.12.2, R4408.5.2 & R4408.10.1 1 of the Florida Building Code and submit progress reports,
inspections reports, and a Certificate of Compliance to the Building Official as per Sections 110.10.6 and 110.10.7 of the Florida Building
Code.
Note: The Building Official determines which discretionary inspections are to be delegated.
/
DATE: J / ) /1 4 IDENTIFICATION, CONTROL OR BUILDING PERMIT #
PROJECT NAME: �HHeron Bav North — Osprey Lakes Plat 3 — Lot
U a )
JOB ADDRESS o n
) 1 r4 �,cbtsi W Cl-c,l lr ('k_ C1nc1 ZIP 33076
LEGAL DESCRIPTION:
FOLIO #
A. MANDATORY INSPECTIONS TYPE BY CODE:
I) Precast Concrete Units — Section 1927.12.1, R4405.9.12.1, 110.10.2.1 Yes 0 No ro
2) Precast Concrete Units — Section 1927.122, R4405.9.12.2, 1 10.10.2.1 Yes 0 No
3) Reinforced Unit Masonry — Section 2122.2.4, R4407.5.4, 110.10.2.2 (per ACI 530.1 -05 -Level B Quality Assurance)*
*unless noted otherwise on plan Yes ❑ No
4) Connections — Section 2218.2, 1 10.10.2.3 Yes ❑No
5) Metal System Buildings— Section 2223.1 1.1, 110.10.2.4, R4408.I0.1 1 Yes 0 No ED
B. DISCRETIONARY INSPECTION TYPE BY BUILDING OFFICIAL:
I) Building Structures or part thereof of Unusual Size, Height, Design or Method of Construction and
Critical Structural Connections — Section 110.10.1.1 Yes ❑ No
2) Windows, Glass Doors and Curtain Walls on buildings over two (2) stories — Section 110.10.1.1 Yes ❑ No
3) Pile Driving Only — Sections 1822, R4404.13, 1 10.10.1.1 Yes ❑ No
4) Precast Concrete Units — Section 1822, R4405.9.12, 110.10.2.1 Yes 0 No
5) Reinforced Unit masonry — Sections 2122.2.4, R4407.5.4, 110.10.2.2 Yes ® No 0
6) Other
Yes ❑ No
C. MANDATORY DOCUMENTATION
1) Inspection schedule stating the specific inspection that will be made and at what phase of construction must be submitted with this application.
2) Progress Repordlnspection reports during construction in accordance with Section 110.10.6.
3) Certificate of Compliance must be submitted prior to the scheduling of the final building inspection, Section 110.10.7.
ACKNOWLEDGMENT
/^( ,...1.6,6v,Owner's Signature: 1--L_'..._-" Permit Holder's Signature:
Printed Name: Paul Erhardt Printed Name: Steven T. lolly
License # (if applicable) CrerC011M5
SPECIAL BUILDING INSPECTOR:
❑ Registered Architect and/or ® Licensed Engineer Signatur of Special Buildinnspector, Embossed Seal AND Date
State of Florida Registration #
Printed Name of Special Building Inspector D. Mar eBlanc
Address of Special Building Inspector SW 30th Ave. Suite 20. Boynton Beach. FL 33426
35683 Fax # (561) 752-5542
Building Official (or designated representative)
Telephone # (56 I) 752-5440
Date:
***BE ADVISED THIS DOES NOT PRECLUDE YOU FROM OTHER MANDATORY INSPECTIONS IN THE CODE***
G:\SHARED\Forms\2010 FBC Special Bldg Insp Form.doc
March 3, 2014
SPECIALTY ENGINEERING CONSULTANTS, Inc.
Dade • Broward • Palm Beach
LETTER OF INTENT FOR SPECIAL INSPECTOR FOR TRUSS ERECTION
City of Parkland
Building Department
6600 University Drive
Parkland, FL 33067
Re: PROJECT: Heron Bay North — Osprey Lakes Plat 3 — Lot 5J
8054 NW 115 Way, Parkland, FL 33076
Building Department:
Pease be advised that we, Specialty Engineering Consultants; Inc, have been retained by WCI Communities,
LLC to supervise the erection of trusses with bottom chord in excess of 35' or height greater than 6' in accordance
with Section 2319.17.2.4 of the Florida Building Code for the referenced project.
This letter of intent is to be followed up by an Inspection Certification for truss erection which attests to the above.
Respectfully submitted,
Specialty • eering Consultants, Inc.
D. Mai' LeBlanc, PE
Partner
State of Florida:
Registered Professional Engineer: #0035683
Registered Special Inspector: #1177
1599 S.W. 30th Avenue, Suite #20 • Boynton Beach, FL 33426 • Office: 561-752-5440 • Fax: 561-752-5542
SPECIALTY ENGINEERING CONSULTANTS, Inc.
Dade • Broward • Palm Beach
STATEMENT OF INTENT AND SCOPE OF WORK FOR ENGINEERED UNIT MASONRY
March 3, 2014
City of Parkland
Building Department
6600 University Drive
Parkland, FL 33067
Re: PROJECT: Heron Bay North — Osprey Lakes Plat 3 — Lot 5J
8054 NW 115 Way, Parkland, FL 33076
Building Department:
We, Specialty Engineering Consultants; Inc, shall personally inspect the entire "Engineered Unit Masonry" system
fer this building, including but not limited to the following:
1. Masonry units, mortar, grout and reinforcing steel met specifications.
2. Dowels properly placed with adequate spacing.
3. Steel column ties in columns, pilasters and beam elevation transitions properly placed, tapped and
tied.
4. 'Masonry field work: head and bed joints, horizontal joint reinforcing installed correctly, cells free of
excessive mortar fins, walls level and plumb tolerances.
5. Monitor grout placement, verify grout slump, proper consolidation of grout and proper low or high
lift grouting procedures were followed.
6. Correct embedment of reinforcing steel, bolts, ties, etc.
7. Compliance with ACI 530-08/ASCE 5-08 and commentaries, approved plans and 2010 FBC.
This letter of intent is to be followed up by an Inspection Certification for Unit Masonry which attests to the above.
Respectfully submitted,
Specialt •- neering Consultants, Inc.
D. Mar
Partner
eBlanc, PE
State of Florida:
Registered Professional Engineer: #0035683
Registered Special Inspector: #1177
1599 S.W. 30th Avenue, Suite #20 • Boynton Beach, FL 33426 • Office: 561-752-5440 • Fax: 561-752-5542
GALE INSULATION
SIO # 401797170
CERTIFICATE OF INSULATION — INSTALLATION BUILDING PERMIT # WL k { ) V
JOB ADDRESS: 8054 NW 115 WAY PARKLAND, FL
LOT 1005 OSPREY LAKE
STATEMENT OF COMPLIANCE: We, the undersigned, hereby certify that the thermal insulation has
been installed in the referenced building in compliance with the Florida Model Energy Efficiency Building
Code and the approved plans and specifications, and in accordance with good construction practice. The
insulation furnished is of the type, thickness and R -value as set forth below:
AREA
TYPE THICKNESS R -VALUE MANUFACTURER
CEILING AREA FIBERGLASS 12.75" / 12" R-38 OWENS CORNING
FLAT / NOT BLOW / BATT
ACCESSIBLE
GARAGE FIBERGLASS 3.5" R-11 OWENS CORNING
COMMON WALL BATT
INTERIOR FIBERGLASS 3.5" R-11 OWENS CORNING
PARTITIONS BATT
EXTERIOR REFLECTIVE .75" R-4.1 FI -FOIL COMPANY
MASONRY FOIL
WALLS
MULTIFAMILY RESIDENTIAL CONSTRUC'T'ION: The COMMON (PARTY) walls separating different tenants shall be
insulated as follows: Frame/Metal Stud Walls R-11 (min); CBS or Concrete Walls R-3 (min) by Energy Code requirements. See
FBC-2001 CHAPTR 13 -ENERGY EFFICIENCY, latest edition. These "minimum levels of insulation" are not included in the
Energy Calculations. but shall be installed in the field.
INSULATION CGC1512179
INSULATION CONTRACTOR'S SIGNATURE:
BUILDER: WCI COMMUNITIES: SIGNATURE:
I PERSONALLY KNOW THE AFFIANT, PAMELA FENTON.
Sworn to and subscribed before me this / q ray of
Notary Public, State of Florida
TIFICATION DATE: SEPTEMBER 19, 2014
C1
JENNIFER SWEET
Notary Public - Mate of Honda
My Comm Expires Jin 29, 2017
Comm,ss•ns EE 869683
, 2014
July 29, 2014
SPECIALTY ENGINEERING CONSULTANTS, Inc.
Dade • Broward • Palm Beach
CERTIFICATE OF COMPLIANCE FOR TRUSS ENGINEERING
City of Parkland Building Department
6600 University Drive
Parkland, FL 33067
Re: PROJECT: Heron Bay North — Osprey Lakes Plat 3 — Lot 5J
8054 NW 115 Way, Parkland, FL
Permit #: 1403-0111
Building Department:
We have personally inspected the truss system on the above referenced property and find the trusses are erected
properly and without any apparent damage. We have checked all aspects of this truss system — roof trusses and
floor trusses, where used — including, but not limited to the following components.
1. Proper size, grade and species of lumber used in the assembly of each truss per engineering.
2. Nail -on position or press -on plates checked for proper size and position per engineering.
3. Trusses and girders checked for proper anchorage for both gravity loads and uplift Toads.
4. Lateral bracing applied to truss members per engineering and building code.
5. All other bracing to resist lateral forces, in addition to that specified by truss engineering, has been
applied as required by the Architect -of -Record's approved plans. This includes the addition of shear walls, let -in
wall bracing, floor system bracing, proper positioning of sheathing, etc.
We have also inspected any repaired and/or modified trusses and have ascertained that they have been
corrected in accordance with: "Sealed" repair engineering supplied by the truss engineer. All engineering
sheets for repaired and/or modified trusses are included herewith.
Respectively submitted,
SPECIA ' ENGINEERING CONSAMTS, INC.
35683
. Mar
resi.
nt
eBlanc, PE
MATE OF
State of Florida:
Registered Professional Engineer:° A8356; 33
Registered Special Inspector: #1.1`l'!
1599 S.W. 30th Avenue, Suite #20 • Boynton Beach, FL 33426 • Office: 561-752-5440 • Fax: 561-752-5542
July 29, 2014
SPECIALTY ENGINEERING CONSULTANTS, Inc.
Dade • Broward • Palm Beach
CERTIFICATE OF COMPLIANCE FOR TRUSS ERECTION
City of Parkland Building Department
6600 University Drive
Parkland, FL 33067
Re: PROJECT: Heron Bay North — Osprey Lakes Plat 3 — Lot 5J
8054 NW 115 Way, Parkland, FL
Permit #: 1403-0111
Building Department:
Please be advised that we, Specialty Engineering Consultants; Inc, monitored the erection of trusses with bottom
chord in excess of 35' or height greater than 6' in accordance with Section 2319.17.2.4 of the Florida Building
Code for the referenced project.
We find that all aspects of this system conform to the approved plans and the Florida Building Code.
Respectfully submitted,
Specialt. • ineering Consul
. Mar LeBlanc, PE
President OF
,.ATE
�OP'r
State of Florida:
Registered Professional Engineer: #0035683
Registered Special Inspector: #1177
1599 S.W. 30th Avenue, Suite #20 • Boynton Beach, FL 33426 • Office: 561-752-5440 • Fax: 561-752-5542
July 29, 2014
SPECIALTY ENGINEERING CONSULTANTS, Inc.
Dade • Broward • Palm Beach
CERTIFICATE OF COMPLIANCE FOR UNIT MASONRY
City of Parkland Building Department
6600 University Drive
Parkland, FL 33067
Re: PROJECT: Heron Bay North — Osprey Lakes Plat 3 — Lot 5J
8054 NW 115 Way, Parkland, FL
Permit #: 1403-0111
Building Department:
We have personally inspected the complete "engineered unit masonry" system for this building.
includes all of its components such as; steel placement; horizontal joint reinforcement; vertical
reinforcing steel for the concrete masonry units and all associated tie beams, tie columns, etc.
have monitored and verified grout placement.
We find that all aspects of this system conform to the approved plans and the Florida Building
2122.4 and BCAC 105.10.2.2.
Respectively submitted,
SPECIALTY ENGINEER'
LeBlanc, PE
President
-,TATE OF
State of Florida:O "•••
•'.
Registered Professional Engirieers •:''35683
Registered Special Inspector: #1177
CQNU..TANTS, INC.
o 35683
This inspection
and horizontal
In addition, we
Code, sections
1599 S.W. 30th Avenue, Suite #20 • Boynton Beach, FL 33426 • Office: 561-752-5440 • Fax: 561-752-5542
July 29, 2014
SPECIALTY ENGINEERING CONSULTANTS, Inc.
Dade • Broward • Palm Beach
CERTIFICATE OF COMPLIANCE FOR TRUSS ENGINEERING
City of Parkland Building Department
6600 University Drive
Parkland, FL 33067
Re: PROJECT: Heron Bay North — Osprey Lakes Plat 3 — Lot 5J
8054 NW 115 Way, Parkland, FL
Permit #: 1403-0111
Building Department:
We have personally inspected the truss system on the above referenced property and find the trusses are erected
properly and without any apparent damage. We have checked all aspects of this truss system — roof trusses and
floor trusses, where used — including, but not limited to the following components.
1. Proper size, grade and species of lumber used in the assembly of each truss per engineering.
2. Nail -on position or press -on plates checked for proper size and position per engineering.
3. Trusses and girders checked for proper anchorage for both gravity loads and uplift loads.
4. Lateral bracing applied to truss members per engineering and building code.
5. All other bracing to resist lateral forces, in addition to that specified by truss engineering, has been
applied as required by the Architect -of -Record's approved plans. This includes the addition of shear walls, let -in
wall bracing, floor system bracing, proper positioning of sheathing, etc.
We have also inspected any repaired and/or modified trusses and have ascertained that they have been
corrected in accordance with: "Sealed" repair engineering supplied by the truss engineer. All engineering
sheets for repaired and/or modified trusses are included herewith.
Respectively submitted,
SPECIAL P NGINEERI
Mar eBlanc, PE
resident
e
NSULTANTS, INC.
,o 35663
State of Florida: �T � OF
Registered Profession I.Engirtegr \_ 683
Registered Special Inspector:..... 77
1599 S.W. 30th Avenue, Suite #20 • Boynton Beach, FL 33426 • Office: 561-752-5440 • Fax: 561-752-5542
July 29, 2014
SPECIALTY ENGINEERING CONSULTANTS, Inc.
Dade • Broward • Palm Beach
CERTIFICATE OF COMPLIANCE FOR TRUSS ERECTION
City of Parkland Building Department
6600 University Drive
Parkland, FL 33067
Re: PROJECT: Heron Bay North — Osprey Lakes Plat 3 — Lot 5J
8054 NW 115 Way, Parkland, FL
Permit #: 1403-0111
Building Department:
Please be advised that we, Specialty Engineering Consultants; Inc, monitored the erection of trusses with bottom
chord in excess of 35' or height greater than 6' in accordance with Section 2319.17.2.4 of the Florida Building
Code for the referenced project.
We find that all aspects of this system conform to the approved plans and the Florida Building Code.
Respectfully submitted,
Specialt - • ineering,Conguitgisa
10 35633
. Mar eBlanc, PE
President
State of Florida:(o
Registered Professional Engirieer,''.1#t35683
Registered Special Inspector; #1177
1599 S.W. 30th Avenue, Suite #20 • Boynton Beach, FL 33426 • Office: 561-752-5440 • Fax: 561-752-5542
July 29, 2014
SPECIALTY ENGINEERING CONSULTANTS, Inc.
Dade • Broward • Palm Beach
CERTIFICATE OF COMPLIANCE FOR UNIT MASONRY
City of Parkland Building Department
6600 University Drive
Parkland, FL 33067
Re: PROJECT: Heron Bay North — Osprey Lakes Plat 3 — Lot 5J
8054 NW 115 Way, Parkland, FL
Permit #: 1403-0111
Building Department:
We have personally inspected the complete "engineered unit masonry" system for this building.
includes all of its components such as; steel placement; horizontal joint reinforcement; vertical
reinforcing steel for the concrete masonry units and all associated tie beams, tie columns, etc.
have monitored and verified grout placement.
We find that all aspects of this system conform to the approved plans and the Florida Building
2122.4 and BCAC 105.10.2.2.
Respectively submitted,
SPECT. ' ENGINEERING CRISULTANTS, INC.
A:'
D. M LeBlanc, PE
Pr- . ident
State of Florida: \�
Registered Professional Engineer.. '.#VO35683
Registered Special Inspector: #1177
This inspection
and horizontal
In addition, we
Code, sections
1599 S.W. 30th Avenue, Suite #20 • Boynton Beach, FL 33426 • Office: 561-752-5440 • Fax: 561-752-5542
NEE4�
I izG
SPECIALTY ENGINEERING CONSULTANTS, Inc.
THRESHOLD/SPECIAL INSP CTION REPORT
PROJECT:
CLIENT:
CONTRACTOR:
INSPECTION TYPE:
PROJECT LOCATION:
et, if
DAY:
DATE:
PERMIT No.
TRACKING #:
PERFORMED BY:
Dade • Broward • Palm Beach
,
7/ Spy
MEMBERS / AREAS INSPECTED:
(
11)1'. -
DISPOSITION
/ RESULTS:
GENERAL NOTES:
Respectfully submitted, DISTRIBUTION COPY:
Speciality Engineering Consultants, Inc.
D. Mark LeBlanc, PE
Partner
State of Florida:
Registered Professional Engineer: #0035683
Registered Special Inspector: #1177
Form001 ThresholdSpec,allnspec GG 01,04
1599 S.W. 30th Avenue, Suite #20 • Boynton Beach, FL 33426 • Office: 561-752-5441) • Fax of -75-)-554-'
SPECIALTY ENGINEERING CONSULTANTS, Inc.
THRESHOLD/SPECIAL INSPECTION REPORT
PROJECT:
CLIENT:
CONTRACTOR:
INSPECTION TYPE:
PROJECT LOCATION:
MEMBERS / AREAS INSPECTED:
DISPOSITION / RESULTS:
GENERAL NOTES:
Respectfully submitted,
Speciality Engineering Consultants, Inc.
D. Mark LeBlanc, PE
Partner
State of Florida:
Registered Professional Engineer: #0035683
Registered Special Inspector: #1177
Form001 ThresholdSpeciallnspec GG 01,04
Dade • Broward • Palm Beach
DAY: • J /-8-t
DATE:
PERMIT No.
TRACKING #:
PERFORMED BY:
f
{
DISTRIBUTION COPY:
1599 S.W. 30th Avenue, Suite #2(1 • Boynton Beach. FL 33426 • Office: 561-752-5440 • Fax: 561-752-5542
' - — 1,4; •
C."
u
SPECIALTY ENGINEERING CONSULTANTS, Inc.
THRESH919/SPECIAL INSPECTION REPORT
PROJECT: jJ5
CLIENT:
CONTRACTOR:
INSPECTION TYPE:
PROJECT LOCATION:
Dade • Broward • Palm Beach
DAY: (ILIA
PERMIT No. 7// .//(/
DATE:
NOS -ON
TRACKING #:
PERFORMED BY:
MEMBERS / AREAS INSPEC,TE
DISPOSITION / RESULTS:
GENERAL NOTES:
1)IJonts
Peyobe
Respectfully submitted,
Speciality Engineering Consultants, Inc.
D. Mark LeBlanc, PE
Partner
State of Florida:
Registered Professional Engineer: #0035683
Registered Special Inspector: #1177
Form001 ThresholdSP,oil0s0ec UGC,'
DISTRIBUTION COPY:
159) S.W. 30th A\ entic, Suite #20 • Boynton Beach. FL 33426 • Office: 561-752-5-1-W i'ax: 561-752-5542
;u I -. S0•,
SPECIALTY ENGINEERING CONSULTANTS, Inc.
THRESHOLD/SPECIAL INSPECTION REPORT
PROJECT: t
CLIENT:
CONTRACTOR:
INSPECTION TYPE:
PROJECT LOCATION:
MEMBERS / AREAS INSPECTED:
Dade • Broward • Palm Beach
DAY: Thu .
DATE: /,./ I l'f / N-1
PERMIT No.
TRACKING #: qo SO
PERFORMED BY: 1-7,e Lu / J � 14 l2)/
DISPOSITION / RESULTS:
/41.A-pri"‘T
GENERAL NOTES:
Respectfully submitted, DISTRIBUTION COPY:
Speciality Engineering Consultants, Inc.
D. Mark LeBlanc, PE
Partner
State of Florida:
Registered Professional Engineer: #0035683
Registered Special Inspector: #1177
Form001 ThresholdSpecialinspec GG 01'04
1599 S.W. 30th Avenue, Suite #20 • Boynton Beach, FL 33426 • Office: 561-752-5440 • Fax: 561-752-5542
SPECIALTY ENGINEERING CONSULTANTS, Inc.
THRESHOLD INSPECTION REPORT
PROJECT:
CLIENT:
CONTRACTOR:
INSPECTION TYPE: B
PROJECT LOCATION: et tee
)
MEMBERS / AREAS INSPECTED:
, I
Dade • Broward • Palm Beach
DAY:
DATE: 513Z-Vyi
PERMIT No,
TRACKING It:
PERFORMED BY:
1X,It 5 T ( e
DISPOSITION / RESULTS:
GENERAL NOTES:
r --tcux Ark, pro c b (a)
Respectfully submitted,
Speciality Engineering Consultants, Inc.
D. Mark LeBlanc, PE
Partner
State of Florida:
Registered Professional Engineer: #0035683
Registered Special Inspector: #1177
Form001 ThresroldSpe0.31Insp-4: 60, 01 04
DISTRIBUTION COPY:
1599 S.W. 30th Avenue. Suite #20 • Boynton Beach, FL 3342f • Office: 561-752-5440 • Fax: 561-752-5542
SPECIALTY ENGINEERING CONSULTANTS, Inc.
THRESHOLD SPECIAL INSPECTION REPORT
PROJECT: CAP,
CLIENT: A /
CONTRACTOR:
INSPECTION TYPE
PROJECT LOCATION: 1;-11 61L.
MEMBERS / AREAS INSPECTED:
DISPOSITION / RESULTS:
GENERAL NOTES:
DAY:
DATE:
Dade • Broward • Palm Beach
ieti4
PERMIT No. /1a- 0/1 /
TRACKING #:
PERFORMED BY:
L_37Lzke 4,11
V�
(AkZ--)1 /1)6( IVCIAY“--/
Respectfully submitted, DISTRIBUTION COPY:
Speciality Engineering Consultants, Inc.
D. Mark LeBlanc, PE
Partner
State of Florida:
Registered Professional Engineer: #0035683
Registered Special Inspector: #1177
Form001 ThresholdSpecallnspec GG 01/04